ST9902- LR150311J RLLIFlfICE JVC3F_0TECHr11Cf1L ROUP Acct ID: 1770 Consulting Engineering * Geotechnical Engineering * Construction Materials 3228 Halifax Street, Suite A, Dallas, Texas 75247 Phone: (972) 444-8889 Fax: (972) 444-8893 File No: C13-0634 Report Date: 03/11/2015 Project: West Sandy Lake Road Location: Sidewalk in Median - Cottonwood Branch Bridge and W. Sandy Lake Rd Client: City of Coppell REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST Material: Concrete Date Sampled: 03/02/2015 Sampled By: Hickman, Brad By Order Of: Royse Order Number: 1770 Number of Specimens: 5 LAB NO: 181472 Test Method: See Below TEST RESULTS Report No: 181472 Page 1 of 1 Maximum Compressive Average Spec Age Tested Diameter Area Load Cure Strength Strength Tested Nbr (date : days) (in) (int) (lbs) Break Type Loc (PSI) (PSI) By Comments A 03/09/15: 7 4.00 12.57 48,350 Type 3 Lab 3,850 3,850 B 03/30/15:28 4.00 12.57 Lab C 03/30/15:28 4.00 12.57 Lab D 03/30/15:28 4.00 12.57 Lab E HOLD (see remarks) - M-ni RF] IU B 1111 E Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Specification Strength: 3,600 psi @ 28 days Slump: 3-5 Slump: 3.5 Inches Transported By: TXI Air Content: 3-6 Air Content: 4.2% Source/Sampled At: Truck / Center Mix Code: 8272 Plant: 131 Date Received: 03/03/2015 Truck/Ticket No: 0 / 2690639 Curing Method: Standard Time Sampled: 11:20 am Time Batched: 10:38 am Temp.: Ambient: 36°F Mix: 50°F Quantity Represented: 10 cu. yds. at 10 cu. yds. placed Remarks: Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ASTM C31, C172, C143, C231 or C173, C1064 and C138. Compressive strength tests per ASTM C39. Client: City of Coppell Attn: Mr. Rick O'Dell (1 -cc copy) Orig: City of Coppell (Coppell, TX) Attn: Mr Keith Marvin, P.E. Respectfully Submitted, Alliance Geotechnical Group Perry C. Kakara, CME Department Manager THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION..