ST0502B- LR160111 (2)ALLIANCE
GEOTEC NIUIL
Wour
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444-8889 Fax: (972) 444-8893
Acct ID: 1770 File No: C15-0812
Report Date: 01/11/2016
Project: Freeport Parkway North
Location: Southbound outside lane Freeport Parkway
Client: City of Coppell
REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST
Set: 1 of 17
Location: Station 29+40
Spec
Age Tested
Diameter
Area
Nbr
(date : days)
(in)
(int)
A
01/09/16:3
6.00
28.27
B
01/13/16:7
6.00
28.27
C
02/03/16:28
6.00
28.27
D
02/03/16:28
6.00
28.27
E
TEST RESULTS
Material: Concrete
Maximum
Compressive
Load
Cure
Strength
(lbs)
Break Type Loc
(PSI)
106,935
Type 3 Lab
3,780
Lab
Lab
Lab
Type 1
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3
Air Content: 3-5
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 1 of 17
Number of Specimens: 5
Average
Strength Tested
(PSI) By Comments
3,780 JR
HOLD (see remarks) -
r-
VVI
Type 2 Type 3 Type 4 Type 5 Type 6
Slump: 2.0 Inches Transported By: Tiseo
Air Content: 3.1% Source/Sampled At: Truck / Center
Mix Code: 2605 M Plant: On -Site
Date Received: 01/07/2016 TruCr, cket No: N/A/ 23918
Curing Method: Standard
1 ime Sampled: 8:05 am
Time Batched: 8:25 am
Temp.: Ambient: 43°F Mix: 58°F
Unit Weight: 148 #/cu ft
Quantity Represented: 10 cu. yds, at 10 cu. yds. placed of a 1600 cu, yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
C1064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617.
Ong: City of Coppell (Coppell, TX) Attn: Mr Rick O'Dell (1 -cc copy)
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, SET, CME Department Manager
I HIS RL=PORI APPLIF_S ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO 1"HE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
11 IF QJALIrIES OF APPAREN ILY IDI--N'TICAI. OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
N01 ED THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION
RLLIHPICE
GGEOTKMIYICflL
GROUP
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444-8889 Fax: (972) 444-8893
Acct ID: 1770 File No: C15-0812
Report Date: 01/11/2016
Project: Freeport Parkway North
Location: Southbound outside lane Freeport Parkway
Client: City of Coppell
REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST
Set: 2 of 17
Location: Station 28+60
Spec
Nbr
A
B
C
D
E
TEST RESULTS
Material: Concrete
Type 1
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3
Air Content: 3-5
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 2 of 17
Number of Specimens: 5
Compressive
Average
Strength
Maximum
(PSI)
Age Tested
Diameter
Area
Load
Cure
(date : days)
(in)
(in')
(lbs)
Break Type Loc
01/09/16: 3
6.00
28.27
116,860
Type 3 Lab
01/13/16:7
6.00
28.27
Lab
02/03/16:28
6.00
28.27
Lab
02/03/16:28
6.00
28.27
Lab
Type 1
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3
Air Content: 3-5
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 2 of 17
Number of Specimens: 5
Compressive
Average
Strength
Strength Tested
(PSI)
(PSI) By Comments
4,130
4,130 JR
4 r
Type 2 Type 3 Type 4
Slump: 1.0 Inches
Air Content: 2.7%
Mix Code: Class P
HOLD (see remarks) -
Type 5 Type 6
Transported By: Tiseo
Source/Sampled At: Truck / Center
Plant: On -Site
Date Received: 01/07/2016 Truck/Ticket No: N/AI 10
Curing Method: Standard
Time Sampled: 8:35 am
Time Batched: 8:54 am
Temp.: Ambient: 42°F Mix: 56°F
Unit Weight: 150.8 #/cu ft
Quantity Represented: 10 cu. yds. at 100 cu. yds. placed of a 1600 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
C1064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617.
Orig: City of Coppell (Coppell, FX) Attn: Mr Rick O'Dell (1 -cc copy) Respectfully Submitted,
Alliance Geotechnical Group
1Aa
Perry C. Kakara, SET, CME Department Manager
THIS REPORT APPLIES ONLY I O THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THF QUALITIES OF APPARENTLY IDENIICAI- OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO I"HEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED. THESE REPORT"S ARE FOR I'HE EXCLUSIVE USE OI: THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION,
RLLiAnce
GEOTECHftICRL
GR UP
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444-8889 Fax: (972) 444-8893
Acct ID: 1770 File No: C15-0812
Report Date: 01/11/2016
Project: Freeport Parkway North
Location: Southbound outside lane Freeport Parkway
Client: City of Coppell _
REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST
Set: 3 of 17
Location:
Spec
Nbr
A
B
C
D
E
TEST RESULTS
Material: Concrete
Type 1
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3
Air Content: 3-5
�'(�
Type 2 Type 3 Type 4 Type 5
Slump: 1.0 Inches
Air Content: 3.0%
Mix Code: Class P
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 3 of 17
Number of Specimens: 5
Average
Strength Tested
(PSI) By Comments
4,230 JR
HOLD (see remarks) -
Type 6
Transported By: Tiseo
Source/Sampled At: Truck / Center
Plant: On -Site
Date Received: 01/07/2016 TrucklTicket No: NIA/ 20
Curing Method: Standard
Time Sampled: 9:04 am
Time Batched: 9:23 am
Temp.: Ambient: 43°F Mix: 59°F
Unit Weight: 149.6 #/Cu ft
Quantity Represented: 10 cu yds at 200 cu. yds placed of a 1600 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
C1064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617.
orig: City of Coppell (Coppell, TX) Attn: Mr Rick O'Dell (1 -cc copy)
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, SET, CME Department Manager
THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THF QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED. THESE_ REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION
Maximum
Compressive
Age Tested
Diameter
Area
Load
Cure
Strength
(date : days)
(in)
(in')
(lbs)
Break Type Loc
(PSI)
01/09/16: 3
6.00
28.27
119,740
Type 3 Lab
4,230
01/13/16:7
6.00
28.27
Lab
02/03/16:28
6.00
28.27
Lab
02/03/16:28
6.00
28.27
Lab
Type 1
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3
Air Content: 3-5
�'(�
Type 2 Type 3 Type 4 Type 5
Slump: 1.0 Inches
Air Content: 3.0%
Mix Code: Class P
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 3 of 17
Number of Specimens: 5
Average
Strength Tested
(PSI) By Comments
4,230 JR
HOLD (see remarks) -
Type 6
Transported By: Tiseo
Source/Sampled At: Truck / Center
Plant: On -Site
Date Received: 01/07/2016 TrucklTicket No: NIA/ 20
Curing Method: Standard
Time Sampled: 9:04 am
Time Batched: 9:23 am
Temp.: Ambient: 43°F Mix: 59°F
Unit Weight: 149.6 #/Cu ft
Quantity Represented: 10 cu yds at 200 cu. yds placed of a 1600 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
C1064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617.
orig: City of Coppell (Coppell, TX) Attn: Mr Rick O'Dell (1 -cc copy)
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, SET, CME Department Manager
THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THF QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED. THESE_ REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION
RLLiAnce
GGEOTECHf/1C19L
G UP
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444-8889 Fax: (972) 444-8893
Acct ID: 1770 File No: C15-0812
Report Date: 01/11/2016
Project: Freeport Parkway North
Location: Southbound outside lane Freeport Parkway
Client: City of Coppell
REPORT REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST
Set: 4 of 17
Location: Station 27+60
Spec
Nbr
A
B
C
D
E
TEST RESULTS
Material: Concrete
Type 1
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3
Air Content: 3-5
Type 2
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 4 of 17
Number of Specimens: 5
Compressive
Average
Strength
Maximum
(PSI)
Age Tested
Diameter
Area
Load
Cure
(date : days)
(in)
(inz)
(Ibs)
Break Type Loc
01/09/16: 3
6.00
28.27
117,350
Type 3 Lab
01/13/16:7
6.00
28.27
Lab
02/03/16: 28
600
28.27
Lab
02/03/16: 28
600
28.27
Lab
Type 1
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3
Air Content: 3-5
Type 2
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 4 of 17
Number of Specimens: 5
Compressive
Average
Strength
Strength Tested
(PSI)
(PSI) By Comments
4,150
4,150 JR
u,ti i
Type 3 Type 4
Slump: 1.0 Inches
Air Content: 3.4%
Mix Code: Class P
HOLD (see remarks) -
Type 5 Type 6
Transported By: Tiseo
Source/Sampled At: Truck / Center
Plant: On -Site
Date Received: 01/07/2016 Truck/Ticket No: KI/AI 30
Curing Method: Standard
Time Sampled: 9:35 am
Time Batched: 10:03 am
Temp.: Ambient: 43°F Mix: 58°F
Unit Weight: 150 #/cu ft
Quantity Represented: 10 cu. yds. at 300 cu yds. placed of a 1600 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
C1064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617.
Ong: City of Coppell (Coppell, TX) Attn: Mr Rick O'Dell (1 -cc copy)
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, SET, CME Department Manager
Tl its REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
I HE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION
HLLinNCE
GEOTECHNICRIL
+GF our
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444-8889 Fax: (972) 444-8893
Acct ID: 1770 File No: C15-0812
Report Date: 01/11/2016
Project: Freeport Parkway North
Location: Southbound outside lane Freeport Parkway
Client. City of Coppell
REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST
TEST RESULTS
Set: 5 of 17
Material: Concrete
Location: Station 26+65
Maximum
Spec Age Tested
Diameter
Area
Load
Cure
Nbr (date : days)
(in)
(int)
(lbs) Break Type
Loc
A 01/09/16: 3
6.00
28.27
126,610 Type 3
Lab
B 01/13/16:7
6.00
28.27
Lab
C 02/03/16:28
6.00
28.27
Lab
D 02/03/16:28
6.00
28.27
Lab
E
f
Type
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3
Air Content: 3-5
Compressive
Strength
(PSI)
4,480
1 Type 2 Type 3 Type 4
Slump: 1.5 Inches
Air Content: 3.4%
Mix Code: Class P
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 5 of 17
Number of Specimens: 5
Average
Strength Tested
(PSI) By Comments
4,480 JR
HOLD (see remarks) -
� I 1_�_ I
Type 5 Type 6
Transported By: Tiseo
Source/Sampled At: Truck / Center
Plant: On -Site
Date Received: 01/07/2016 Truck/Ticket No: N/A / 40
Curing Method: Standard
I ime Sampled: 10:10 am
Time Batched: 10:34 am
Temp.: Ambient: 44°F Mix: 60°F
Unit Weight: 148.4 #/cu ft
Quantity Represented: 10 cu. yds at 400 cu. yds. placed of a 1600 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
C1064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617.
Orig: City or Coppell (Coppell, FX) Attn: Mr Rick O'Dell (1 -cc copy)
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, SET, CME Department Manager
I HIS REPORI APPLIES ONLY TO I HE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALITIES OFAPPARENTLY IDENTICAI OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENTAN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED. TFIESE REPOR rS ARE FOR TI IE EXCLUSIVE USE OF THE ADDRESSED CLIENTAND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION
RuiAnce
GGEOTECHnICRL
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444-8889 Fax: (972) 444-8893
Acct ID: 1770 File No: C15-0812
Report Date: 01/11/2016
Project: Freeport Parkway North
Location: Southbound outside lane Freeport Parkway
Client: City of Coppell
REPORT. REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST
TEST RESULTS
Set: 6 of 17 Material: Concrete
Location: Station 25+71
Spec
Nbr
A
B
C
D
E
I
Type 1
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3
Air Content: 3-5
Type 2 Type 3 Type 4 Type 5
Slump: 1.0 Inches
Air Content: 3.8%
Mix Code: Class P
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 6of17
Number of Specimens: 5
Average
Strength Tested
(PSI) By Comments
4,720 JR
HOLD (see remarks) -
Type 6
Transported By: Tiseo
Source/Sampled At: Truck / Center
Plant: On -Site
Date Received: 01/07/2016 Truck/Ticket No: NIA/ 50
Curing Method: Standard
Time Sampled: 10:45 am
'Time Batched: 11:01 am
Temp.: Ambient: 44°F Mix: 59'F
Unit Weight: 148.4 #/cu ft
Quantity Represented: 10 cu. yds at 500 cu yds. placed of a 1600 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172_, C143,
C1064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617.
Orig. City of Coppell (Coppell, TX) Attn: Mr, Rick O'Dell (1 -cc copy)
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, SET, CME Department Manager
THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALITIES OF APPARENTLY IDENTICAL. OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOT ED THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION
Maximum
Compressive
Age Tested
Diameter
Area
Load
Cure
Strength
(date : days)
(in)
(in')
(Ibs)
Break Type Loc
(PSI)
01/09/16: 3
6.00
28.27
133,560
Type 3 Lab
4,720
01/13/16: 7
6.00
2827
Lab
02/03/16:28
6.00
28.27
Lab
02/03/16:28
6.00
28.27
Lab
I
Type 1
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3
Air Content: 3-5
Type 2 Type 3 Type 4 Type 5
Slump: 1.0 Inches
Air Content: 3.8%
Mix Code: Class P
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 6of17
Number of Specimens: 5
Average
Strength Tested
(PSI) By Comments
4,720 JR
HOLD (see remarks) -
Type 6
Transported By: Tiseo
Source/Sampled At: Truck / Center
Plant: On -Site
Date Received: 01/07/2016 Truck/Ticket No: NIA/ 50
Curing Method: Standard
Time Sampled: 10:45 am
'Time Batched: 11:01 am
Temp.: Ambient: 44°F Mix: 59'F
Unit Weight: 148.4 #/cu ft
Quantity Represented: 10 cu. yds at 500 cu yds. placed of a 1600 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172_, C143,
C1064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617.
Orig. City of Coppell (Coppell, TX) Attn: Mr, Rick O'Dell (1 -cc copy)
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, SET, CME Department Manager
THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALITIES OF APPARENTLY IDENTICAL. OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOT ED THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION
RU.IAi10E
4 G GEt7TECHfIICPIL
GROUP
Consulting Engineering " Geotechnical Engineering " Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444-8889 Fax: (972) 444-8893
Acct ID: 1770 File No: C15-0812
Report Date: 01/11/2016
Project: Freeport Parkway North
Location: Southbound outside lane Freeport Parkway
Client: City of Coppell
REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST
TEST RESULTS
Set: 7 of 17 Material: Concrete
Location: Station 25+20
Spec
Nbr
A
B
C
D
E
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 7of17
Number of Specimens: 5
Average
Strength Tested
(PSI) By Comments
4,220 JR
Type 1 Type 2 Type 3 Type 4 Type 5 Type 6
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3 Slump: 1.0 Inches
Air Content: 3-5 Air Content: 3.8%
Mix Code: Class P
HOLD (see remarks) -
Transported By: Tiseo
Source/Sampled At: Truck / Center
Plant: On -Site
Date Received: 01107/2016 Truck/Ticket No: N/A 160
Curing Method: Standard
I ime Sampled: 11:10 am
'Time Batched: 11:27 am
Temp.: Ambient: 45°F Mix: 59°F
Unit Weight: 147.2 #/cu ft
Quantity Represented: 10 cu. yds at 600 cu. yds, placed of a 1600 cu yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
C1064 and C138 Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617
Orig: City of Coppell (Coppell, TX) Attn: Mr Rick O'Dell (1 -cc copy)
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, SET, CME Department Manager
I HIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO FHE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALITIES OF APPARENTLY IDENTICAL. OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS 50
NOTED. THESE RF FOR I S ARE FOR THE E=XCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION
Maximum
Compressive
Age Tested
Diameter
Area
Load
Cure
Strength
(date : days)
(in)
(in')
(lbs)
Break Type Loc
(PSI)
01/09/16: 3
6.00
28.27
119,335
Type 3 Lab
4,220
01/13/16: 7
6.00
2827
Lab
02/03/16:28
6.00
28.27
Lab
02/03/16: 28
6.00
2827
Lab
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 7of17
Number of Specimens: 5
Average
Strength Tested
(PSI) By Comments
4,220 JR
Type 1 Type 2 Type 3 Type 4 Type 5 Type 6
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3 Slump: 1.0 Inches
Air Content: 3-5 Air Content: 3.8%
Mix Code: Class P
HOLD (see remarks) -
Transported By: Tiseo
Source/Sampled At: Truck / Center
Plant: On -Site
Date Received: 01107/2016 Truck/Ticket No: N/A 160
Curing Method: Standard
I ime Sampled: 11:10 am
'Time Batched: 11:27 am
Temp.: Ambient: 45°F Mix: 59°F
Unit Weight: 147.2 #/cu ft
Quantity Represented: 10 cu. yds at 600 cu. yds, placed of a 1600 cu yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
C1064 and C138 Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617
Orig: City of Coppell (Coppell, TX) Attn: Mr Rick O'Dell (1 -cc copy)
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, SET, CME Department Manager
I HIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO FHE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALITIES OF APPARENTLY IDENTICAL. OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS 50
NOTED. THESE RF FOR I S ARE FOR THE E=XCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION
RLLIfiNCE
(� G cEorecHrncRL
GROUP
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444-8889 Fax: (972) 444-8893
Acct ID: 1770 File No: C15-0812
Report Date: 01/11/2016
Project: Freeport Parkway North
Location: Southbound outside lane Freeport Parkway
Client: City of Coppell
REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST
Set: 8 of 17
Location: Station 24+20
Spec
Nbr
A
B
C
D
E
TEST RESULTS
Material: Concrete
Type 1
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3
Air Content: 3-5
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 8 of 17
Number of Specimens: 5
Compressive
Average
Strength
Maximum
(PSI)
Age Tested
Diameter
Area
Load
Cure
(date : days)
(in)
(in Z)
(lbs)
Break Type Loc
01/09/16: 3
6.00
2827
114,885
Type 3 Lab
01/13/16:7
6.00
28.27
Lab
02/03/16:28
6.00
28.27
Lab
02/03/16 ; 28
6.00
28.27
Lab
Type 1
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3
Air Content: 3-5
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 8 of 17
Number of Specimens: 5
Compressive
Average
Strength
Strength Tested
(PSI)
(PSI) By Comments
4,060
4,060 JR
II I �I : � i f • I•: y, 11 ` I � � '� l
Type 2 Type 3 Type 4 Type 5 Type 6
HOLD (see remarks) -
Slump: 2.0 Inches Transported By: Tiseo
Air Content: 4.4% Source/Sampled At: Truck / Center
Mix Code: Class P Plant: On -Site
Date Received: 01/07/2016 Truck/Ticket III N/AI70
Curing Method: Standard
Time Sampled: 11:35 am
Time Batched: 11,53 am
Temp: Ambient: 45°F Mix: 59°F
Unit Weight: 147.2 #/cu ft
Quantity Represented: 10 cu. yds at 700 cu. yds placed of a 1600 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
C1064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617.
Orig: City of Coppell (Coppell. TX) Attn: Mr Rick O'Dell (1 -cc copy)
Respectfully Submitted,
Alliance Geotechnical Group
F
Perry C. Kakara, SET, CME Department Manager
THIS REPORT APPL IES ONLY TO TI 1E STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QJALI TIES OF APPARENT LY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENTAN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
N01 ED THESE REPORTS ARE FOR THE EXCL USIVE USE OF THE ADDRESSED CLIEN T AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION
ALLiAnte
GEOTECHfIICRL
GROUP
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444-8889 Fax: (972) 444-8893
Acct ID: 1770 File No: C15-0812
Report Date: 01/11/2016
Project: Freeport Parkway North
Location: Southbound outside lane Freeport Parkway
Client:
REPORT:
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
City of Coppell
REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST LAB NO: 200468
Test Method: See Below
TEST RESULTS Report No: 200468
Page 9 of 17
Set: 9 of 17
Location: Station 23+30
Spec
Nbr
A
B
C
D
E
Material: Concrete
Number of Specimens: 5
Date Received: 01/07/2016 Truc Ice o.
Curing Method: Standard
Time Sampled: 12:05 pm
Time Batched: 12:21 pm
Temp.: Ambient: 45°F Mix: 58°F
Unit Weight: 150.8 #/cu ft
Quantity Represented: 10 cu yds. at 800 cu yds placed of a 1600 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
C1064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617.
Ong: City of Coppell (Coppell, TX) Attn: Mr Rick O'Dell (1 -cc copy)
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, SET, CME Department Manager
I ITIS REPORT APPI IES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
I VIE OJALI IIES OF APPARENT1 Y IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURE=S, NOR DO -THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED. T HESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION.
Maximum
Compressive
Average
Age Tested
Diameter
Area Load
Cure Strength
Strength Tested
(date : days)
(in)
(int) (lbs)
Break Type Loc (PSI)
(PSI) By Comments
01/09/16: 3
6.00
28.27 119,075
Type 3 Lab 4,210
4,210 JR
01/13/16: 7
600
28.27
Lab
02/03/16:28
6.00
28.27
Lab
02/03/16:28
6.00
28.27
Lab
HOLD (see remarks) -
Type 1 Type
2 Type 3 Type 4 Type 5
Type 6
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3
Slump: 1.0 Inches
Transported By: Tiseo
Air Content: 3-5
Air Content: 3.0%
Source/Sampled At: Truck I Center
Mix Code: Class P
Plant: On -Site
11 I. k t N N/A / 80
Date Received: 01/07/2016 Truc Ice o.
Curing Method: Standard
Time Sampled: 12:05 pm
Time Batched: 12:21 pm
Temp.: Ambient: 45°F Mix: 58°F
Unit Weight: 150.8 #/cu ft
Quantity Represented: 10 cu yds. at 800 cu yds placed of a 1600 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
C1064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617.
Ong: City of Coppell (Coppell, TX) Attn: Mr Rick O'Dell (1 -cc copy)
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, SET, CME Department Manager
I ITIS REPORT APPI IES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
I VIE OJALI IIES OF APPARENT1 Y IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURE=S, NOR DO -THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED. T HESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION.
ALLiAnce
GGEOTKHPIICfiL
GROUP
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444-8889 Fax: (972) 444-8893
Acct ID: 1770 File No: C15-0812
Report Date: 01/11/2016
Project: Freeport Parkway North
Location: Southbound outside lane Freeport Parkway
Client: City of Coppell
REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST
TEST RESULTS
Set: 10 of 17 Material: Concrete
Location: Station 22+80
Spec
Nbr
A
B
C
D
E
Type 1
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3
Air Content: 3-5
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 10 of 17
Number of Specimens: 5
Average
Strength Tested
(PSI) By Comments
3,670 JR
HOLD (see remarks) -
Type 2 Type 3 Type 4 Type 5 Type 6
Slump: 2.5 Inches Transported By: Tiseo
Air Content: 4.4% Source/Sampled At: Truck / Center
Mix Code: Class P Plant: On -Site
Date Received: 01/07/2016 Truck/Ticket No: N/AI 90
Curing Method: Standard
Time Sampled: 12:30 pm
'Time Batched: 12:49 pm
Temp.: Ambient: 47°F Mix: 59°F
Unit Weight: 146.4 #/cu ft
Quantity Represented: 10 cu. yds. at 900 cu, yds placed of a 1600 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
C1064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617
Ong: City of Coppell (Coppell, TX) Attn: Mr Rick O'Dell (1 -cc copy)
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, SET, CME Department Manager
THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION.
Maximum
Compressive
Age Tested
Diameter
Area
Load
Cure
Strength
(date : days)
(in)
(in?)
(Ibs)
Break Type Loc
(PSI)
01/09/16: 3
6.00
2827
103,640
Type 3 Lab
3,670
01/13/16: 7
6 00
28.27
Lab
02/03/16:28
6.00
28.27
Lab
02/03/16: 28
6.00
2827
Lab
Type 1
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3
Air Content: 3-5
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 10 of 17
Number of Specimens: 5
Average
Strength Tested
(PSI) By Comments
3,670 JR
HOLD (see remarks) -
Type 2 Type 3 Type 4 Type 5 Type 6
Slump: 2.5 Inches Transported By: Tiseo
Air Content: 4.4% Source/Sampled At: Truck / Center
Mix Code: Class P Plant: On -Site
Date Received: 01/07/2016 Truck/Ticket No: N/AI 90
Curing Method: Standard
Time Sampled: 12:30 pm
'Time Batched: 12:49 pm
Temp.: Ambient: 47°F Mix: 59°F
Unit Weight: 146.4 #/cu ft
Quantity Represented: 10 cu. yds. at 900 cu, yds placed of a 1600 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
C1064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617
Ong: City of Coppell (Coppell, TX) Attn: Mr Rick O'Dell (1 -cc copy)
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, SET, CME Department Manager
THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION.
RLLIfifICE
`Q G GEOTECHnICfiL
GROUP
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444-8889 Fax: (972) 444-8893
Acct ID: 1770 File No: C15-0812 Date Sampled: 01/06/2016
Report Date: 01/11/2016 Sampled By: Corbin, Rodney
Project: Freeport Parkway North By Order Of: Walter
Location: Southbound outside lane Freeport Parkway Order Number: 1770
Client: City of Coppell
REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST LAB NO: 200468
Test Method: See Below
TEST RESULTS Report No: 200468
Page 11 of 17
Set: 11 of 17 Material: Concrete Number of Specimens: 5
Location: Station 21+50
Maximum Compressive Average
Spec Age Tested Diameter Area Load Cure Strength Strength Tested
Nbr (date : days) (in) (in') (Ibs) Break Type Loc (PSI) (PSI) By Comments
A 01/09/16: 3 6.00 28.27 115,595 Type 3 Lab 4,090 4,090 JR
B 01/13/16:7 6.00 28.27 Lab
C 02/03/16: 28 6.00 2827 Lab
D 02/03/16:28 6.00 28.27 Lab
E HOLD (see remarks) s s
Type 1 Type 2 Type 3 Type 4 Type 5 Type 6
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3 Slump: 2.0 Inches Transported By: Tiseo
Air Content: 3-5 Air Content: 4.6% Source/Sampled At: Truck / Center
Mix Code: Class P Plant: On -Site
Date Received: 01/07/2016 Truck/Ticket No: N/A / 100
Curing Method: Standard
Time Sampled: 1:00 pm
Time Batched: 1:31 pm
Temp.: Ambient: 47°F Mix: 59°F
Unit Weight: 148 #/cu ft
Quantity Represented: 10 cu. yds at 1000 cu, yds. placed of a 1600 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
C1064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617.
Orig: City of Coppell (Coppell, TX)Attn: Mr Rick O'Dell (1 -cc copy)
Respectfully Submitted,
Alliance Geotechnical Group
Perry C, Kakara, SET, CME Department Manager
1 ITIS REPORT APPLIES ONLY To T I IE. SIANDARDS OR PROCEDURES INDICATED AND 10 THE SAMPLES) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
I HI= QUALITIES OF APPARENTLY IDENTICAI OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOT EU THESE REPORTS ARE FOR THE EXCLUSIVE USE OF I HE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION
RLLIAnCE
GEOTKHfIfCHL
GROVP
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444-8889 Fax: (972) 444-8893
Acct ID: 1770 File No: C15-0812
Report Date: 01/11/2016
Project: Freeport Parkway North
Location: Southbound outside lane Freeport Parkway
Client: City of Coppell _
REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST
TEST RESULTS
Set: 12 of 17
Material: Concrete
Location: Station 20+50
Maximum
Compressive
Spec:
Age Tested
Diameter
Area
Load
Cure Strength
(PSI)
Nbr
(date : days)
(in)
(in')
(Ibs)
Break Type
LOG
A
01/09/16: 3
600
28 27
117,900
Type 3
Lab 4.170
B
01/13/16:7
6.00
28.27
Lab
C
02/03/16:28
6.00
28.27
Lab
D
02/03/16:28
6.00
28.27
Lab
E
04/14/16:99
6.00
28.27Lab
I jII IIIL_
_ .
�
ILk
I i
Type
1 Type 2 Type 3
Type 4 Type 5
Specification
Strength: 3,600
psi @ 28 days
Slump: 1-3
Slump:
1.0 Inches
Air Content: 3-5
Air Content:
3.6%
Mix Code:
Class P
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 12 of 17
Number of Specimens: 5
Average
Strength Tested
(PSI) By Comments
4,170 JR
7.
Type 6
Transported By: Tiseo
Source/Sampled At: Truck / Center
Plant: On -Site;
Date Received: 01 /07/2016 Truck /Ticket No: N/A 1110
Curing Method: Standard
Time Sampled: 1:40 pm
Time Batched: 1:59 pm
Temp.: Ambient: 46°F Mix: 60°F
Unit Weight: 149.6 #/cu ft
Quantity Represented: 10 cu. yds at 1100 cu yds. placed of a 1600 cu. yd. total placement
Rernarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
C1064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617
Onq: City of Coppell (Coppell, IX) Attn: Mr Rick O'Dell (1 -cc copy)
Respectfully Submitted,
Alliance Geotechnical Group
r
Perry C. Kakara, SET, CME Department Manager
THIS REPORT APPLIES ONLY To IHE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALTIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF I FIE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION
RLLIRnCE
GGEOTECFiI'IICRL
GiOUP
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444-8889 Fax: (972) 444-8893
Acct ID: 1770 File No: C15-0812
Report Date: 01/11/2016
Project: Freeport Parkway North
Location: Southbound outside lane Freeport Parkway
Client: City of Coppell
REPORT, REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST
Set: 13 of 17
Compressive
Location: Station 19+75
Cure
Strength
Spec Age Tested
Diameter
Area
Nbr (date : days)
(in)
(in')
A 01/09/16: 3
6.00
2827
B 01113/16:7
6.00
28.27
C 02/03/16:28
6.00
28.27
D 02/03116: 28
600
28.27
E
TEST RESULTS
Material: Concrete
Maximum
Compressive
Load
Cure
Strength
(lbs)
Break Type Loc
(PSI)
124,075
Type 3 Lab
4,390
Lab
Lab
Lab
Type 1
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3
Air Content: 3-5
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 13 of 17
Number of Specimens: 5
Average
Strength Tested
(PSI) By Comments
4,390 JR
HOLD (see remarks) -
�'T f 1 r l lI
Type 2 Type 3 Type 4 Type 5 Type 6
Slump: 2.0 Inches Transported By: Tiseo
Air Content: 4.9% Source/Sampled At: Truck / Center
Mix Code: Class P Plant: On -Site
Date Received: 01/07/2016 TrucklTicket III 120
Curing Method: Standard
Time Sampled: 2:10 pm
Time Batched: 2:27 pm
Temp.: Ambient: 47°F Mix: 58°F
Unit Weight: 146.4 #/cu ft
Quantity Represented: 10 cu. yds. at 1200 cu. yds. placed of a 1600 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
C1064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617.
Orig: City of Coppell (Coppell, TX) Attn: Mr Rick O'Dell (I -CC copy)
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, SET, CME Department Manager
THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCE=DURES INDICATED AND TO THE SAMPLE(S) TESTED ANDIOR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALrrIES OF APPARENTLY IDENTICAL. OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENTAN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED. 'THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENTAND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION
ALLIRfItE
GGE0TECHf11CRL
GROUP
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444-8889 Fax: (972) 444-8893
Acct ID: 1770 File No: C15-0812
Report Date: 01/11/2016
Project: Freeport Parkway North
Location: Southbound outside lane Freeport Parkway
Client: City of Coppell
REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST
Set: 14 of 17
Location: Station 19+19
Spec
Nbr
A
B
C
D
E
TEST RESULTS
Material: Concrete
Type 1
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3
Air Content: 3-5
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 14 of 17
Number of Specimens: 5
Compressive
Average
Strength
Maximum
(PSI)
Age Tested
Diameter
Area
Load
Cure
(date : days)
(in)
(int)
(lbs)
Break Type Loc
01/09/16 :3
6.00
28.27
124,075
Type 3 Lab
01/13/16:7
6.00
28.27
Lab
02/03/16: 28
6.00
2827
Lab
02/03/16:28
6.00
28.27
Lab
Type 1
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3
Air Content: 3-5
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 14 of 17
Number of Specimens: 5
Compressive
Average
Strength
Strength Tested
(PSI)
(PSI) By Comments
4,390
4,390 JR
Type 2 Type 3 Type 4 Type 5
Slump: 1 0 Inches
Air Content: 4.3%
Mix Code: Class P
HOLD (see remarks) -
Type 6
Transported By: Tiseo
Source/Sampled At: Truck / Center
Plant: On -Site
Date Received: 01/07/2016 Truck/Ticket No: NIA / 130
Curing Method: Standard
Time Sampled: 2:35 pm
Time Batched: 3:08 pm
Temp.: Ambient: 47°F Mix: 59°F
Unit Weight: 148.4 #/cu ft
Quantity Represented: 10 cu. yds at 1300 cu. yds, placed of a 1600 cu yd total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
C1064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617.
Ong: City o(Coppell (Coppell, TX) Attn: Mr Rick O'Dell (1 -cc copy) Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, SET, CME Department Manager
THIS REPORTAPPLIES ONI Y TO THE. STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALITIES OF APPARENTLY IDENTICAL OR SIMII-AR PRODUCTS OR PROCEDURE=S, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NO rEO THESE REPOR I S ARE FOR I HE FXCLUSIVE USF- OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION..
nLL inNcE
OEOTECHnIML
0hour
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444-8889 Fax: (972) 444-8893
Acct ID: 1770 File No: C15-0812
Report Date: 01/11/2016
Project: Freeport Parkway North
Location: Southbound outside lane Freeport Parkway
Client City of Coppell _
REPORT REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST
Set: 15 of 17
Location: Station 18+22
Spec
Nbr
A
B
C
D
E
TEST RESULTS
Material: Concrete
Type 1
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3
Air Content: 3-5
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 15 of 17
Number of Specimens: 5
Compressive
Average
Strength
Maximum
(PSI)
Age Tested
Diameter
Area
Load
Cure
(date : days)
(in)
(int)
(Ibs)
Break Type Loc
01/09/16: 3
6.00
28.27
112,705
Type 3 Lab
01/13/16:7
6.00
28.27
Lab
02/03/16:28
6.00
28.27
Lab
02/03/16:28
6.00
28.27
Lab
Type 1
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3
Air Content: 3-5
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 15 of 17
Number of Specimens: 5
Compressive
Average
Strength
Strength Tested
(PSI)
(PSI) By Comments
3,990
3,990 JR
Type 2 Type 3 Type 4 Type 5
Slump: 1.5 Inches
Air Content: 5.0%
Mix Code: Class P
HOLD (see remarks) -
I I
Type 6
Transported By: Tiseo
Source/Sampled At: Truck / Center
Plant: On -Site
Date Received: 01/07/2016 Truck/Ticket No: N/A 1140
Curing Method: Standard
Time Sampled: 3:15 pm
Time Batched: 3:36 pm
Temp.: Ambient: 48°F Mix: 55°F
Unit Weight: 147.6 #/cu ft
Quantity Represented: 10 cu. yds. at 1400 cu yds placed of a 1600 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, 0172, C143,
C1064 and C138. Compressive strength test per ASTM C39, Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617
Ong: City of Coppell (Cop pell, TX) Attn: Mr Rick O'Dell (1 -cc copy)
Respectfully Submitted,
Alliance Geotechnical Group
i
r
Perry C. Kakara, SET, CME Department Manager
THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS So
NO ED THESE REPORTS ARE FOR THF EXCLUSIVE USE OF FI IE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION,
RLLIAfICE
GGEOTKHhICRL
GROUP
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444-8889 Fax: (972) 444-8893
Acct ID: 1770 File No: C15-0812
Report Date: 01/11/2016
Project: Freeport Parkway North
Location: Southbound outside lane Freeport Parkway
Client: City of Coppell
REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST
TEST RESULTS
Set: 16 of 17
Average
Strength
Material: Concrete
(PSI)
Location: Station 17+30
4,130
4,130 JR
Maximum
Spec Age Tested
Diameter
Area
Load
Cure
Nbr (date : days)
(in)
(inz)
(lbs) Break Type
Loc
A 01/09/16: 3
6.00
28.27
116,815 Type 3
Lab
B 01/13/16:7
6.00
28.27
Lab
C 02/03/16:28
6.00
28.27
Lab
D 02/03/16:28
6.00
28.27
Lab
E
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 16 of 17
Number of Specimens: 5
Compressive
Average
Strength
Strength Tested
(PSI)
(PSI) By Comments
4,130
4,130 JR
Type 1 Type 2 Type 3 Type 4
Type 5 Type 6
HOLD (see remarks) -
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3 Slump: 1.0 Inches Transported By: Tiseo
Air Content: 3-5 Air Content: 4.1 % Source/Sampled At: Truck / Center
Mix Code: Class P Plant: On -Site
Date Received: 01/07/2016 Truck/Ticket No: N/A/ 150
Curing Method: Standard
Time Sampled: 4:00 pm
Time Batched: 4:09 pm
Temp : Ambient: 48°F Mix: 58°F
Unit Weight: 149.6 #/cu ft
Quantity Represented: 10 cu yds at 1500 cu. yds. placed of a 1600 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
C1064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617.
Orifi City of Coppell (Coppell, TX) Attn: Mr Rick O'Dell (1 -cc copy)
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, SET, CME Department Manager
11 -IIS REPORT APPLIES ONLY TO THE. STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED THESE REPORrS ARE FOR 11 IE.. EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION.
ALuOnce
(� G 0Eorechn109L
GROUP
Consulting Engineering " Geotechnical Engineering " Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444-8889 Fax: (972) 444-8893
Acct ID: 1770 File No: C15-0812
Report Date: 01/11/2016
Project: Freeport Parkway North
Location: Southbound outside lane Freeport Parkway
Client: City of Coppell
REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST
Set: 17 of 17
Location: Station 16+55
Spec
Nbr
A
B
C
D
E
TEST RESULTS
Material: Concrete
Type 1
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3
Air Content: 3-5
I
Type 2 Type 3 Type 4 Type 5
Slump: 2.0 Inches
Air Content: 5.0%
Mix Code: Class P
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 17 of 17
Number of Specimens: 5
Average
Strength Tested
(PSI) By Comments
3,290 JR
HOLD (see remarks) -
Type 6
Transported By: Tiseo
Source/Sampled At: Truck / Center
Plant: On -Site:
Date Received: 01/07/2016 TrucklTicket No: NIAI 160
Curing Method: Standard
Time Sampled: 4:35 pm
Time Batched: 4:29 pm
Temp.: Ambient: 49°F Mix: 59°F
Unit Weight: 144.4 #/cu ft
Quantity Represented: 10 cu. yds. at 1600 cu. yds. placed of a 1600 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
C1064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617.
Orig: City of Coppell (Coppell, TX) Attn: Mr Rick O'Dell (1 -CC copy)
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, SET, CME Department Manager
THIS REPORT APPLIES ONLY TO T HE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
I HE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NO I ED THESE REPORTS AIRE F OR TO--. FXCI USIVE USE OF TI IE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION
Maximum
Compressive
Age Tested
Diameter
Area
Load
Cure
Strength
(date : days)
(in)
(in')
(Ibs)
Break Type Loc
(PSI)
01/09/16: 3
6.00
28.27
93,125
Type 3 Lab
3,290
01/13/16:7
6.00
28.27
Lab
02/03/16:28
6.00
28.27
Lab
02/03/16:28
6.00
28.27
Lab
Type 1
Specification
Strength: 3,600 psi @ 28 days
Slump: 1-3
Air Content: 3-5
I
Type 2 Type 3 Type 4 Type 5
Slump: 2.0 Inches
Air Content: 5.0%
Mix Code: Class P
Date Sampled: 01/06/2016
Sampled By: Corbin, Rodney
By Order Of: Walter
Order Number: 1770
LAB NO: 200468
Test Method: See Below
Report No: 200468
Page 17 of 17
Number of Specimens: 5
Average
Strength Tested
(PSI) By Comments
3,290 JR
HOLD (see remarks) -
Type 6
Transported By: Tiseo
Source/Sampled At: Truck / Center
Plant: On -Site:
Date Received: 01/07/2016 TrucklTicket No: NIAI 160
Curing Method: Standard
Time Sampled: 4:35 pm
Time Batched: 4:29 pm
Temp.: Ambient: 49°F Mix: 59°F
Unit Weight: 144.4 #/cu ft
Quantity Represented: 10 cu. yds. at 1600 cu. yds. placed of a 1600 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted in remarks, concrete was sampled and tested in accordance with ASTM C31, C172, C143,
C1064 and C138. Compressive strength test per ASTM C39. Air Content was per ASTM C231 and
cylinders were not capped per ASTM C617.
Orig: City of Coppell (Coppell, TX) Attn: Mr Rick O'Dell (1 -CC copy)
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, SET, CME Department Manager
THIS REPORT APPLIES ONLY TO T HE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
I HE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NO I ED THESE REPORTS AIRE F OR TO--. FXCI USIVE USE OF TI IE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION