Freeport NIP(7.5)-LR010525 (2)REPORT OF FLOOR FLATNESS INSPECTION ENGINEERING, INC. 8901 Carpenter Freeway, Suite 100 Dallas, Texas 75247 PROJECT NAME: FREEPORT 9 DATE PLACED: 05/24/2001 ;)ATE TESTED: 05/25/2001 PROJECT NO.: 94011192 REPORT NO.: 94011192.0001 SLAB-ON-GRADE, POUR #1 350.0' 10 A RUN 02 RUN 04 RUN 09 RUN 06 RUN 10 C RUN 01 RUN 07 RUN 03 RUN 08 RUN 05 IrRUN 12 RUN 11 93.0' NORTH SLAB-ON-GRADE, POUR #1 NOT TO SCALE Run Name Combined Test Section DATA~94011192 FREEPORT9 POUR1 No. Rdgs measured Ff RUNO1 75 RUN02 75 RUN03 75 RUN04 75 RUN05 75 RUN06 75 RUN07 75 RUN08 75 RUN09 75 RUN10 75 RUNll 75 RUN12 75 measured FI 69.11 <59.23-79.00> 55.79 <47.81-63.77> 44.72 <38.32-51.12> 36.71 ~31.46-41.97> 43.72 <37.47-49.97> 56.13 <48.10-64.16> 50.05 <42.89-57.21> 42.80 <36.68-48.92> 51.03 <43.73-58.33> 40.52 <34.73-46.32> 32.62 <27.95-37.28> 40.91 <35.06-46.77> 47.05 <39.79-54.32> 50.35 <42.58-58.13> 34.91 <29.52-40.31> 29.78 <25.18-34.38> 34.19 <28.91-39.47> 42.06 <35.56-48.55> 26.99 <22.82-31.15> 41.16 <34.80-47.51> 39.77 <33.63-45.91> 43.49 <36.77-50.20> 27.94 <23.62-32.25> 39.01 <32.99-45.04> Totals: 900 44.39 <45.84-42.95> Spec Ff: 35 Floor area above Ff Spec: 3727 sq feet. Spec Fl: 25 Floor area above F1 Spec: 5665 sq feet. 35.96 <37.22-34'~71> HBC ENGINEERING, INC. 8901 CARPENTER FRWY. SUITE 100 DALLAS, TEXAS 75247 Phone : 214-630-1010 Fax : 214-630-7070