Fellowship-LR 990408 (2)IN-PLACE DENSITY 2 _;STING
ENGINEERING, INC.
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
Date of Service: 03/24/1999 Report No.: 9908606 Report Date
04/08/1999
Client No.: 47677000 Project No.: 94991026
Client: Julian P. Barry General Contractors Project: Fellowship of Las Colinas
Attn: Harold Luedke Phase III - Expansion
6616 Forest Park Road
Dallas TX 75235 Coppell, Texas
Services:
PROJECT DATA
CONTRACTOR: Julian P. Barry Laboratory Test Method: ASTM D-698
Field Test Method: ASTM D-2922
ASTM D-2922
MOISTURE DENSITY RELATIONS:
Maximum Project Requirements
M/D No. Description Moisture % Density pcf Moisture Density
1 Dk bm silty cl (lime treated) 29.5 89.0 -1/+3% 95%
FIELD DENSITY TESTS
TEST M/l) MOISTURE DRY DENSITY DENSITY
NO TEST LOCATION No. (%) (pcf) (% max)
Parking Area & Fire lane
73 Parking, Grid 275W/720S, Final lift 1 29.6 88.3 99
74 Parking, Grid 290W/780S, Final lift 1 30.3 87.5 98
75 Parking, Grid 290W/850S, Final lift 1 29.8 88.1 99
76 Fire lane, Grid 350W/875S, Final lift 1 29.7 86.8 98
77 Fire lane, Grid 650W/720S, Final lift 1 30.7 87.5 98
78 Parking, Grid 550W/700S, Final lift 1 31.0 88.3 99
79 Parking, Grid 550W/650S, Final lift 1 30.2 84.9 95
80 Parking, Grid 425W/675S, Final lift I 30.7 85.1 96
81 Fire lane, Grid 550W/400S, Final lift I 32.0 85.7 96
82 Fire lane, Grid 325W/550S, Final lift 1 29.5 87.2 98
83 Fire lane, Grid 100W/675S, Final lift 1 29.8 88.1 99
84 Fire lane, Grid 150N/25W, Final lift 1 29.3 87.8 99
85 Fire lane, Grid 450N/25W, Final lift 1 30.1 85.6 96
This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of HBC Engineering, Inc.
07TMI' Pa,~e 1 of 2
Report No.: 9908606
Test results on this report meet project specification.
Technician: Roy Montgomery ~Enginee '~[r g' Inc.
Report Distribution:
(1) Julian P. Barry General Contractors
(1) Urban Architecture Eug
( 1 ) City of Grapevine Vice President
(1) City of Coppell
This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of HBC Engineering, lnc.
0TFMP Page 2 of 2