Park West Crossing- LR141119Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0361
11/19/14
12/18/14 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0824
1235
Plant:
Ticket No.:
P259
25977171
Field Test Data
Test
Air Content (%):
Result Specification
4 3-5
3.3 3-6
55
33
146.0
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/19/14 0915
Daniel Duran
Clear
270/500 10
5
0
Sample #3, see attached sketchSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
3 1 4.00 12.57 11/26/14 7 53,030 5 4,220
3 2 4.00 12.57 12/17/14 28 68,000 4 5,410
3 3 4.00 12.57 12/17/14 28 64,140 4 5,100
3 4 4.00 12.57 12/17/14 28 67,650 2 5,380
Average (28 days) 5,300
3 5 4.00 12.57 01/14/15 56
Comments:Average compressive strength of 28 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Daniel Duran
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 3 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0361
11/19/14
12/18/14 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
1015
1159
Plant:
Ticket No.:
P259
25977391
Field Test Data
Test
Air Content (%):
Result Specification
4 1/4 3-5
3.6 3-6
54
38
145.9
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/19/14 1050
Daniel Duran
Clear
390/500 10
0
0
Sample #4, see attached sketchSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
4 1 4.00 12.57 11/26/14 7 51,610 5 4,110
4 2 4.00 12.57 12/17/14 28 70,200 4 5,590
4 3 4.00 12.57 12/17/14 28 68,110 4 5,420
4 4 4.00 12.57 12/17/14 28 65,220 4 5,190
Average (28 days) 5,400
4 5 4.00 12.57 01/14/15 56
Comments:Average compressive strength of 28 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Daniel Duran
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 4 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0361
11/19/14
12/18/14 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
1033
1375
Plant:
Ticket No.:
P259
25977435
Field Test Data
Test
Air Content (%):
Result Specification
4 1/4 3-5
3.6 3-6
58
43
145.0
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/19/14 1125
Daniel Duran
Clear
420/500 10
0
0
Sample #5, see attached sketchSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
5 1 4.00 12.57 11/26/14 7 66,750 5 5,310
5 2 4.00 12.57 12/17/14 28 78,020 4 6,210
5 3 4.00 12.57 12/17/14 28 76,830 2 6,110
5 4 4.00 12.57 12/17/14 28 80,980 4 6,440
Average (28 days) 6,250
5 5 4.00 12.57 01/14/15 56
Comments:Average compressive strength of 28 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey James D. Baze
Project Manager
Structure Tone Southwest
Reviewed By:
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Daniel Duran
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 5 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0361
11/19/14
01/15/15 Revision 2 - 56-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0504
1235
Plant:
Ticket No.:
P259
25976906
Field Test Data
Test
Air Content (%):
Result Specification
3 1/2 3-5
3.9 3-6
54
36
145.0
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/19/14 0548
Daniel Duran
Clear
90/500 10
0
0
Sample #1, see attached sketchSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
1 1 4.00 12.57 11/26/14 7 67,250 4 5,350
1 2 4.00 12.57 12/17/14 28 79,440 5 6,320
1 3 4.00 12.57 12/17/14 28 76,700 4 6,100
1 4 4.00 12.57 12/17/14 28 81,820 4 6,510
Average (28 days) 6,310
1 5 4.00 12.57 01/14/15 56 82,850 3 6,590
Comments:Compressive strength of 56 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Daniel Duran
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 1 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0361
11/19/14
01/15/15 Revision 2 - 56-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0622
1377
Plant:
Ticket No.:
P259
25976992
Field Test Data
Test
Air Content (%):
Result Specification
4 3-5
3.6 3-6
52
38
145.0
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/19/14 0715
Daniel Duran
Cloudy
170/500 10
0
0
Sample #2, see attached sketchSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
2 1 4.00 12.57 11/26/14 7 61,760 4 4,920
2 2 4.00 12.57 12/17/14 28 77,260 2 6,150
2 3 4.00 12.57 12/17/14 28 80,670 4 6,420
2 4 4.00 12.57 12/17/14 28 77,890 4 6,200
Average (28 days) 6,260
2 5 4.00 12.57 01/14/15 56 84,300 4 6,710
Comments:Compressive strength of 56 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Daniel Duran
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 2 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0361
11/19/14
01/15/15 Revision 2 - 56-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0824
1235
Plant:
Ticket No.:
P259
25977171
Field Test Data
Test
Air Content (%):
Result Specification
4 3-5
3.3 3-6
55
33
146.0
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/19/14 0915
Daniel Duran
Clear
270/500 10
5
0
Sample #3, see attached sketchSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
3 1 4.00 12.57 11/26/14 7 53,030 5 4,220
3 2 4.00 12.57 12/17/14 28 68,000 4 5,410
3 3 4.00 12.57 12/17/14 28 64,140 4 5,100
3 4 4.00 12.57 12/17/14 28 67,650 2 5,380
Average (28 days) 5,300
3 5 4.00 12.57 01/14/15 56 73,080 5 5,820
Comments:Compressive strength of 56 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Daniel Duran
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 3 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0361
11/19/14
01/15/15 Revision 2 - 56-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
1015
1159
Plant:
Ticket No.:
P259
25977391
Field Test Data
Test
Air Content (%):
Result Specification
4 1/4 3-5
3.6 3-6
54
38
145.9
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/19/14 1050
Daniel Duran
Clear
390/500 10
0
0
Sample #4, see attached sketchSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
4 1 4.00 12.57 11/26/14 7 51,610 5 4,110
4 2 4.00 12.57 12/17/14 28 70,200 4 5,590
4 3 4.00 12.57 12/17/14 28 68,110 4 5,420
4 4 4.00 12.57 12/17/14 28 65,220 4 5,190
Average (28 days) 5,400
4 5 4.00 12.57 01/14/15 56 75,160 3 5,980
Comments:Compressive strength of 56 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Daniel Duran
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 4 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0361
11/19/14
01/15/15 Revision 2 - 56-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
1033
1375
Plant:
Ticket No.:
P259
25977435
Field Test Data
Test
Air Content (%):
Result Specification
4 1/4 3-5
3.6 3-6
58
43
145.0
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/19/14 1125
Daniel Duran
Clear
420/500 10
0
0
Sample #5, see attached sketchSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
5 1 4.00 12.57 11/26/14 7 66,750 5 5,310
5 2 4.00 12.57 12/17/14 28 78,020 4 6,210
5 3 4.00 12.57 12/17/14 28 76,830 2 6,110
5 4 4.00 12.57 12/17/14 28 80,980 4 6,440
Average (28 days) 6,250
5 5 4.00 12.57 01/14/15 56 84,410 2 6,720
Comments:Compressive strength of 56 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey James D. Baze
Project Manager
Structure Tone Southwest
Reviewed By:
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Daniel Duran
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 5 of 5CR0001, 11-16-12, Rev.6
REINFORCING STEEL OBSERVATIONS REPORT
Report Number:94141126.0362
Service Date:11/20/14 8901 Carpenter Frwy., Suite 100
Report Date:11/26/14 Dallas, TX 75247
214-630-1010 Reg No: F-3272
Client Project
ML Realty Partners Park West Crossing
Attn: Timothy Geisler 910, 920 & 930 Freeport Pkwy
One Pierce Pl Ste 450W & 631 Southwestern Blvd
Itasca, IL 60143 Coppell, TX
Project Number: 94141126
Services: Reinforcing steel (rebar) placement observation.
Terracon Rep.: Vincent Green
Reported To:
Contractor:Structure Tone Southwest
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike
Toole(1) Structure Tone Southwest Inc., Robin
Povey
Reviewed By:____________________________________
James D. Baze
Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to
the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
R940003, 07-01-12, Rev.0 Page 1 of 1 dgr
PROJECT DATA
Drawings Utilized:C6.01/Paving Detail, dated 04/23/14
Locations/Items Observed:Paving, see attached sketch
Test Method:Visual Observation
REPORT OF OBSERVATION
ITEMS OBSERVED CORRECT INCORRECT ITEMS OBSERVED CORRECT INCORRECT ITEMS OBSERVED CORRECT INCORRECT
Placing Drawings
Approved X Bar Length and Shape X Column Tie Spacing & Type
Bar Size X Proper Bar Placement X Stirrup Spacing & Type
Bar Grade X Properly Tied X Welded Splices
Rebar Clean X Dowel Bars in Place Mechanical Splices
Trash & Debris Removed X Proper Bar Supports X Lapped Splices X
Number of Bars X Proper Cover/Clearance X
Discrepancies/Comments:
No discrepancies were noted at the time of this observation.
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0363
11/20/14
12/09/14
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0409
1185
Plant:
Ticket No.:
259
25978048
Field Test Data
Test
Air Content (%):
Result Specification
5 3-5
4.5 3-6
67
42
142.4
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/20/14 0500
Vincent Green
40/500 10
0
0
Sample #1, see attached sketchSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
1 1 4.00 12.57 12/01/14 11 58,360 5 4,640
1 2 4.00 12.57 12/18/14 28
1 3 4.00 12.57 12/18/14 28
1 4 4.00 12.57 12/18/14 28
1 5 4.00 12.57 01/15/15 56
Comments:
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 1 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0363
11/20/14
12/09/14
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0605
1396
Plant:
Ticket No.:
259
25978170
Field Test Data
Test
Air Content (%):
Result Specification
4 3/4 3-5
3.2 3-6
57
41
149.6
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/20/14 0702
Vincent Green
140/500 10
0
0
Sample #2, see attached sketchSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
2 1 4.00 12.57 12/01/14 11 61,970 2 4,930
2 2 4.00 12.57 12/18/14 28
2 3 4.00 12.57 12/18/14 28
2 4 4.00 12.57 12/18/14 28
2 5 4.00 12.57 01/15/15 56
Comments:
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 2 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0363
11/20/14
12/09/14
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0805
1005
Plant:
Ticket No.:
259
25978358
Field Test Data
Test
Air Content (%):
Result Specification
4 1/2 3-5
3.7 3-6
60
45
148.4
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/20/14 0850
Vincent Green
250/500 10
0
0
Sample #3, see attached sketchSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
3 1 4.00 12.57 12/01/14 11 56,530 4 4,500
3 2 4.00 12.57 12/18/14 28
3 3 4.00 12.57 12/18/14 28
3 4 4.00 12.57 12/18/14 28
3 5 4.00 12.57 01/15/15 56
Comments:
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 3 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0363
11/20/14
12/09/14
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
1005
1333
Plant:
Ticket No.:
259
25978572
Field Test Data
Test
Air Content (%):
Result Specification
4 3/4 3-5
3.5 3-6
69
58
148.8
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/20/14 1107
Vincent Green
340/500 10
0
0
Sample #4, see attached sketchSample Location:
Placement Method:340/500
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
4 1 4.00 12.57 12/01/14 11 54,240 2 4,320
4 2 4.00 12.57 12/18/14 28
4 3 4.00 12.57 12/18/14 28
4 4 4.00 12.57 12/18/14 28
4 5 4.00 12.57 01/15/15 56
Comments:
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 4 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0363
11/20/14
12/09/14
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
1157
1333
Plant:
Ticket No.:
259
25978756
Field Test Data
Test
Air Content (%):
Result Specification
4 1/2 3-5
3.4 3-6
70
65
149.2
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/20/14 1253
Vincent Green
430/500 10
0
0
Sample #5, see attached sketchSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
5 1 4.00 12.57 12/01/14 11 52,090 5 4,150
5 2 4.00 12.57 12/18/14 28
5 3 4.00 12.57 12/18/14 28
5 4 4.00 12.57 12/18/14 28
5 5 4.00 12.57 01/15/15 56
Comments:
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey James D. Baze
Project Manager
Structure Tone Southwest
Reviewed By:
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 5 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0363
11/20/14
12/19/14 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0409
1185
Plant:
Ticket No.:
259
25978048
Field Test Data
Test
Air Content (%):
Result Specification
5 3-5
4.5 3-6
67
42
142.4
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/20/14 0500
Vincent Green
40/500 10
0
0
Sample #1, see attached sketchSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
1 1 4.00 12.57 12/01/14 11 58,360 5 4,640
1 2 4.00 12.57 12/18/14 28 61,940 5 4,930
1 3 4.00 12.57 12/18/14 28 67,030 4 5,330
1 4 4.00 12.57 12/18/14 28 58,390 5 4,650
Average (28 days) 4,970
1 5 4.00 12.57 01/15/15 56
Comments:Average compressive strength of 28 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 1 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0363
11/20/14
12/19/14 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0605
1396
Plant:
Ticket No.:
259
25978170
Field Test Data
Test
Air Content (%):
Result Specification
4 3/4 3-5
3.2 3-6
57
41
149.6
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/20/14 0702
Vincent Green
140/500 10
0
0
Sample #2, see attached sketchSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
2 1 4.00 12.57 12/01/14 11 61,970 2 4,930
2 2 4.00 12.57 12/18/14 28 63,370 5 5,040
2 3 4.00 12.57 12/18/14 28 63,960 5 5,090
2 4 4.00 12.57 12/18/14 28 60,600 5 4,820
Average (28 days) 4,980
2 5 4.00 12.57 01/15/15 56
Comments:Average compressive strength of 28 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 2 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0363
11/20/14
12/19/14 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0805
1005
Plant:
Ticket No.:
259
25978358
Field Test Data
Test
Air Content (%):
Result Specification
4 1/2 3-5
3.7 3-6
60
45
148.4
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/20/14 0850
Vincent Green
250/500 10
0
0
Sample #3, see attached sketchSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
3 1 4.00 12.57 12/01/14 11 56,530 4 4,500
3 2 4.00 12.57 12/18/14 28 56,570 4 4,500
3 3 4.00 12.57 12/18/14 28 59,170 5 4,710
3 4 4.00 12.57 12/18/14 28 55,790 5 4,440
Average (28 days) 4,550
3 5 4.00 12.57 01/15/15 56
Comments:Average compressive strength of 28 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 3 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0363
11/20/14
12/19/14 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
1005
1333
Plant:
Ticket No.:
259
25978572
Field Test Data
Test
Air Content (%):
Result Specification
4 3/4 3-5
3.5 3-6
69
58
148.8
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/20/14 1107
Vincent Green
340/500 10
0
0
Sample #4, see attached sketchSample Location:
Placement Method:340/500
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
4 1 4.00 12.57 12/01/14 11 54,240 2 4,320
4 2 4.00 12.57 12/18/14 28 54,520 5 4,340
4 3 4.00 12.57 12/18/14 28 55,360 5 4,410
4 4 4.00 12.57 12/18/14 28 51,780 4 4,120
Average (28 days) 4,290
4 5 4.00 12.57 01/15/15 56
Comments:Average compressive strength of 28 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 4 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0363
11/20/14
12/19/14 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
1157
1333
Plant:
Ticket No.:
259
25978756
Field Test Data
Test
Air Content (%):
Result Specification
4 1/2 3-5
3.4 3-6
70
65
149.2
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/20/14 1253
Vincent Green
430/500 10
0
0
Sample #5, see attached sketchSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
5 1 4.00 12.57 12/01/14 11 52,090 5 4,150
5 2 4.00 12.57 12/18/14 28 56,780 4 4,520
5 3 4.00 12.57 12/18/14 28 63,350 4 5,040
5 4 4.00 12.57 12/18/14 28 57,160 4 4,550
Average (28 days) 4,700
5 5 4.00 12.57 01/15/15 56
Comments:Average compressive strength of 28 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey James D. Baze
Project Manager
Structure Tone Southwest
Reviewed By:
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 5 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0363
11/20/14
01/16/15 Revision 2 - 56-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0409
1185
Plant:
Ticket No.:
259
25978048
Field Test Data
Test
Air Content (%):
Result Specification
5 3-5
4.5 3-6
67
42
142.4
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/20/14 0500
Vincent Green
40/500 10
0
0
Sample #1, see attached sketchSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
1 1 4.00 12.57 12/01/14 11 58,360 5 4,640
1 2 4.00 12.57 12/18/14 28 61,940 5 4,930
1 3 4.00 12.57 12/18/14 28 67,030 4 5,330
1 4 4.00 12.57 12/18/14 28 58,390 5 4,650
Average (28 days) 4,970
1 5 4.00 12.57 01/15/15 56 68,150 5 5,420
Comments:Compressive strength of 56 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 1 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0363
11/20/14
01/16/15 Revision 2 - 56-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0605
1396
Plant:
Ticket No.:
259
25978170
Field Test Data
Test
Air Content (%):
Result Specification
4 3/4 3-5
3.2 3-6
57
41
149.6
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/20/14 0702
Vincent Green
140/500 10
0
0
Sample #2, see attached sketchSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
2 1 4.00 12.57 12/01/14 11 61,970 2 4,930
2 2 4.00 12.57 12/18/14 28 63,370 5 5,040
2 3 4.00 12.57 12/18/14 28 63,960 5 5,090
2 4 4.00 12.57 12/18/14 28 60,600 5 4,820
Average (28 days) 4,980
2 5 4.00 12.57 01/15/15 56 70,790 2 5,630
Comments:Compressive strength of 56 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 2 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0363
11/20/14
01/16/15 Revision 2 - 56-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0805
1005
Plant:
Ticket No.:
259
25978358
Field Test Data
Test
Air Content (%):
Result Specification
4 1/2 3-5
3.7 3-6
60
45
148.4
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/20/14 0850
Vincent Green
250/500 10
0
0
Sample #3, see attached sketchSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
3 1 4.00 12.57 12/01/14 11 56,530 4 4,500
3 2 4.00 12.57 12/18/14 28 56,570 4 4,500
3 3 4.00 12.57 12/18/14 28 59,170 5 4,710
3 4 4.00 12.57 12/18/14 28 55,790 5 4,440
Average (28 days) 4,550
3 5 4.00 12.57 01/15/15 56 60,190 4 4,790
Comments:Compressive strength of 56 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 3 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0363
11/20/14
01/16/15 Revision 2 - 56-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
1005
1333
Plant:
Ticket No.:
259
25978572
Field Test Data
Test
Air Content (%):
Result Specification
4 3/4 3-5
3.5 3-6
69
58
148.8
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/20/14 1107
Vincent Green
340/500 10
0
0
Sample #4, see attached sketchSample Location:
Placement Method:340/500
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
4 1 4.00 12.57 12/01/14 11 54,240 2 4,320
4 2 4.00 12.57 12/18/14 28 54,520 5 4,340
4 3 4.00 12.57 12/18/14 28 55,360 5 4,410
4 4 4.00 12.57 12/18/14 28 51,780 4 4,120
Average (28 days) 4,290
4 5 4.00 12.57 01/15/15 56 55,890 4 4,450
Comments:Compressive strength of 56 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 4 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0363
11/20/14
01/16/15 Revision 2 - 56-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
1157
1333
Plant:
Ticket No.:
259
25978756
Field Test Data
Test
Air Content (%):
Result Specification
4 1/2 3-5
3.4 3-6
70
65
149.2
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/20/14 1253
Vincent Green
430/500 10
0
0
Sample #5, see attached sketchSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
5 1 4.00 12.57 12/01/14 11 52,090 5 4,150
5 2 4.00 12.57 12/18/14 28 56,780 4 4,520
5 3 4.00 12.57 12/18/14 28 63,350 4 5,040
5 4 4.00 12.57 12/18/14 28 57,160 4 4,550
Average (28 days) 4,700
5 5 4.00 12.57 01/15/15 56 69,210 5 5,510
Comments:Compressive strength of 56 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey James D. Baze
Project Manager
Structure Tone Southwest
Reviewed By:
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 5 of 5CR0001, 11-16-12, Rev.6
REINFORCING STEEL OBSERVATIONS REPORT
Report Number:94141126.0365
Service Date:11/21/14 8901 Carpenter Frwy., Suite 100
Report Date:12/01/14 Dallas, TX 75247
214-630-1010 Reg No: F-3272
Client Project
ML Realty Partners Park West Crossing
Attn: Timothy Geisler 910, 920 & 930 Freeport Pkwy
One Pierce Pl Ste 450W & 631 Southwestern Blvd
Itasca, IL 60143 Coppell, TX
Project Number: 94141126
Services: Reinforcing steel (rebar) placement observation.
Terracon Rep.: Vincent Green
Reported To:
Contractor:Structure Tone Southwest
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike
Toole(1) Structure Tone Southwest Inc., Robin
Povey
Reviewed By:____________________________________
James D. Baze
Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to
the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
R940003, 07-01-12, Rev.0 Page 1 of 1 dgr
PROJECT DATA
Drawings Utilized:C6.01/Paving Detail, dated 04/23/14
Locations/Items Observed:Paving, see attached sketch
Test Method:Visual Observation
REPORT OF OBSERVATION
ITEMS OBSERVED CORRECT INCORRECT ITEMS OBSERVED CORRECT INCORRECT ITEMS OBSERVED CORRECT INCORRECT
Placing Drawings
Approved X Bar Length and Shape X Column Tie Spacing & Type
Bar Size X Proper Bar Placement X Stirrup Spacing & Type
Bar Grade X Properly Tied X Welded Splices
Rebar Clean X Dowel Bars in Place X Mechanical Splices
Trash & Debris Removed X Proper Bar Supports X Lapped Splices X
Number of Bars X Proper Cover/Clearance X
Discrepancies/Comments:
No discrepancies were noted at the time of this observation.
*Concrete placement was cancelled due to weather.
CONCRETE PLACEMENT OBSERVATION REPORT
Report Number:94141126.0369
Service Date:11/24/14 8901 Carpenter Frwy., Suite 100
Report Date:12/03/14 Dallas, TX 75247
214-630-1010 Reg No: F-3272
Client Project
ML Realty Partners Park West Crossing
Attn: Timothy Geisler 910, 920 & 930 Freeport Pkwy
One Pierce Pl Ste 450W & 631 Southwestern Blvd
Itasca, IL 60143 Coppell, TX
Project Number: 94141126
Services: Concrete placement observation.
Terracon Rep.: Bernardino Rojas
Reported To:
Contractor:Structure Tone Southwest
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike
Toole(1) Structure Tone Southwest Inc., Robin
Povey
Reviewed By:____________________________________
James D. Baze
Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to
the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
BC0001, 10-16-13, Rev.10 Page 1 of 1 tp
On this date, Terracon's representative arrived at the above referenced job site as scheduled for concrete placement observation. After
arriving at the job site, Terracon's representative was notified that the scheduled concrete placement was cancelled due to weather.
REINFORCING STEEL OBSERVATIONS REPORT
Report Number:94141126.0370
Service Date:11/24/14 8901 Carpenter Frwy., Suite 100
Report Date:12/03/14 Dallas, TX 75247
214-630-1010 Reg No: F-3272
Client Project
ML Realty Partners Park West Crossing
Attn: Timothy Geisler 910, 920 & 930 Freeport Pkwy
One Pierce Pl Ste 450W & 631 Southwestern Blvd
Itasca, IL 60143 Coppell, TX
Project Number: 94141126
Services: Reinforcing steel (rebar) placement observation.
Terracon Rep.: Daniel Duran
Reported To:
Contractor:Structure Tone Southwest
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike
Toole(1) Structure Tone Southwest Inc., Robin
Povey
Reviewed By:____________________________________
James D. Baze
Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to
the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
R940003, 07-01-12, Rev.0 Page 1 of 1 tp
PROJECT DATA
Drawings Utilized:Civil Sheets/Details: C6.01/4” Thick, #3 @ 18” OCEW, dated 10/15/13
Locations/Items Observed:Building D, Sidewalk, see attached sketch
Test Method:Visual Observation
REPORT OF OBSERVATION
ITEMS OBSERVED CORRECT INCORRECT ITEMS OBSERVED CORRECT INCORRECT ITEMS OBSERVED CORRECT INCORRECT
Placing Drawings
Approved X Bar Length and Shape X Column Tie Spacing & Type
Bar Size X Proper Bar Placement X Stirrup Spacing & Type
Bar Grade X Properly Tied X Welded Splices
Rebar Clean X Dowel Bars in Place X Mechanical Splices
Trash & Debris Removed X Proper Bar Supports X Lapped Splices X
Number of Bars X Proper Cover/Clearance X
Discrepancies/Comments:
No discrepancies were noted at the time of this observation.
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0371
11/24/14
12/04/14
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
10J11504
Redi-Mix
Material Information
0720
1006
Plant:
Ticket No.:
136
25980064
Field Test Data
Test
Air Content (%):
Result Specification
4 1/2 3-5
4.2 3-6
58
53
147.8
3,000
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/24/14 0800
Daniel Duran
Clear
30/100 10
0
0
See Placement LocationSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Building D, Sidewalks, see attached
sketch
Placement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
1 1 4.00 12.57 12/01/14 7 41,850 2 3,330
1 2 4.00 12.57 12/22/14 28
1 3 4.00 12.57 12/22/14 28
1 4 4.00 12.57 12/22/14 28
1 5 4.00 12.57 01/19/15 56
Comments:
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey James D. Baze
Project Manager
Structure Tone Southwest
Reviewed By:
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Daniel Duran
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 1 of 1CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0371
11/24/14
12/23/14 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
10J11504
Redi-Mix
Material Information
0720
1006
Plant:
Ticket No.:
136
25980064
Field Test Data
Test
Air Content (%):
Result Specification
4 1/2 3-5
4.2 3-6
58
53
147.8
3,000
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/24/14 0800
Daniel Duran
Clear
30/100 10
0
0
See Placement LocationSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Building D, Sidewalks, see attached
sketch
Placement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
1 1 4.00 12.57 12/01/14 7 41,850 2 3,330
1 2 4.00 12.57 12/22/14 28 54,130 5 4,310
1 3 4.00 12.57 12/22/14 28 56,870 4 4,530
1 4 4.00 12.57 12/22/14 28 54,500 4 4,340
Average (28 days) 4,390
1 5 4.00 12.57 01/19/15 56
Comments:Average compressive strength of 28 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey James D. Baze
Project Manager
Structure Tone Southwest
Reviewed By:
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Daniel Duran
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 1 of 1CR0001, 11-16-12, Rev.6
FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
94141126.0372
11/24/14
12/03/14
8901 Carpenter Frwy., Suite 100
Dallas, TX 75247
214-630-1010 Reg No: F-3272
Client Project
ML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
Park West Crossing
910, 920 & 930 Freeport Pkwy
& 631 Southwestern Blvd
Coppell, TX
Project Number:94141126
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description (pcf)Test Method
98-2/+21114.614.094141126.0359 Recycled crushed concrete with
clayey sand
ASTM D698
Field Test Data
No.Test Location Elev.No.
Test Lift /Mat.Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in)(pcf)(pcf)(pcf)
Approaches
2187 North side Final 1 BS 129.3 17.2 15.3 112.1 98
2188 West Side - South Final 1 BS 130.3 16.6 14.6 113.7 99
2189 West Side - Center Final 1 BS 131.2 16.0 13.9 115.2 100+
2190 West Side - North Final 1 BS 129.7 16.9 15.0 112.8 98
Comments:
Datum:Serial No:32769
Test and/or retest results on this report meet project requirements as noted above.
BS - Backscatter
Perform in-place density and moisture content tests to determine degree of compaction and material moisture
condition.
Services:
Reported To:
Contractor:
Mike, Structure Tone
Structure Tone Southwest
James D. Baze
Project Manager
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Reviewed By:
Terracon Rep.: Craig Blackwell
ASTM D6938Test Methods:
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1
REINFORCING STEEL OBSERVATIONS REPORT
Report Number:94141126.0373
Service Date:11/25/14 8901 Carpenter Frwy., Suite 100
Report Date:12/03/14 Dallas, TX 75247
214-630-1010 Reg No: F-3272
Client Project
ML Realty Partners Park West Crossing
Attn: Timothy Geisler 910, 920 & 930 Freeport Pkwy
One Pierce Pl Ste 450W & 631 Southwestern Blvd
Itasca, IL 60143 Coppell, TX
Project Number: 94141126
Services: Reinforcing steel (rebar) placement observation.
Terracon Rep.: Daniel Duran
Reported To:
Contractor:Structure Tone Southwest
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike
Toole(1) Structure Tone Southwest Inc., Robin
Povey
Reviewed By:____________________________________
James D. Baze
Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to
the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
R940003, 07-01-12, Rev.0 Page 1 of 1 dgr
PROJECT DATA
Drawings Utilized:C6.01/Legend, dated 11/15/2013
Locations/Items Observed:Paving, see attached sketch
Test Method:Visual Observation
REPORT OF OBSERVATION
ITEMS OBSERVED CORRECT INCORRECT ITEMS OBSERVED CORRECT INCORRECT ITEMS OBSERVED CORRECT INCORRECT
Placing Drawings
Approved X Bar Length and Shape X Column Tie Spacing & Type
Bar Size X Proper Bar Placement X Stirrup Spacing & Type
Bar Grade X Properly Tied X Welded Splices
Rebar Clean X Dowel Bars in Place X Mechanical Splices
Trash & Debris Removed X Proper Bar Supports X Lapped Splices X
Number of Bars X Proper Cover/Clearance X
Discrepancies/Comments:
No discrepancies were noted at the time of this observation.
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0374
11/25/14
12/05/14
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0412
1256
Plant:
Ticket No.:
259
25980908
Field Test Data
Test
Air Content (%):
Result Specification
4 3-5
4.2 3-6
57
38
146.0
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/25/14 0450
Daniel Duran
Clear
80/500 10
0
0
Sample #1, see attached sketchSample Location:
Placement Method:Pump
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
1 1 4.00 12.57 12/02/14 7 61,830 5 4,920
1 2 4.00 12.57 12/23/14 28
1 3 4.00 12.57 12/23/14 28
1 4 4.00 12.57 12/23/14 28
1 5 4.00 12.57 01/20/15 56
Comments:
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Daniel Duran
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 1 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0374
11/25/14
12/05/14
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0606
1377
Plant:
Ticket No.:
259
25981006
Field Test Data
Test
Air Content (%):
Result Specification
4 1/4 3-5
4.6 3-6
59
40
145.8
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/25/14 0700
Daniel Duran
Clear
190/500 10
0
0
Sample #2, see attached sketchSample Location:
Placement Method:Pump
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
2 1 4.00 12.57 12/02/14 7 62,870 4 5,000
2 2 4.00 12.57 12/23/14 28
2 3 4.00 12.57 12/23/14 28
2 4 4.00 12.57 12/23/14 28
2 5 4.00 12.57 01/20/15 56
Comments:
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Daniel Duran
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 2 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0374
11/25/14
12/05/14
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0844
1377
Plant:
Ticket No.:
259
25981230
Field Test Data
Test
Air Content (%):
Result Specification
4 1/2 3-5
4.7 3-6
59
46
145.0
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/25/14 0928
Daniel Duran
Clear
300/500 10
10
0
Sample #3, see attached sketchSample Location:
Placement Method:Pump
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
3 1 4.00 12.57 12/02/14 7 65,650 2 5,220
3 2 4.00 12.57 12/23/14 28
3 3 4.00 12.57 12/23/14 28
3 4 4.00 12.57 12/23/14 28
3 5 4.00 12.57 01/20/15 56
Comments:
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Daniel Duran
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 3 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0374
11/25/14
12/05/14
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0944
1286
Plant:
Ticket No.:
259
25981339
Field Test Data
Test
Air Content (%):
Result Specification
4 3-5
4.4 3-6
58
44
144.9
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/25/14 1045
Daniel Duran
Clear
380/500 10
0
0
Sample #4, see attached sketchSample Location:
Placement Method:Pump
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
4 1 4.00 12.57 12/02/14 7 58,260 5 4,640
4 2 4.00 12.57 12/23/14 28
4 3 4.00 12.57 12/23/14 28
4 4 4.00 12.57 12/23/14 28
4 5 4.00 12.57 01/20/15 56
Comments:
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Daniel Duran
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 4 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0374
11/25/14
12/05/14
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
1059
1159
Plant:
Ticket No.:
259
25981470
Field Test Data
Test
Air Content (%):
Result Specification
4 3-5
4.6 3-6
60
57
145.8
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/25/14 1155
Daniel Duran
Clear
450/500 10
0
0
Sample #5, see attached sketchSample Location:
Placement Method:Pump
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
5 1 4.00 12.57 12/02/14 7 62,630 5 4,980
5 2 4.00 12.57 12/23/14 28
5 3 4.00 12.57 12/23/14 28
5 4 4.00 12.57 12/23/14 28
5 5 4.00 12.57 01/20/15 56
Comments:
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey James D. Baze
Project Manager
Structure Tone Southwest
Reviewed By:
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Daniel Duran
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 5 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0374
11/25/14
12/24/14 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0412
1256
Plant:
Ticket No.:
259
25980908
Field Test Data
Test
Air Content (%):
Result Specification
4 3-5
4.2 3-6
57
38
146.0
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/25/14 0450
Daniel Duran
Clear
80/500 10
0
0
Sample #1, see attached sketchSample Location:
Placement Method:Pump
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
1 1 4.00 12.57 12/02/14 7 61,830 5 4,920
1 2 4.00 12.57 12/23/14 28 76,790 4 6,110
1 3 4.00 12.57 12/23/14 28 71,770 3 5,710
1 4 4.00 12.57 12/23/14 28 76,760 4 6,110
Average (28 days) 5,980
1 5 4.00 12.57 01/20/15 56
Comments:Average compressive strength of 28 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Daniel Duran
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 1 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0374
11/25/14
12/24/14 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0606
1377
Plant:
Ticket No.:
259
25981006
Field Test Data
Test
Air Content (%):
Result Specification
4 1/4 3-5
4.6 3-6
59
40
145.8
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/25/14 0700
Daniel Duran
Clear
190/500 10
0
0
Sample #2, see attached sketchSample Location:
Placement Method:Pump
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
2 1 4.00 12.57 12/02/14 7 62,870 4 5,000
2 2 4.00 12.57 12/23/14 28 75,180 3 5,980
2 3 4.00 12.57 12/23/14 28 78,860 4 6,280
2 4 4.00 12.57 12/23/14 28 74,160 4 5,900
Average (28 days) 6,050
2 5 4.00 12.57 01/20/15 56
Comments:Average compressive strength of 28 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Daniel Duran
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 2 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0374
11/25/14
12/24/14 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0844
1377
Plant:
Ticket No.:
259
25981230
Field Test Data
Test
Air Content (%):
Result Specification
4 1/2 3-5
4.7 3-6
59
46
145.0
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/25/14 0928
Daniel Duran
Clear
300/500 10
10
0
Sample #3, see attached sketchSample Location:
Placement Method:Pump
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
3 1 4.00 12.57 12/02/14 7 65,650 2 5,220
3 2 4.00 12.57 12/23/14 28 76,910 4 6,120
3 3 4.00 12.57 12/23/14 28 71,170 5 5,660
3 4 4.00 12.57 12/23/14 28 75,010 5 5,970
Average (28 days) 5,920
3 5 4.00 12.57 01/20/15 56
Comments:Average compressive strength of 28 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Daniel Duran
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 3 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0374
11/25/14
12/24/14 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0944
1286
Plant:
Ticket No.:
259
25981339
Field Test Data
Test
Air Content (%):
Result Specification
4 3-5
4.4 3-6
58
44
144.9
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/25/14 1045
Daniel Duran
Clear
380/500 10
0
0
Sample #4, see attached sketchSample Location:
Placement Method:Pump
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
4 1 4.00 12.57 12/02/14 7 58,260 5 4,640
4 2 4.00 12.57 12/23/14 28 65,850 5 5,240
4 3 4.00 12.57 12/23/14 28 65,970 5 5,250
4 4 4.00 12.57 12/23/14 28 67,190 5 5,350
Average (28 days) 5,280
4 5 4.00 12.57 01/20/15 56
Comments:Average compressive strength of 28 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Daniel Duran
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 4 of 5CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0374
11/25/14
12/24/14 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
1059
1159
Plant:
Ticket No.:
259
25981470
Field Test Data
Test
Air Content (%):
Result Specification
4 3-5
4.6 3-6
60
57
145.8
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:11/25/14 1155
Daniel Duran
Clear
450/500 10
0
0
Sample #5, see attached sketchSample Location:
Placement Method:Pump
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
5 1 4.00 12.57 12/02/14 7 62,630 5 4,980
5 2 4.00 12.57 12/23/14 28 77,940 4 6,200
5 3 4.00 12.57 12/23/14 28 72,030 5 5,730
5 4 4.00 12.57 12/23/14 28 79,170 4 6,300
Average (28 days) 6,080
5 5 4.00 12.57 01/20/15 56
Comments:Average compressive strength of 28 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey James D. Baze
Project Manager
Structure Tone Southwest
Reviewed By:
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Daniel Duran
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 5 of 5CR0001, 11-16-12, Rev.6
REINFORCING STEEL OBSERVATIONS REPORT
Report Number:94141126.0377
Service Date:12/01/14 8901 Carpenter Frwy., Suite 100
Report Date:12/15/14 Dallas, TX 75247
214-630-1010 Reg No: F-3272
Client Project
ML Realty Partners Park West Crossing
Attn: Timothy Geisler 910, 920 & 930 Freeport Pkwy
One Pierce Pl Ste 450W & 631 Southwestern Blvd
Itasca, IL 60143 Coppell, TX
Project Number: 94141126
Services: Reinforcing steel (rebar) placement observation.
Terracon Rep.: Vincent Green
Reported To:
Contractor:Structure Tone Southwest
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike
Toole(1) Structure Tone Southwest Inc., Robin
Povey
Reviewed By:____________________________________
James D. Baze
Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to
the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
R940003, 07-01-12, Rev.0 Page 1 of 1 tp
PROJECT DATA
Drawings Utilized:C6.01/Paving Details
Locations/Items Observed:Paving, see attached sketch
Test Method:Visual Observation
REPORT OF OBSERVATION
ITEMS OBSERVED CORRECT INCORRECT ITEMS OBSERVED CORRECT INCORRECT ITEMS OBSERVED CORRECT INCORRECT
Placing Drawings
Approved X Bar Length and Shape X Column Tie Spacing & Type
Bar Size X Proper Bar Placement X Stirrup Spacing & Type
Bar Grade X Properly Tied X Welded Splices
Rebar Clean X Dowel Bars in Place Mechanical Splices
Trash & Debris Removed X Proper Bar Supports X Lapped Splices X
Number of Bars X Proper Cover/Clearance X
Discrepancies/Comments:
No discrepancies were noted at the time of this observation.
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0378
12/01/14
12/15/14
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0416
1426
Plant:
Ticket No.:
236
25983024
Field Test Data
Test
Air Content (%):
Result Specification
4 3-5
3.7 3-6
59
36
143.2
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:12/01/14 0455
Vincent Green
Cloudy
50/500 10
0
0
Sample #1, see attached sketchSample Location:
Placement Method:
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
1 1 4.00 12.57 12/08/14 7 63,310 3 5,040
1 2 4.00 12.57 12/29/14 28
1 3 4.00 12.57 12/29/14 28
1 4 4.00 12.57 12/29/14 28
1 5 4.00 12.57 01/26/15 56
Comments:
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 1 of 6CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0378
12/01/14
12/15/14
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0613
1444
Plant:
Ticket No.:
236
25983072
Field Test Data
Test
Air Content (%):
Result Specification
4 3-5
3.5 3-6
58
35
144.4
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:12/01/14 0650
Vincent Green
140/500 10
0
0
Sample #2, see attached sketchSample Location:
Placement Method:
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
2 1 4.00 12.57 12/08/14 7 63,940 5 5,090
2 2 4.00 12.57 12/29/14 28
2 3 4.00 12.57 12/29/14 28
2 4 4.00 12.57 12/29/14 28
2 5 4.00 12.57 01/26/15 56
Comments:
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 2 of 6CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0378
12/01/14
12/15/14
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0727
1184
Plant:
Ticket No.:
236
25983134
Field Test Data
Test
Air Content (%):
Result Specification
4 1/2 3-5
3.8 3-6
58
36
143.6
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:12/01/14 0831
Vincent Green
230/500 10
5
0
Sample #3, see attached sketchSample Location:
Placement Method:
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
3 1 4.00 12.57 12/08/14 7 65,690 4 5,230
3 2 4.00 12.57 12/29/14 28
3 3 4.00 12.57 12/29/14 28
3 4 4.00 12.57 12/29/14 28
3 5 4.00 12.57 01/26/15 56
Comments:
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 3 of 6CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0378
12/01/14
12/15/14
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0856
1432
Plant:
Ticket No.:
236
25983247
Field Test Data
Test
Air Content (%):
Result Specification
5 3-5
3.5 3-6
60
37
144.8
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:12/01/14
Vincent Green
350/500 10
10
0
Sample #4, see attached sketchSample Location:
Placement Method:
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
4 1 4.00 12.57 12/08/14 7 66,500 4 5,290
4 2 4.00 12.57 12/29/14 28
4 3 4.00 12.57 12/29/14 28
4 4 4.00 12.57 12/29/14 28
4 5 4.00 12.57 01/26/15 56
Comments:
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 4 of 6CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0378
12/01/14
12/15/14
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0954
1191
Plant:
Ticket No.:
236
25983311
Field Test Data
Test
Air Content (%):
Result Specification
5 3-5
3.3 3-6
62
35
145.2
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:12/01/14
Vincent Green
430/500 10
10
0
Sample #5, see attached sketchSample Location:
Placement Method:
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
5 1 4.00 12.57 12/08/14 7 66,480 5 5,290
5 2 4.00 12.57 12/29/14 28
5 3 4.00 12.57 12/29/14 28
5 4 4.00 12.57 12/29/14 28
5 5 4.00 12.57 01/26/15 56
Comments:
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 5 of 6CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0378
12/01/14
12/15/14
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
1120
0000
Plant:
Ticket No.:
236
25983409
Field Test Data
Test
Air Content (%):
Result Specification
5 3-5
3.5 3-6
60
40
144.4
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:12/01/14 1221
Vincent Green
540/540 10
5
0
Sample #6, see attached sketchSample Location:
Placement Method:
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
6 1 4.00 12.57 12/08/14 7 56,700 4 4,510
6 2 4.00 12.57 12/29/14 28
6 3 4.00 12.57 12/29/14 28
6 4 4.00 12.57 12/29/14 28
6 5 4.00 12.57 01/26/15 56
Comments:
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey James D. Baze
Project Manager
Structure Tone Southwest
Reviewed By:
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 6 of 6CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0378
12/01/14
12/30/14 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0416
1426
Plant:
Ticket No.:
236
25983024
Field Test Data
Test
Air Content (%):
Result Specification
4 3-5
3.7 3-6
59
36
143.2
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:12/01/14 0455
Vincent Green
Cloudy
50/500 10
0
0
Sample #1, see attached sketchSample Location:
Placement Method:
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
1 1 4.00 12.57 12/08/14 7 63,310 3 5,040
1 2 4.00 12.57 12/29/14 28 80,010 4 6,370
1 3 4.00 12.57 12/29/14 28 81,730 4 6,500
1 4 4.00 12.57 12/29/14 28 77,180 5 6,140
Average (28 days) 6,340
1 5 4.00 12.57 01/26/15 56
Comments:Average compressive strength of 28 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 1 of 6CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0378
12/01/14
12/30/14 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0613
1444
Plant:
Ticket No.:
236
25983072
Field Test Data
Test
Air Content (%):
Result Specification
4 3-5
3.5 3-6
58
35
144.4
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:12/01/14 0650
Vincent Green
140/500 10
0
0
Sample #2, see attached sketchSample Location:
Placement Method:
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
2 1 4.00 12.57 12/08/14 7 63,940 5 5,090
2 2 4.00 12.57 12/29/14 28 74,340 5 5,920
2 3 4.00 12.57 12/29/14 28 69,610 5 5,540
2 4 4.00 12.57 12/29/14 28 66,910 5 5,330
Average (28 days) 5,600
2 5 4.00 12.57 01/26/15 56
Comments:Average compressive strength of 28 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 2 of 6CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0378
12/01/14
12/30/14 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0727
1184
Plant:
Ticket No.:
236
25983134
Field Test Data
Test
Air Content (%):
Result Specification
4 1/2 3-5
3.8 3-6
58
36
143.6
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:12/01/14 0831
Vincent Green
230/500 10
5
0
Sample #3, see attached sketchSample Location:
Placement Method:
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
3 1 4.00 12.57 12/08/14 7 65,690 4 5,230
3 2 4.00 12.57 12/29/14 28 73,740 4 5,870
3 3 4.00 12.57 12/29/14 28 72,740 5 5,790
3 4 4.00 12.57 12/29/14 28 74,720 5 5,950
Average (28 days) 5,870
3 5 4.00 12.57 01/26/15 56
Comments:Average compressive strength of 28 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 3 of 6CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0378
12/01/14
12/30/14 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0856
1432
Plant:
Ticket No.:
236
25983247
Field Test Data
Test
Air Content (%):
Result Specification
5 3-5
3.5 3-6
60
37
144.8
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:12/01/14
Vincent Green
350/500 10
10
0
Sample #4, see attached sketchSample Location:
Placement Method:
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
4 1 4.00 12.57 12/08/14 7 66,500 4 5,290
4 2 4.00 12.57 12/29/14 28 77,350 5 6,160
4 3 4.00 12.57 12/29/14 28 82,110 2 6,530
4 4 4.00 12.57 12/29/14 28 81,610 4 6,490
Average (28 days) 6,390
4 5 4.00 12.57 01/26/15 56
Comments:Average compressive strength of 28 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 4 of 6CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0378
12/01/14
12/30/14 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
0954
1191
Plant:
Ticket No.:
236
25983311
Field Test Data
Test
Air Content (%):
Result Specification
5 3-5
3.3 3-6
62
35
145.2
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:12/01/14
Vincent Green
430/500 10
10
0
Sample #5, see attached sketchSample Location:
Placement Method:
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
5 1 4.00 12.57 12/08/14 7 66,480 5 5,290
5 2 4.00 12.57 12/29/14 28 75,710 4 6,030
5 3 4.00 12.57 12/29/14 28 74,870 4 5,960
5 4 4.00 12.57 12/29/14 28 78,440 4 6,240
Average (28 days) 6,080
5 5 4.00 12.57 01/26/15 56
Comments:Average compressive strength of 28 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 5 of 6CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0378
12/01/14
12/30/14 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
135P25P4
Redi-Mix
Material Information
1120
0000
Plant:
Ticket No.:
236
25983409
Field Test Data
Test
Air Content (%):
Result Specification
5 3-5
3.5 3-6
60
40
144.4
3,500
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:12/01/14 1221
Vincent Green
540/540 10
5
0
Sample #6, see attached sketchSample Location:
Placement Method:
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Pavement, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
6 1 4.00 12.57 12/08/14 7 56,700 4 4,510
6 2 4.00 12.57 12/29/14 28 67,040 5 5,340
6 3 4.00 12.57 12/29/14 28 71,040 5 5,650
6 4 4.00 12.57 12/29/14 28 66,110 4 5,260
Average (28 days) 5,420
6 5 4.00 12.57 01/26/15 56
Comments:Average compressive strength of 28 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey James D. Baze
Project Manager
Structure Tone Southwest
Reviewed By:
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Vincent Green
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 6 of 6CR0001, 11-16-12, Rev.6
STRUCTURAL STEEL OBSERVATIONS REPORT
Report Number:94141126.0380
Service Date:12/02/14 8901 Carpenter Frwy., Suite 100
Report Date:12/03/14 Dallas, TX 75247
214-630-1010 Reg No: F-3272
Client Project
ML Realty Partners Park West Crossing
Attn: Timothy Geisler 910, 920 & 930 Freeport Pkwy
One Pierce Pl Ste 450W & 631 Southwestern Blvd
Itasca, IL 60143 Coppell, TX
Project Number: 94141126
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to
the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
BC0001, 10-16-13, Rev.10 Page 1 of 2 sbv
On this date, Terracon's representative arrived at the above referenced job site as scheduled for structural steel observations. A visual
observation was performed as noted below.
A.Building A, Roof Level Framing @ A-G/1-4:
*1.Tilt wall panel to panel welded connections, one location @ G.5/1 was found to be incomplete.
2.Perimeter metal deck support angle underside welds to the tilt wall panel embed plates were determined
to be compliant.
3.Girder bottom chord extensions stabilizer plates at the tilt wall panels, welds were determined to be
compliant.
4. Joist to girder midspan ST Brace installations were determined to be compliant.
B.Building B, Roof Level Framing @ A-H/1-4:
1.Tilt wall panel to panel welded connections were determined to be compliant.
2.Perimeter metal deck support angle underside welds to the tilt wall panel embed plates were determined
to be compliant.
3.Girder bottom chord extension stabilized plates at the tilt wall panels, welds were determined to be compliant.
4.Joist to girder midspan ST Brace installations were determined to be compliant.
C.Building C, Roof Level Framing @ A-M/1-4. Reinspection Items From Reports Dated 10-10-2014 & 10-16-2014.
1.Joist seat field fixes at the supporting tilt wall attachments at A/1 and M/1 were now determined to be compliant.
*2.Tilt wall panel to panel welded connections, the following discrepancies were found:
*A.Line A/35
*B.Line F.4/1
*C.Line G.7/1
3.Perimeter metal deck support angle underside welds to the tilt wall panel embed plates were determined to be compliant.
STRUCTURAL STEEL OBSERVATIONS REPORT
Report Number:94141126.0380
Service Date:12/02/14 8901 Carpenter Frwy., Suite 100
Report Date:12/03/14 Dallas, TX 75247
214-630-1010 Reg No: F-3272
Client Project
ML Realty Partners Park West Crossing
Attn: Timothy Geisler 910, 920 & 930 Freeport Pkwy
One Pierce Pl Ste 450W & 631 Southwestern Blvd
Itasca, IL 60143 Coppell, TX
Project Number: 94141126
Services: Structural steel observation.
Terracon Rep.: Randy T. Walcker, C.W.I.
Reported To:
Contractor:Structure Tone Southwest
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike
Toole(1) Structure Tone Southwest Inc., Robin
Povey
Reviewed By:____________________________________
James D. Baze
Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to
the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
BC0001, 10-16-13, Rev.10 Page 2 of 2 sbv
4.Girder bottom chord extension stabilizer plates at the tilt wall panels, welds were determined to be compliant.
5.Joist to girder midspan ST Brace installations were determined to be compliant.
D.Building D, Roof Level Framing @ A-P/1-5. Reinspection Items From Report Dated 10-08-2014:
*1.Tilt wall panel to panel welded connections, the following discrepancies were found:
*A.Line A/1
*B.Line E.5/5
*C.Line F.5/5
*2.Girder bottom chord extension stabilizer plates at the tilt wall panels, one location @ N/5 was found to be incomplete.
3.South wall leave out panel bay structural steel items, joist seat welds and joist bridging was now determined
to be compliant.
4.Perimeter metal deck support angle underside welds to the tilt wall panel embed plates were determined to
be compliant.
5.Joist to girder midspan ST Brace installations were determined to be compliant.
*Noted discrepancies and/or incomplete work.
REINFORCING STEEL OBSERVATIONS REPORT
Report Number:94141126.0381
Service Date:12/09/14 8901 Carpenter Frwy., Suite 100
Report Date:12/16/14 Dallas, TX 75247
214-630-1010 Reg No: F-3272
Client Project
ML Realty Partners Park West Crossing
Attn: Timothy Geisler 910, 920 & 930 Freeport Pkwy
One Pierce Pl Ste 450W & 631 Southwestern Blvd
Itasca, IL 60143 Coppell, TX
Project Number: 94141126
Services: Reinforcing steel (rebar) placement observation.
Terracon Rep.: Muthanna Al Ani
Reported To:
Contractor:Structure Tone Southwest
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike
Toole(1) Structure Tone Southwest Inc., Robin
Povey
Reviewed By:____________________________________
James D. Baze
Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to
the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
R940003, 07-01-12, Rev.0 Page 1 of 1 sbv
PROJECT DATA
Drawings Utilized:No plans were available at this time.
Locations/Items Observed:Three Approaches along Freeport Pkwy.
Test Method:Visual Observation
REPORT OF OBSERVATION
ITEMS OBSERVED CORRECT INCORRECT ITEMS OBSERVED CORRECT INCORRECT ITEMS OBSERVED CORRECT INCORRECT
Placing Drawings
Approved X Bar Length and Shape Column Tie Spacing & Type
Bar Size Proper Bar Placement Stirrup Spacing & Type
Bar Grade Properly Tied Welded Splices
Rebar Clean X Dowel Bars in Place Mechanical Splices
Trash & Debris Removed X Proper Bar Supports Lapped Splices
Number of Bars Proper Cover/Clearance
Discrepancies/Comments:
No discrepancies were noted at the time of this observation.
NOTE:Onsite representative observed that the reinforcing steel observation consisted of #3 bars at 12 O.C.E.W.
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0382
12/09/14
12/18/14
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
10L11504
Redi-Mix
Material Information
1004
1425
Plant:
Ticket No.:
136
25989276
Field Test Data
Test
Air Content (%):
Result Specification
5 3-5
4.4 3-6
64
43
148.0
4,000
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:12/09/14 1102
Muthanna Al Ani
Foggy, calm
40/110 10
0
0
See attached sketchSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Three Drive Approaches along
Freeport Parkway
Placement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
1 1 4.00 12.57 12/16/14 7 59,960 5 4,770
1 2 4.00 12.57 01/06/15 28
1 3 4.00 12.57 01/06/15 28
1 4 4.00 12.57 01/06/15 28
1 5 4.00 12.57 02/03/15 56
Comments:
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Muthanna Al Ani
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 1 of 2CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0382
12/09/14
12/18/14
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
10L11504
Redi-Mix
Material Information
1338
1424
Plant:
Ticket No.:
136
25989626
Field Test Data
Test
Air Content (%):
Result Specification
5 3-5
4.6 3-6
65
51
147.6
4,000
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:12/09/14 1420
Muthanna Al Ani
Mostly cloudy, calm
110/110 10
0
0
See attached sketchSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Three Drive Approaches along
Freeport Parkway
Placement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
2 1 4.00 12.57 12/16/14 7 66,540 2 5,300
2 2 4.00 12.57 01/06/15 28
2 3 4.00 12.57 01/06/15 28
2 4 4.00 12.57 01/06/15 28
2 5 4.00 12.57 02/03/15 56
Comments:
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey James D. Baze
Project Manager
Structure Tone Southwest
Reviewed By:
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Muthanna Al Ani
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 2 of 2CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0382
12/09/14
01/07/15 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
10L11504
Redi-Mix
Material Information
1004
1425
Plant:
Ticket No.:
136
25989276
Field Test Data
Test
Air Content (%):
Result Specification
5 3-5
4.4 3-6
64
43
148.0
4,000
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:12/09/14 1102
Muthanna Al Ani
Foggy, calm
40/110 10
0
0
See attached sketchSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Three Drive Approaches along
Freeport Parkway
Placement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
1 1 4.00 12.57 12/16/14 7 59,960 5 4,770
1 2 4.00 12.57 01/06/15 28 72,660 2 5,780
1 3 4.00 12.57 01/06/15 28 69,400 2 5,520
1 4 4.00 12.57 01/06/15 28 72,820 2 5,800
Average (28 days) 5,700
1 5 4.00 12.57 02/03/15 56
Comments:Average compressive strength of 28 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey
Structure Tone Southwest
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Muthanna Al Ani
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 1 of 2CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0382
12/09/14
01/07/15 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
10L11504
Redi-Mix
Material Information
1338
1424
Plant:
Ticket No.:
136
25989626
Field Test Data
Test
Air Content (%):
Result Specification
5 3-5
4.6 3-6
65
51
147.6
4,000
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:12/09/14 1420
Muthanna Al Ani
Mostly cloudy, calm
110/110 10
0
0
See attached sketchSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Three Drive Approaches along
Freeport Parkway
Placement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
2 1 4.00 12.57 12/16/14 7 66,540 2 5,300
2 2 4.00 12.57 01/06/15 28 79,750 2 6,350
2 3 4.00 12.57 01/06/15 28 82,350 4 6,550
2 4 4.00 12.57 01/06/15 28 85,760 4 6,830
Average (28 days) 6,580
2 5 4.00 12.57 02/03/15 56
Comments:Average compressive strength of 28 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey James D. Baze
Project Manager
Structure Tone Southwest
Reviewed By:
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Muthanna Al Ani
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 2 of 2CR0001, 11-16-12, Rev.6
FOUNDATION OBSERVATIONS REPORT
Report Number:94141126.0383
Service Date:12/10/14 8901 Carpenter Frwy., Suite 100
Report Date:12/16/14 Dallas, TX 75247
214-630-1010 Reg No: F-3272
Client Project
ML Realty Partners Park West Crossing
Attn: Timothy Geisler 910, 920 & 930 Freeport Pkwy
One Pierce Pl Ste 450W & 631 Southwestern Blvd
Itasca, IL 60143 Coppell, TX
Project Number: 94141126
Services: Foundation observations.
Terracon Rep.: Marco Rojas
Reported To:
Contractor:Structure Tone Southwest
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike
Toole(1) Structure Tone Southwest Inc., Robin
Povey
Reviewed By:____________________________________
James D. Baze
Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to
the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
BC0001, 10-16-13, Rev.10 Page 1 of 1 dgr
On this date, Terracon's representative arrived at the above referenced job site as scheduled for belled (underreamed) pier observation. See
the attached sheet(s) for recorded data.
REPORT OF DRILLED BELLED PIERS
Project: Park West Crossing - Monument Piers Report No.: 94141126.0383
910, 920 & 930 Freeport Pkwy & 631 Southwestern Blvd, Coppell, TX Date of Service: 12/10/14
Project No.: 94141126 Technician: M. Rojas
Driller: Auger Page: 1 of 2
Pier Identification North South
Pier Diameter (in.)18 18
Bell Diameter (in.)36 36
Top of Pier Elevation (ft)N/A N/A
Req. Depth from Exist. Grade (ft)15.0 15.0
Initial Depth of Pier from Existing Grade
(ft)15.4 15.1
Final Depth of Pier from Existing Grade
(ft)15.4 15.5
Depth from Top of Concrete (ft)14.5 14.5
Condition of Bottom (wet or dry)Dry Dry
Plumb Within Tolerance (yes or no)Yes Yes
Casing Diameter (in) N/A N/A
Cased Depth (ft)N/A N/A
Number of Vertical Bars (ea.)4 4
Reinforcing Bar Size (#)6 6
Length of Vertical Bars (ft.)14.0 14.0
Time Drilling was Completed 9:43 8:56
Time Concrete was Placed 15:30 15:33
R940002, 08-05-14, Rev.3
8901 Carpenter Frwy.,Suite #100
Dallas,TX 75247
(214)630-1010 Reg No.:F-3272
REPORT OF DRILLED PIERS
Project: Park West Crossing - Light Pole Piers Report No.: 94141126.0383
910, 920 & 930 Freeport Pkwy & 631 Southwestern Blvd, Coppell, TX Date of Service: 12/10/14
Project No.: 94141126 Technician: M. Rojas
Driller: Auger Page: 2 of 2
Pier Identification North South
Pier Diameter (in.)24 24
Top of Ground Elevation (ft.)N/A N/A
Top of Pier Elevation (ft.)N/A N/A
Depth to Bearing Stratum from
Ground (ft.)N/A N/A
Depth of Pier from Ground (ft.)8.3 8.2
Required Depth (ft.)8.0 8.0
Actual Depth (ft.)8.3 8.2
Depth from Top of Concrete (ft.)10.8 10.8
Condition of Bottom (wet or dry)Dry Dry
Plumb Within Tolerance (yes or no)Yes Yes
Casing Diameter (in.) N/A N/A
Cased Depth (ft.)N/A N/A
Number of Vertical Bars (ea.)8 8
Reinforcing Bar Size (#)8 8
Length of Vertical Bars (ft.)10.0 10.0
Time Drilling was Completed 10:12 10:27
Time Concrete was Placed 15:45 16:00
R940001, 08-05-14 Rev.4
8901 Carpenter Frwy.,Suite #100
Dallas,Texas 75247
(214)630-1010
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0384
12/10/14
12/18/14
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
10J11521
Redi-Mix
Material Information
1444
1422
Plant:
Ticket No.:
P130
25990695
Field Test Data
Test
Air Content (%):
Result Specification
4 3/4 3-5
1.2 0-3
69
57
148.4
3,000
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:12/10/14 1530
Marco Rojas
Cloudy
10/20 10
10
0
Building A, Monument Piers &
Footings
Sample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Building A, N Ramp & Building B, S
Ramp, Monument Piers & Footings;
E of Building C near Parking Area,
Light Pole Piers
Placement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
1 1 4.00 12.57 12/17/14 7 51,820 3 4,120
1 2 4.00 12.57 01/07/15 28
1 3 4.00 12.57 01/07/15 28
1 4 4.00 12.57 01/07/15 28
1 5 4.00 12.57 02/04/15 56
Comments:
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey James D. Baze
Project Manager
Structure Tone Southwest
Reviewed By:
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Marco Rojas
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 1 of 1CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0384
12/10/14
01/08/15 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
10J11521
Redi-Mix
Material Information
1444
1422
Plant:
Ticket No.:
P130
25990695
Field Test Data
Test
Air Content (%):
Result Specification
4 3/4 3-5
1.2 0-3
69
57
148.4
3,000
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:12/10/14 1530
Marco Rojas
Cloudy
10/20 10
10
0
Building A, Monument Piers &
Footings
Sample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Building A, N Ramp & Building B, S
Ramp, Monument Piers & Footings;
E of Building C near Parking Area,
Light Pole Piers
Placement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
1 1 4.00 12.57 12/17/14 7 51,820 3 4,120
1 2 4.00 12.57 01/07/15 28 69,410 4 5,520
1 3 4.00 12.57 01/07/15 28 68,370 4 5,440
1 4 4.00 12.57 01/07/15 28 68,060 4 5,420
Average (28 days) 5,460
1 5 4.00 12.57 02/04/15 56
Comments:Average compressive strength of 28 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey James D. Baze
Project Manager
Structure Tone Southwest
Reviewed By:
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Marco Rojas
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 1 of 1CR0001, 11-16-12, Rev.6
STRUCTURAL STEEL OBSERVATIONS REPORT
Report Number:94141126.0386
Service Date:12/10/14 8901 Carpenter Frwy., Suite 100
Report Date:12/11/14 Dallas, TX 75247
214-630-1010 Reg No: F-3272
Client Project
ML Realty Partners Park West Crossing
Attn: Timothy Geisler 910, 920 & 930 Freeport Pkwy
One Pierce Pl Ste 450W & 631 Southwestern Blvd
Itasca, IL 60143 Coppell, TX
Project Number: 94141126
Services: Structural steel observations.
Terracon Rep.: Randy T. Walcker, C.W.I.
Reported To:
Contractor:Structure Tone Southwest
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike
Toole(1) Structure Tone Southwest Inc., Robin
Povey
Reviewed By:____________________________________
James D. Baze
Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to
the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
BC0001, 10-16-13, Rev.10 Page 1 of 1 dgr
On this date, Terracon's representative arrived at the above referenced job site as scheduled for structural steel observations. A visual
observation was performed as noted below.
A.Building A, C & D – Re-observation Items from Structural Steel Observation Report #94141126.0380, dated 12/02/14:
1.Building A, 1 tilt wall panel to panel welded connections at Line G.5/1 was now determined to be compliant.
2.Building C
a.Two tilt wall panel to panel welded connections at Lines F.4/1 & G.7/1 were now determined to be compliant.
*b.One tilt wall panel to panel welded connection at Line A/3.5 was still found to be incomplete.
3.Building D
a.Two tilt wall panel to panel welded connections at Lines E.5/5 & F.5/5 were now determined to be compliant.
*b.One tilt wall panel to panel welded connection at Line A/1 was still found to be incomplete.
c.Girder bottom chord extension stabilizer plate at the tilt wall panel, 1 location at Line N/5 was now determined
to be compliant.
*Noted discrepancies and/or incomplete work.
REINFORCING STEEL OBSERVATIONS REPORT
Report Number:94141126.0387
Service Date:12/10/14 8901 Carpenter Frwy., Suite 100
Report Date:12/16/14 Dallas, TX 75247
214-630-1010 Reg No: F-3272
Client Project
ML Realty Partners Park West Crossing
Attn: Timothy Geisler 910, 920 & 930 Freeport Pkwy
One Pierce Pl Ste 450W & 631 Southwestern Blvd
Itasca, IL 60143 Coppell, TX
Project Number: 94141126
Services: Reinforcing steel (rebar) placement observation.
Terracon Rep.: Marco Rojas
Reported To:
Contractor:Structure Tone Southwest
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike
Toole(1) Structure Tone Southwest Inc., Robin
Povey
Reviewed By:____________________________________
James D. Baze
Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to
the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
R940003, 07-01-12, Rev.0 Page 1 of 1 dgr
PROJECT DATA
Drawings Utilized:S3.1/#2, dated 10/24/13
Locations/Items Observed:Footing for Ramp Wall at North side ramp of Bldg. A;
South side ramp of Bldg. B
Test Method:Visual Observation
REPORT OF OBSERVATION
ITEMS OBSERVED CORRECT INCORRECT ITEMS OBSERVED CORRECT INCORRECT ITEMS OBSERVED CORRECT INCORRECT
Placing Drawings
Approved X Bar Length and Shape X Column Tie Spacing & Type
Bar Size X Proper Bar Placement X Stirrup Spacing & Type
Bar Grade X Properly Tied X Welded Splices
Rebar Clean X Dowel Bars in Place X Mechanical Splices
Trash & Debris Removed X Proper Bar Supports X Lapped Splices X
Number of Bars X Proper Cover/Clearance X
Discrepancies/Comments:
No discrepancies were noted at the time of this observation.
REINFORCING STEEL OBSERVATIONS REPORT
Report Number:94141126.0391
Service Date:12/16/14 8901 Carpenter Frwy., Suite 100
Report Date:12/22/14 Dallas, TX 75247
214-630-1010 Reg No: F-3272
Client Project
ML Realty Partners Park West Crossing
Attn: Timothy Geisler 910, 920 & 930 Freeport Pkwy
One Pierce Pl Ste 450W & 631 Southwestern Blvd
Itasca, IL 60143 Coppell, TX
Project Number: 94141126
Services: Reinforcing steel (rebar) placement observation.
Terracon Rep.: Ronald Regalado Ventura
Reported To:
Contractor:Structure Tone Southwest
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike
Toole(1) Structure Tone Southwest Inc., Robin
Povey
Reviewed By:____________________________________
James D. Baze
Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to
the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
R940003, 07-01-12, Rev.0 Page 1 of 1 tp
PROJECT DATA
Drawings Utilized:Civil Sheets/Details: C6.01/Legend, dated 04/23/14
Locations/Items Observed:Sidewalks, see attached sketch
Test Method:Visual Observation
REPORT OF OBSERVATION
ITEMS OBSERVED CORRECT INCORRECT ITEMS OBSERVED CORRECT INCORRECT ITEMS OBSERVED CORRECT INCORRECT
Placing Drawings
Approved X Bar Length and Shape X Column Tie Spacing & Type
Bar Size X Proper Bar Placement X Stirrup Spacing & Type
Bar Grade X Properly Tied X Welded Splices
Rebar Clean X Dowel Bars in Place X Mechanical Splices
Trash & Debris Removed X Proper Bar Supports X Lapped Splices X
Number of Bars X Proper Cover/Clearance X
Discrepancies/Comments:
No discrepancies were noted at the time of this observation.
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0392
12/16/14
12/24/14
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
10J11504
Redi-Mix
Material Information
0632
1396
Plant:
Ticket No.:
P259
25994022
Field Test Data
Test
Air Content (%):
Result Specification
4 1/2 3 - 5
3.0 3 - 6
61
39
145.6
3,000
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:12/16/14 0801
Ronald Regalado Ventura
Sunny
20/70 10
10
0
See Placement LocationSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Sidewalks, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
1 1 4.00 12.57 12/23/14 7 56,270 4 4,480
1 2 4.00 12.57 01/13/15 28
1 3 4.00 12.57 01/13/15 28
1 4 4.00 12.57 01/13/15 28
1 5 4.00 12.57 02/10/15 56
Comments:
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey James D. Baze
Project Manager
Structure Tone Southwest
Reviewed By:
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Ronald Regalado Ventura
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 1 of 1CR0001, 11-16-12, Rev.6
Report Number:
Service Date:
Report Date:
Task:
Client Project
Project Number:94141126
Coppell, TX
& 631 Southwestern Blvd
910, 920 & 930 Freeport Pkwy
Park West CrossingML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
214-630-1010 Reg No: F-3272
Dallas, TX 75247
8901 Carpenter Frwy., Suite 100
94141126.0392
12/16/14
01/13/15 Revision 1 - 28-day results
CONCRETE COMPRESSIVE STRENGTH TEST REPORT
Specified Strength:28 days
Mix ID:
Supplier:
Batch Time:
Truck No.:
10J11504
Redi-Mix
Material Information
0632
1396
Plant:
Ticket No.:
P259
25994022
Field Test Data
Test
Air Content (%):
Result Specification
4 1/2 3 - 5
3.0 3 - 6
61
39
145.6
3,000
Slump (in):
psi @
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Sample Time:12/16/14 0801
Ronald Regalado Ventura
Sunny
20/70 10
10
0
See Placement LocationSample Location:
Placement Method:Direct Discharge
Water Added Before (gal):
Water Added After (gal):
Accumulative Yards:Batch Size (cy):
Sidewalks, see attached sketchPlacement Location:
Laboratory Test Data
Set Avg Diam.Area DateDate Test
Age at
Load
Maximum
Strength
Compressive
Fracture
No.ID
Specimen
Received Tested (days)Type(in)(sq in)(lbs)(psi)
1 1 4.00 12.57 12/23/14 7 56,270 4 4,480
1 2 4.00 12.57 01/13/15 28 68,020 5 5,410
1 3 4.00 12.57 01/13/15 28 68,420 5 5,450
1 4 4.00 12.57 01/13/15 28 67,960 5 5,410
Average (28 days) 5,420
1 5 4.00 12.57 02/10/15 56
Comments:Average compressive strength of 28 day cylinders complies with the specified strength.
Samples Made By: Terracon
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Services:
Reported To:
Contractor:
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike Toole
(1) Structure Tone Southwest Inc., Robin Povey James D. Baze
Project Manager
Structure Tone Southwest
Reviewed By:
ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231Test Methods:
Terracon Rep.: Ronald Regalado Ventura
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Page 1 of 1CR0001, 11-16-12, Rev.6
STRUCTURAL STEEL OBSERVATIONS REPORT
Report Number:94141126.0393
Service Date:12/16/14 8901 Carpenter Frwy., Suite 100
Report Date:12/22/14 Dallas, TX 75247
214-630-1010 Reg No: F-3272
Client Project
ML Realty Partners Park West Crossing
Attn: Timothy Geisler 910, 920 & 930 Freeport Pkwy
One Pierce Pl Ste 450W & 631 Southwestern Blvd
Itasca, IL 60143 Coppell, TX
Project Number: 94141126
Services: Structural steel observations.
Terracon Rep.: Randy T. Walcker, C.W.I.
Reported To:
Contractor:Structure Tone Southwest
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) Structure Tone Southwest Inc., Mike
Toole(1) Structure Tone Southwest Inc., Robin
Povey
Reviewed By:____________________________________
James D. Baze
Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to
the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
BC0001, 10-16-13, Rev.10 Page 1 of 1 tp
On this date, Terracon's representative arrived at the above referenced job site as scheduled for structural steel observations. A visual
observation was performed as noted below.
A.Building C and Building D, Roof Level Framing – Re-observation Items From Structural Steel Observation Report
94141126.0386, Dated 12/10/14:
1.Building C, tilt wall panel to panel welded connection at line A/3.5 was now determined to be compliant.
2.Building D, tilt wall panel to panel welded connection at Line A/1 was now determined to be compliant.