RE: Verizon PlansKeith
Here are the comments for the Verizon plans. Most are pretty minor:
Sheet 2 – The proposed line passes through our proposed 8” water line.
We could adjust up or down in the field, but it looks like they could go
a little lower through that area.
Sheet 3 – They are passing directly beneath a light pole. They should
be plenty deep, but again, it looks like they could adjust to miss this.
Sheet 4 – They are proposing to be dangerously close to where one of
the bridge piers is going to be. I would recommend they stay as close
to the right of way as possible to give bridge guys plenty of room.
Sheet 6 – They are pretty close to the proposed traffic signal pole
foundation. Would suggest they veer away from this.
Sheet 6 – The large either needs to be moved directly next to the
sidewalk, or they need to make certain that they are setting it at the
proper finished grade.
That’s it. If anything else comes up, just let me know.
I’ll get you the recommendation letter later this afternoon.
Thanks.