Acct ID: 1770 File No: C15-0812
Report Date: 11/18/2015 Previously Reported: 10/30/2015
Project: Freeport Parkway North
Location: Paving culvert box
Client: City of Coppell
REPORT REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST
TEST RESULTS
Set: 1 of 2 Material: Concrete
Location: Station 13+14.10
Spec
Nbr
A
B
C
D
Date Sampled: 10/20/2015
Sampled By: Reyes, Jason
By Order Of: Walter
Order Number: 1770
LAB NO: 195979
Test Method: See Below
Report No: 195979
Page 1 of 2
Number of Specimens: 4
Type 1
Specification
Strength: 4,000 psi @ 28 days
Slump: 3-6
Air Content: 3-5
Comments
HOLD (see remarks) -
]F�
Type 2 Type 3 Type 4 Type 5 Type 6
CONFORMS
Slump: 6 0 Inches Transported By: LMC
Air Content: 4.8% Source/Sampled At: Truck I Center
Mix Code: 1701 Plant: 956
Date Received: 10/21/2015 Truck/Ticket No: 3032 / 63096239
Curing Method: Standard
Time Sampled: 8:20 am
Time Batched: 7:39 am
Temp.: Ambient: 60°F Mix: 87°F
Unit Weight: 140.5 #/cu ft
Quantity Represented: 9.5 cu. yds. at 19 cu. yds. placed of a 114 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
C1064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617
Ong'. City of Coppell (Coppell, TX) Attn: Mr. Rick O'Dell (1 -cc copy)
Respectfully Submitted,
Alliance Geotech
n
ical Group
Perry C. Kakara, SET, CME Department Manager
THIS REPORTAPPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
TIIE QUALITIES OF APPARENTLY IDENI ICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED. TI'IESF REPORTS ART_ FOR TIME EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION
Maximum
Compressive
Average
Age Tested
Diameter
Area
Load
Cure
Strength
Strength Tested
(date : days)
(in)
(int)
(Ibs)
Break Type
Loc
(PSI)
(PSI) By
10/27/15: 7
6.00
28.27
106,915
Type 3
Lab
3,780
3,780
11/17/15: 28
6.00
28.27
137,380
Type 3
Lab
4,860
JR
11/17/15: 28
6.00
2827
134,940
Type 3
Lab
4,770
4,820 JR
Type 1
Specification
Strength: 4,000 psi @ 28 days
Slump: 3-6
Air Content: 3-5
Comments
HOLD (see remarks) -
]F�
Type 2 Type 3 Type 4 Type 5 Type 6
CONFORMS
Slump: 6 0 Inches Transported By: LMC
Air Content: 4.8% Source/Sampled At: Truck I Center
Mix Code: 1701 Plant: 956
Date Received: 10/21/2015 Truck/Ticket No: 3032 / 63096239
Curing Method: Standard
Time Sampled: 8:20 am
Time Batched: 7:39 am
Temp.: Ambient: 60°F Mix: 87°F
Unit Weight: 140.5 #/cu ft
Quantity Represented: 9.5 cu. yds. at 19 cu. yds. placed of a 114 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
C1064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617
Ong'. City of Coppell (Coppell, TX) Attn: Mr. Rick O'Dell (1 -cc copy)
Respectfully Submitted,
Alliance Geotech
n
ical Group
Perry C. Kakara, SET, CME Department Manager
THIS REPORTAPPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
TIIE QUALITIES OF APPARENTLY IDENI ICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED. TI'IESF REPORTS ART_ FOR TIME EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION
flLLIAI'ICE
GGEOTECHI'iICRL
GROU
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444-8889 Fax: (972) 444-8893
Acct ID: 1770 File No: C15-0812
Report Date: 11/18/2015 Previously Reported: 10/30/2015
Project: Freeport Parkway North
Location: Paving culvert box
Client: City of Coppell
REPORT REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST
Set: 2 of 2
Location: Station 11+87.10
Spec
Nbr
A
B
C
D
TEST RESULTS
Material: Concrete
Date Sampled: 10/20/2015
Sampled By: Reyes, Jason
By Order Of: Walter
Order Number: 1770
LAB NO: 195979
Test Method. See Below
Report No: 195979
Page 2 of 2
Number of Specimens: 4
Type 1
Specification
Strength: 4,000 psi @ 28 days
Slump: 3-6
Air Content: 3-5
Comments
HOLD (see remarks) -
11 1 1 'le, I I I I I I'. -I I I
Type 2 Type 3 Type 4 Type 5 Type 6
CONFORMS
Slump: 4.5 Inches Transported By: LMC
Air Content: 4.1 % Source/Sampled At: Truck / Center
Mix Code: 1701 Plant: 956
Date Received: 10/21/2015 Truck/Ticket No: 1420 / 63096247
Curing Method: Standard
Time Sampled: 10:15 am
Time Batched: 9:21 am
Temp.: Ambient: 66°F Mix: 88°F
Unit Weight: 144.8 #/cu ft
Quantity Represented: 9.5 cu. yds. at 85.5 cu. yds. placed of a 114 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
01064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617.
Orifi: City of Coppell (Coppell, TX) Attm Mr Rick O'Dell (1 -cc copy)
Respectfully Submitted,
Alliance Geotechnical Group
Perry C, Kakara, SET, CME Department Manager
I HIS REPORT APPLIES ONLY TO 1 HE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUA[ ITIES OF APPARENTLY IDEM ICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS 50
NOTED THESE REPORTS ARE FOR THE EXCLUSIVE USE OF TI IE ADDRESSFD Ct IENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION.
Maximum
Compressive
Average
Age Tested
Diameter
Area
Load
Cure
Strength
Strength
Tested
(date : days)
(in)
(in')
(Ibs)
Break Type
Loc
(PSI)
(PSI)
By
10/27/15: 7
6.00
28.27
110,905
Type 3
Lab
3,920
3,920
JR
11/17/15: 28
6.00
28.27
142,025
Type 3
Lab
5,020
JR
11/17/15: 28
6.00
28.27
144,660
Type 3
Lab
5,120
5,070
JR
Type 1
Specification
Strength: 4,000 psi @ 28 days
Slump: 3-6
Air Content: 3-5
Comments
HOLD (see remarks) -
11 1 1 'le, I I I I I I'. -I I I
Type 2 Type 3 Type 4 Type 5 Type 6
CONFORMS
Slump: 4.5 Inches Transported By: LMC
Air Content: 4.1 % Source/Sampled At: Truck / Center
Mix Code: 1701 Plant: 956
Date Received: 10/21/2015 Truck/Ticket No: 1420 / 63096247
Curing Method: Standard
Time Sampled: 10:15 am
Time Batched: 9:21 am
Temp.: Ambient: 66°F Mix: 88°F
Unit Weight: 144.8 #/cu ft
Quantity Represented: 9.5 cu. yds. at 85.5 cu. yds. placed of a 114 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
01064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617.
Orifi: City of Coppell (Coppell, TX) Attm Mr Rick O'Dell (1 -cc copy)
Respectfully Submitted,
Alliance Geotechnical Group
Perry C, Kakara, SET, CME Department Manager
I HIS REPORT APPLIES ONLY TO 1 HE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUA[ ITIES OF APPARENTLY IDEM ICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS 50
NOTED THESE REPORTS ARE FOR THE EXCLUSIVE USE OF TI IE ADDRESSFD Ct IENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION.
HLLIHnCE
GEOTKHf11CfiL
GROUP
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444-8889 Fax: (972) 444-8893
Acct ID: 1770
Date Received: 11/11/2015 ruc c
File No: C15-0812
Date Sampled: 11/10/2015
Report Date: 11/18/2015
Sampled By: Smith, Vernon
Project: Freeport Parkway North
By Order Of: Walter
Location: Retaining wall at Station 0+4,
Sampled-, Freeport Parkway
Order Number:1770
eastbound wall
Number of
Client: City of Coppell
Specimens: 4
REPORT: REPORT OF CONCRETE COMPRESSIVE
STRENGTH TEST
LAB NO: 197140
Material: Concrete
Test Method: See Below
TEST RESULTS
Report No: 197140
Page 1 of 1
Maximum Compressive
Average
Spec Age Tested Diameter Area
Load Cure Strength
(PSI)
Strength Tested
(PSI) By
Nbr (date : days) (in) (inz)
(lbs) Break Type Loc
Comments
A 11/17/15 :7 6.00 28.27
120,220 Type 3 Lab 4,250
4.250 JR
B 12/08/15:28 6.00 28.27
Lab
C 12/08/15: 28 6.00 2827
Lab
HOLD (see remarks)
D
_
Type 1
Type 2 Type 3 Type 4 Type 5
Type 6
Specification
Strength: 3,600 psi @ 28 days
Slump: 3-6
Slump: 5.0 Inches
Transported By: LMC
Air Content: 3-5
Air Content: 4.5%
Source/Sampled At: Truck / Center
Mix Code: 1701
Plant: 956
T k/TIt Na 7060/ 63096631
k
e
Curing Method: Standard
Time Sampled: 11:30 am
Time Batched: 10:26 am
Temp.: Ambient: 66°F Mix: 70°F
Unit Weight: 144 8 #/cu ft
Quantity Represented: 9.5 cu. yds. at 9.5 cu- yds. placed of a 19.0 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
C1064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617.
Orlq. City of Coppell (Coppell, TX) Attn: Mr Rick O'Dell (1 -cc copy)
Respectfully Submitted,
Alliance Geotechnical Group
r ,E
Perry C. Kakara, SET, CME Department Manager
THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTE -D. THESE_ REPORTS ARE FOR THE EXCLUSIVE_ USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION.