Loading...
Hammond- LR150803 (2) 8908 Ambassador Row,Dallas, 75247 Rone Engineering Texas Engineering Firm Registration,No.o.F-1572-1572 Corporate Phone:(214)630-9745 Report of In-Place Density Testing Client: JRose Architects Report No.: 14134078 230 Lake Drive Project No.: 1519926 Mount Vernon, TX 75457 Date of Service: 07/31/2015 Report Date: 08/03/2015 Project: Hammond Street Residential Development Coppell, Texas Services: Perform In-Place Density Testing PROJECT DATA Contractor: Standard Counts Test Method:ASTM D-6938 Gauge: Troxler 3430 Moisture Density Gauge Serial No: 38369 Current: 678 Current: 2196 Test Mode: DT Previous: 669 Previous: 2185 MOISTURE DENSITY RELATIONS Maximum Moisture Density Project Requirements M/D No. Description % (pcf) Moisture Density 14127134 Reddish Brown/Silty, Clayey Sand 12.0 117.5 -2/+2 95 min FIELD DENSITY TESTS Test Probe M/D Moisture Wet Density Dry Density Density No Test Location Depth No. % (pcf) (pcf) (%max) Select fill 1 Lot 15, final 6" 14127134 11.5 125.0 112.1 95 Select fill 2 Lot 14, final 6" 14127134 12.9 128.5 113.8 97 Technician: Lanny Gist Rone Engineering See Report 14133810 for technician time Report Distribution: fr f { Orig:JRose Architects(Mount Vernon,TX)Attn:Ms.Barb Rose (1-ec copy) 1-ec Rone Engineering Project Managers Attn:Mr.Josh Oliver Josh Oliver,EIT 1-ec JRose Architects Attn:Mr.Jason Rose Project Manager LIMITATIONS:The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition,appearance,etc.)or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services,Ltd. (TM/JO) Page 1 of 1