WA9302A-LR 961008G
EOTECH N ICAL
E NGINEERING
E NVIRONMENTAL
GEE Consultants, Inc.
10046 Monroe Drive
· Dallas, Texas 75229 · (214) 352-5433
· Fax (214) 352-6972
REPORT OF CONCRETE MIX INSPECTION
Report Date:
Client:
Project:
Contractor:
Concrete Supplier and Plant:
Location of Placement:
MATERIALS
October 8, 1996 Date Concrete Placed:. June 28, 1996
City of Coppell
Village Parkway Pump Station Addition
North Texas Municipal Construction Co., Inc.
DFW Redimix, Inc.
Paving
s,~cc/ na~h w~. INSPECTION DATA
Description (Lbs. / Cu. Yd)
Mix Number: 3,000
Cement:
Fly Ash:
Coarse Aggregate:
Intermediate Aggregate:
Fine Aggregate:
Admixtures:
1
2
Added Water: 0 Gallons
Standard 6"x12"
Area 28.27 Square Inches
Concrete Repor~ No.: 7
Time Sample Batched: unknown
Time Sampled: 5:15 pm
Sample Location: 20' North and 8' East of entry to tank
Truck/Ticket No: 307/2894
Temperature:
Ambient Range: 72°F
Concrete Range: 82°F
Slump Range (inches): 5'
Weather Conditions: Cloudy
Time Started: 4:00 pro.
Time Completed: 6:00 pm
Sample Air Content (%): 2
Total Cubic Yards Placed: 69
Required Strength (Lbs./sq.in.): 3,000 psi
Specimen Measured Age Date
Number Slump (in.) (Days) Tested
VPP 25 7 10/01/96
VPP 26 7 10/01/96
VPP 27 28 10/22/96
VPP 28 28 10/22/96
Test Methods Utilized Fracture Regular
ASTM C-31,C-39,C-143 (Unless Noted Oatenvise)
Remarks and/or Distribution:
T~L~
82,980
84,720
Compressive Strength
(Lbs./Sq.ln.)
2,940
3,000
Cylinders Made By: D.F.
Re~rB
CO:
Mr. Larry Davis - City of Coppeil
Mr. Mike Diagre - North Texas Municipal Construction Co.
Mr. Gary Hendricks - Shimek, Jacobs and Finklea
~,ll ~on~ulttuts,
Rev£ewed by: ~ ~