Loading...
Arbor Manors-CS091007 (3) Michelle Matunas From:Keith Marvin Sent:Wednesday, October 07, 2009 4:15 PM To:Glenn Hollowell; Ted Dutt Cc:Michael Garza Subject:Fwd: Arbor Manors Sanitary Sewer Revision Attachments:X_Projects LDD_05088_dwg_05088-SANPROFILES (3) (1).pdf This looks like it will work. They are not showing our 24" water line, but when we put that in we went under the existing 8" line, so we will be over with this too. Any thoughts? Keith >>> "Casey Ross" <cross@daa-civil.com> 10/7/2009 3:56 PM >>> Keith, Please find attached a revision for the sanitary sewer line connection at the northwest corner of Arbor Manors. We adjusted the existing north/south "Verizon" line from the existing manhole on the north side of Sandy Lake Road to the northern most existing manhole on Verizon's property. The replacement portion going under Sandy Lake needed to be upsized to a 12" so we could meet TCEQ minimum slope requirements. The steepest that line could be is 0.20%. We also adjust the proposed Line "J" from Station 0+00 to 8+03.24. Please review and let me know if you have any questions. Thanks, Casey Ross, P.E. Dowdey, Anderson & Assoc. 5225 Village Creek Drive, Suite 200 Plano, TX 75093 972-931-0694 (O) 469-576-1039 (C) 972-931-9538 (F) 1