Walk-thru Coppetl Business Center 1H 9/1~00
2.
3.
4.
6.
7.
8.
9.
12.
1~.
16.
17.
18.
Need valve extension, to bring up to 4' from top of valve stack,
Need plugs for all ball valves on DC in vault (2 vaults).
Need bracing under wheel valves in vault (2 vaults).
Paint top lid blue on 2 vaults.
Olin bypass Jo vaults.
Remove dirt for drainage around 2 vaults.
Paint ali F.H. valve lids red.
All F.H. need blue marker buttons on strut to mark F.H.
Mark all F.H. valves in red on curb.
F.H. need chains to all caps,
Mark WAD in red on curb.
Mark manhole in red on curb.
Mark FLV in red on curb fire line to building.
Valve stack at $.E. of bulJdin~ to city F.H. clean dirt so can work valve.
Remove dLrt at valve to F.H. in nliddle of building on east side or raise valve stack
(too low).
Valve off 12" llne to F. xeeutive Dr. not working.
Executive Dr.
Domestic 2" meter must be on to check for leaks.
below lower fitting to check bypass cutoff.
2" DC nc~ds to be tested and ball valves need plugs.
Valve must work to cot off water to
Clean out bottom of ~ lean
C,l'fY OF COl~.q,U. PI. IJ, LfC WO~g$ DEPAR'I'MF.,NT
09/15/00 09:35 CITY OF COPPELL a CITY OF COPPELL N0.038 Q02
19.
20.
21.
22.
Irrigation meter is set but no 2" DC: at this time-cannot check for l~ak. DC will ~
!
to be tested.
Mark on curb DWS in blue for 2# domestic meter.
Replace valve stack and pad at F,H, northwest of building.
Clean valve stack to City F.H, on west side of bu;I.ding.