FW: Sandy Lake Rd. - Plan Review CommentsKeith,
Please note comments below from Andrew and attachments.
Please let us know if you have any questions.
Chris
Chris Schmitt, P.E.
Principal
17304 Preston Road, Suite 1340
Dallas, Texas 75252
214.461.9867 Main
903.421.1897 Mobile
214.461.9864 Fax
cschmitt@tnpinc.com <mailto:cschmitt@tnpinc.com>
From: Andrew Luce
Sent: Thursday, May 01, 2014 11:12 AM
To: Chris Schmitt
Cc: Mitch Holmes; Robert Jenkins
Subject: RE: Sandy Lake Rd. - Plan Review Comments
Chris,
Please find attached the final two revised sheets.
Sheet 42 has been revised to provide a clear floor/ground space at the
pedestrian push button at the intersection. The result is the ramp has
been flattened to 2% and the trail has been lowered 0.40’ for
approximately 300’. We had to go this far because the trail was already
at 5% slope and could not catch up until the crest of the hill. We also
provided a detail showing the cross slope transition of the sidewalk
along S. Coppell Rd. tying into the trail. These changes were
coordinated with, and approved by Bob Davies.
Sheet 98 has had note #7 added to reference details that give
requirements for clear floor or ground space and vertical height
requirements for the push buttons.
These revisions should address all remaining comments from Bob.
If you have any questions, please let me know.
Thanks,
Andrew