Loading...
WA9302A-CS 960719 SHIMEK, JACOBS & FINKLEA CONSULTING ENGINEERS 8333 Douglas Avenue, #820 Dallas, Texas 75225 (214) 361-7900 ROSS L. JACOBS, P.E. RONALD V. CONWAY, P.E. JOHN W. BIRKHOFF, P.E. JOE R. CARTER, P.E, GARY C. HENDRICKS, P.E. July 19, 1996 C. L. SHIMEK, P.E. I. C. FINKLEA, P.E. North Texas Municipal Construction Co., Inc. Re: City of Coppell Village Parkway Pump Station Addition Gentlemen: We have reviewed the corrected motor data for the proposed 250 hp pump motors, dated July 18, 1996, submitted by your pump supplier. We offer no objections to the revised motor data, but would like to point out that the revised data shows a motor approximately 5.5 inches longer than the data originally submitted. According to the dimensional chart included in the original submittal, the pump and motor base plate is to be 84-inches in length. The concrete pump pad shown on sheet S1 of the plans is proposed to be 84-inches in length. This leaves no room for adjustment that may be required as the pumps are set. We have discussed this with your pump supplier and understand they can provide a base plate as small as 75-inches and still accommodate the larger motor frame as revised. We offer no objections to the smaller base plate if it will aid in the installation of the pumps. Please be advised that nder no circumstances can we allow the pump pad to exceed the planned dimensions, nor allow for a smaller opening between the pump pads than shown. We are returning three copies of the revised submittal with our review stamp. If you have any questions, please do not hesitate to contact us. SiZ/~;~s' Gary C. Hendricks, P.E. ~c.'cl°s~; Larry Davis WATER, WASTEWATER PUMPS AND EQUIPMENT 5~0 REDBIRD CENTER DR. · DAUAS, TX 75237 · (214) 631-5650 · 1-800-783-6756 ° FAX (214) 333-2786, FAX (214) 988-14~6 North Texas Municipal Construction Co. July 18, 1996 5614 Dyer Street Dallas, Texas 75206 Attn: Michael Daigre ~ : Re: City of Coppell ViIlage Parkway Pump Station your order (Vi!lage-PO-002) Dear Mike, I have just been informed by I.D.P. Factory that G.E. Company has submitted on the wrong motor. They submitted on a RANDOM WOUND instead of FORM WOUND, which is what is required. Attached is the correct motor data. As you will note the efficiency is the same at full load and slightly better at 3/4 load and the guaranteed efficiency is 95.4 instead of 95.2. The full load amps will increase slightly from 288 amps to 290 amps. The overall dimension of the correct motor is 50.06 inches, which is 5.5 inches longer than what was submitted on. Provided we get a release for production by July 23, 1996, the delivery for this motor is September 20th, however, we are expediting this order to get a September 8th delivery or better. G.E. has placed this order on hold production until such time we receive approval from the engineer. As we discussed this morning, with your permission, I will hand deliver these corrections today to Mr. Gary Hendricks at Shimek, Jacobs, & Finklea. ' EXCEPTION TAKEN [] MAKE CORRECTIO~ NO'rED I will keep you advised of our progress as we go alon~ [E] RF_JECTED [] REVISE AND RESUBMIT [] SUBMIT SPECIFIED ITEM incere , Checking ls only for general conformance with the design  Concept of the project and general compliance with tie Information given in the ccntract documents. Any action shown is subject to the requirements of the plans and Nabil T. Azzam, specifications. Contractor is responsible for: dimensions Manager which shall be confirmed and correlated at tile lob site; fabrication processes and techniques of construction, co- ordination of his work with that of all other trades and .performing his work in a safe and satisfactory rnar:ner. SHIMEK, JACOBS & FINKLEA CONSULTING .NGI ERS Daffi. ~ ~f~ By /, · 5BNT By:.M~nNL,F~,CTDtlN6 ; 7-17-~6; 9:41; lN~-D~S55 ~ 1 214 388 144C;~ 2/4 ~ GE MOTORS AND INDUSTRIAL SYSTEMS "'-~ Pks2 referrace IDP PC~ Ir207691. Having z,~elv~ a enginz~ing ~ has disr, ov~d d~sr ~ initial print ~ppru~,al data was incom~ SUl::la'Di~'lld refle__rj,~,y!__ performtaste data 0~ a I-and~m wotlnd lists infc.,~lien con~un~ with a ~ wound desi~z, p~r Best t~cgard~ mad Industrial Syalmu, 163,~ B~-z~,way, Fort Wsyae, I1',1 468Qt Tel: C219)439-~-7~ Fox: (2t9~439-2733 GENERAL ELECTRIC COMPANY GE MOTORS & INDUSTRIAL SYSTEMS 2000 TAYLOR STREET- BOX 2205 FORT WAYNE, INDIANA 488O1 ~ 12, 1996 1,52,(0 01;' DATA TRANSMITTAL CUSTOMER: INGERSOLL-DRESSER PUMP C MARKS: 3900 COOK BLVD CHESA2EA/(E VA 23323 *************************e*****************************ee****************** CUSTOMER ORDER NO. P207691 G.E. REQUISITION NO. 680-21513 G.E. ORDER NO. 960401423 m PRINT APPROVAL m **********************~**************************************************** ITEM NO. 1&2 MODEL NO. NEW MODEL TYPE KS FRAME 449TS HP 250 RPM-FL 1785 PHASE 3 VOLTS 460 HZ 60 TIME I~ATING CONT SERVICE FACTOR 1.15 AMB-MAX 40 DEG C INSUL CLASS F NEMA DESIGN B CODE G AMPS - FL 290.0 OUTLINE 225B6500EF DESIGN 49DS1932A ENCLOSURE IS WP- I ADDITIONAL MOTOR DATA: B RISE @ 1.0 SF - VPI - EXTRA BAKE AND DIP - 100 OHM PLATINUM STATOR ~TD'S (2) 100 OHM PLATINUM BTD'S - GROUND LUG IN C/B - FORM WOUND LOAD~ 125 115 100 75 50 25 EFF 95.4 95.6 95.8 95.9 95.6 93.3 P.F. 85.4 85.1 84.0 80.7 71.9 50.0 AMPS 359.3 331.0 290.0 226.8 170.2 125.4. DISTRIBUTION INFORI~ATION: 4' REVISED MDT'S & OUTLINES TO CHARGEE, ATTN: KERRY FRITZ I OF SAME TO RRIA/~ POUNI)S, 4-6 PREPARED BY TERRI STEWART, TECHNICAL DATA PRINTS ARE NOT TO SCALE, ARE LOANED SUBJECT TO RETURN UPON DEMAND, WITH THE EXPRESS CONDITION THAT THEY WILL NOT BE USED IN ANY WAY DETRIMENTAL TO THE r_,,EA,F, dE~ ~r-F--C'TlarC ~ CERTIFIED FOR SHAFT AND MOUNTING DIMENSIONS ONLY ......... JL. .j~*T,";;':" 225B6500EF~';']~;~ R V DESCNIP! IUN I)AI'I:. APPf,'DVED R£VIS~:U ~ RI:DI~Ak~. 910-87,1 RLC 30, O I ....... 1 I .......... ~ 50i0~ Ill II _,,,.. .......... .~r 31 '"m'1 ,:,.,,.,,~.,,,, ....-~/-:'~--,, ,~ ..........,,. ,,, ---t ' ,[ ..... I ' I --9.311 ..... ......... 0 9 / I5.3't II 1.50 .... · t 4 ~ ; 2.00 - i. 00 2. 375 I1.~ [ .... 2.374 10.9~ --. DIA 4.00-8 NPT (SEE NOTES) 2.614 .47 I00-11 I/2-NP51 H~E5) (449 FR)- ' -- 27.30 I' NOTES: FIRST MADE FOR 5K449SS201 I. CONDUIT BOx MAY BE .PLACED WITH THE ENTRANCE DOWN. UP DR TOWARD DR I VE END. ,...,. o,,.~..,mc m,.~ca,,c.B IGNATURES I DATE O,~s~ ~ ,- ,~' ~'~ O. ~AGAR 031101~ 2. F'I ASH. AS SHOWN. ,~-K,~ ~ltl WalR. Imdina 3. F - 2 ASH. - CONDU I T BOX ON OPPOS ITE S I DE . , ~ ,,,~, ~ c~ ......... ,~ OUTLINE ~c. ~ ~ ,sin D.WAGAR 03/l ll~ ' 447144BT8 T.E.F.C. IACCEBBORY 10X] .,~.,~ 700 CU. IN. CONDUIT BOX