WA9302A-LR 961023G
EOTECH N I CA L
E NGINEERING
E
!
NVIRONMENTAL
GEE Consultants, Inc.
10046 Monroe Drive
Dallas, Texas 75229 · (214) 352-5433
Fax (214) 352-6972
REPORT OF CONCRETE MIX INSPECTION
Report Date:
Client:
Project:
Contractor:
Concrete Supplier and Plant:
.~ .oc.,ation of. Placement:
MATERIALS
October 23, 1996 Date Concrete Placed: September 24, 1996
City of Coppell
Village Parkway Pump Station Addition
North Texas Municipal Construction Co., Inc.
DFW Redimix, Inc.
Paving
s~ce/ B,~h w-. INSPECTION DATA
Description (Lbs. / Cu. Yd)
Standard 6"x12"
Area 28.27 Square Inches
Concrete Report No.: 7
Mix Number:
Cement:
Fly Ash:
Coarse Aggregate:
Intermediate .Aggregate:
Fine Aggregate:
Admixtures:
1
2
Added Water:
3,000 Time Sample Batched: unknown
Time Sampled: 5:15 pm
Sample Location: 20' North and 8' East of entry to tank
Track/Ticket No: 307/2894
Temperature:
Ambient Range: 72°F
Concrete Range: 82°F
Slump Range (inches):
Weather Conditions: Cloudy
Time Started: 4:00 pm.
'Time Completed: 6:00 pm
0 Gallons Sample Air Content (%): 2
Total Cubic Yards Placed: 69
Required Strength (Lbs./sq.in.): 3,000 psi
Specimen
Number
VPP 25
VPP 26
VPP 27
VPP 28
Test Methods 1Utilized
ASTM C-31,C-39,C-143
Remarks and/or Distribution:
Measured
s~rap (in.)
Age Date Total Load Compresslye Str~mgth
(Days) Tested (Lbs.) (L,bs./Sq./n.)
7 10/01/96 82,980 2,940
7 10/01/96 84,720 3,000
28 10/22/96 100,800 3,570
28 10/22/96 107,060 3,780
Fracture Regular
(Unless Noled Oll~rwise) Cylinders Made By: D.F.
Remarks
cc:
Mr. Larry Davis - City of Coppell
Mr. Mike Diagre - North Texas Municipal Construction Co.
Mr. Gary Hendricks - Shimek, Jacobs and Finklea
Consultante, xnc.
Rev~eved