ST0502A- LR160310ALLIANCE
G GEOTECHNICAL
_CfiWP
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444-8889 Fax: (972) 444-8893
Acct ID:
1770
File No: C15-0812 Date Sampled: 03/07/2016
Report Date:
03/10/2016
Sampled By:
Avila, Eli
Project:
Freeport Parkway North
By Order Of:
Walter
Location:
Retaining wall
Moisture
Order Number:
1770
Client:
City of Coppell
Percent
Test
REPORT:
Nuclear Field Density Test
Density
LAB NO:
205359
Proctor
Spec.
Moisture
Test Method:
See Below
No.
Depth
Location
TEST RESULTS Report No:
205359
(Pcf)
Number
No.
Page 1 of 1
Density
Fail
Optimum
Maximum
Walls 2 and 3 at Sta. 0+36
131.7
13.5
Proctor Moisture
Dry Density
1
+0.6
Proctor No
Date (%)
(Pcfl
Color / Description
Walls 2 and 3 at Sta. 0+72
191363-1
08/12/2015 12.9
117.2
Red Clayey sand with trace organics
1
Specification
Moisture Band
Specification No. Compaction. % Minimum Maximum
1 95 0.0
Location:
Wet
Moisture
Dry
Percent
Test
Lift # /
Density
Content
Density
Proctor
Spec.
Moisture
Proctor
Pass
No.
Depth
Location
(Pcfl
%
(Pcf)
Number
No.
Deviation
Density
Fail
1
1 st
Walls 2 and 3 at Sta. 0+36
131.7
13.5
116.0
191363-1
1
+0.6
99.0
Pass
2
1 st
Walls 2 and 3 at Sta. 0+72
131.5
13.0
116.4
191363-1
1
+0.1
99.3
Pass
3
1 st
Wall 7 at Sta. 0+108
131.2
13.3
115.8
191363-1
1
+0.4
98.8
Pass
4
1st
Wall 8 at Sta. 1+36
132.6
13.6
116.7
191363-1
1
+0.7
99.6
Pass
5
1st
Wall 9 at Sta. 2+20
131.6
14.1
115.3
191363-1
1
+1.2
98.4
Pass
6
1 st
Wall 9 at Sta. 2+64
131.6
14.5
114.9
191363-1
1
+1.6
98.0
Pass
Gauge No.: 69505 Daily Standard Counts: 03/07/2016 DS: 2449 MS: 630
Test Methods: ASTM D6938-10
CONFORMS
Orig: City of Coppell (Coppell, TX) Attn: Mr. Rick O'Dell (1 -cc copy)
Respectfully Submitted,
Alliance Geotechnical Group
/,4 c�
Perry C. Kakara, SET, CME Department Manager
THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENTAND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION