DFW Trade JV-LR 990401 (2) TRINITY ENGINEERING TESTING CORPORATION
P.O. Box 223571 DALLAS, TEXAS 75222-3571 972-870-0808
TO: INDUSTRIAL DEV INTERNATIONAL PROJECT: DFW TRADE CENTER
5420 LBJ FRWY, SUITE 1275 BUILDING H
DALLAS, TX 75240 TETCO NO.: 3126
DATE: 4/1/99
REPORT NO.: 499003
REPORT OF FLOOR FLATNESS AND FLOOR LEVELNESS
THE FOLLOWING AREA OF BUILDING H WAS TESTED FOR FLOOR FLATNESS AND LEVELNESS
ON 3-31-99 BY J. TIPTON USING A TYPE II GAUGE IN GENERAL ACCORDANCE WITH ASTM E 1155:
B, 21; D, 21; B, 14; D, 14
THE RESULTS ARE AS FOLLOWS: MINIMUM LOCAL VALUE
REQUIREMENTS
FF = 52 (50.9 - 53.9) 22 MINIMUM
FL = 48 (46.9 - 49.9) 16 MINIMUM
THE OVERALL RESULTS FOR BUILDING H ARE AS FOLLOWS:
SPECIFIED OVERALL VALUE
REQUIREMENTS
FF = 56 32 MINIMUM
FL = 44 25 MINIMUM
COPIES TO: 1-CLIENT, ATT: KEN KUESEL
1-KAJIMA CONST
1-COMPASS BAN K ~TRINITY ENGINEERING TESTING CORP.
1-MacGREGOR ASSOC. ARCHITECTS ~ ~/~
1-POTTER CONCRETE CO.
1-PIONEER CONCRETE
1-CITY OF GRAPEVINE
1-CITY OF COPPELL Bil ampbell, Jr., P.E.
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected.
Thev are not intended to be indicative of Qualifies of aDoarentlv identical Qroducts. The use of our name must receive Qrior written aQQroval.