Duke Freeport- LR160513May 13, 2016
Duke Realty
South/West Region
14241 North Dallas Parkway, Suite 1000
ATTN:Mr. Sean Jeanes, P.E. LEED AP
Tohatsu
Location:
Permits:
Dallas, TX 75254
19:6710-A
NEC Bethel Road and Freeport Parkway
Coppell, TX
RE:
ECS Job #
3033 Kellway Drive, Suite 110
Carrollton, TX 75006
(972) 392-3222 [Phone]
(214) 483-9684 [Fax]
ECS Texas, LLP
LETTER OF TRANSMITTAL
Texas Registered Engineering Firm # F-8461
CC:Duke Realty - Todd Henry
Duke Realty - Glen Stevenson
Pacheco Koch Consulting Engineers - Clayton J. Strolle, LEED AP
City of Coppell - Matt Mabry
Weir Bros., Inc. - Mike Weir
ENCL:
We are enclosing:
Materials Engineering Division Reports
For your use
As requested
X
X
X
Field Report # 40 05/11/2016 Utility BF, Footing
Timothy TarbuttonMark R. Zortman, P.E.
Principal Engineer Project ManagerMAY 13 2016
1000.1
This report (and any included attachments) shall not be reproduced, except in full, without the prior written approval of ECS.
ECS Texas, LLP
19:6710-A
40
Tohatsu Wednesday 05/11/2016
Project No.
Report No.
Day & DateProject
3033 Kellway Drive, Suite 110
Carrollton, TX 75006
(972) 392-3222 [Phone]
(214) 483-9684 [Fax]
FIELD REPORT
3.50
The undersigned arrived on site, as requested, to observe:
1. The placement and compaction of soils for Sanitary Sewer Line SS-1B backfill.
Utilizing the nuclear test method to check the compaction of soils; test results indicated that the
compacted material, at the areas and elevations tested, met or exceeded the project
requirements of 95% of the maximum dry density as obtained in our laboratory using the
ASTM D 698-12 Method A Standard.
Locations and elevations of all tests are based on stakeout provided by others. We cannot be
responsible for structures located off of the observed engineered pad, misaligned utilities or
stakeout errors causing uncontrolled fill to be placed in structural areas.
2. The bearing capacity of soil of Footings B-2.
Utilizing a Dynamic Cone Penetrometer (ASTM STP-399) to check the bearing capacity of soil
at the aforementioned locations, test results indicated that soils, at the areas and elevations
tested, should be capable of supporting a foundation designed for a net allowable bearing
capacity 3000 psf.
Footing B-2 was excavated on 5/10/16. DCP testing was done 5/11/16 but concrete was not
placed. Retesting will be required.
88°/ Sunny
55.00
2.00
0.50
0.00
01:00P 03:00P
Utility BF, Footing
Location
Contractor
On-Site Time
Lab Time
Client
Coppell, TX
Arrival Departure
Summary of Services Performed (field test data, locations, elevations & depths are estimates) & Individuals Contacted.
Duke Realty - Sean Jeanes, P.E. LEED AP
Duke Realty - Sean Jeanes, P.E. LEED AP
Trip Charges*
Remarks
Chargeable Items
Weather
Mileage*
1.00Travel Time*
Total
Time of
Re Obs.Time
* Travel time and mileage will be billed in accordance with the contract.
Tolls/Parking*
Milton E. Perez, — Field TechnicianBy 1705
1080396
Report of Spread Footing - Foundation Observations
Project:
Location:
Contractor:
Project No.
Day/Date:
LocationFooting
Number
Size (W x H x L)
Design Actual
Footing Bottom Elevation
Depth of
Undercut (in)
Description of
Steel Placed
Description of
Subgrade
Material
# of Blows / increment
Design
Bearing
Pressure
Design
Required Blow Counts
Tohatsu 6710-A
NEC Bethel Road and Freeport Parkway
Coppell - Dallas County - TX - 75019-
Duke Realty
05/11/16
7' x 2'6" x 7'B2 7' x 2'6" x 7'97.5 2.5 .1 8 #5 CLAYEY Sand 5
8.0 3000
ECS Texas, LLP
By:Milton E. Perez
WO:61928
ECS TEXAS, LLP
Test Method ASTM Nuclear
Project No:
Contractor:
Project Name:Date:
Client:
Page 1
Technician:
Nuclear Gauge No.
Make
Model
Ser. No.
Density Std
Moisture Std
6710-A Tohatsu 05/11/16
Duke Realty
Duke Realty
Milton E. Perez
66373
Troxler
3430
3430
2023
644
Field Compaction Summary, ASTM Nuclear
Description Proctor Method Uncorrected Max. Density Uncorrected Opt. MCSample No.
D4S-5 Clayey SAND, Light Brown ASTM D 698-12 Method A Standard 116.70 11.40
Test Data
Test
No.
Test
Mode
Station /
Location
Probe
Depth
(in.)
Lift /
Elev
Corrected
Maximum
Dry
Density
(pcf)
Corrected
Optimum
Moisture
Content
(%)
%
Oversize
Wet
Density
(pcf)
Dry
Density
(pcf)
Moisture
Content
(%)
Percent
Comp.
(%)CommentsP / F
Sample No.
1 DT 6 Sanitary Sewer, SS-1B, STA 1+50 SG-3'6
"
0.00 116.70 11.40 131.0 111.3 17.6 95.4 PD4S-5
2 DT 6 Sanitary Sewer, SS-1B, STA 1+50 SG-3'0.00 116.70 11.40 131.4 111.1 18.2 95.2 PD4S-5
3 DT 6 Sanitary Sewer, SS-1B, STA 1+50 SG-2'6
"
0.00 116.70 11.40 130.6 111.1 17.5 95.2 PD4S-5
4 DT 6 Sanitary Sewer, SS-1B, STA 1+50 SG-2'0.00 116.70 11.40 130.9 111.0 18.0 95.1 PD4S-5
5 DT 6 Sanitary Sewer, SS-1B, STA 1+50 SG-1'6
"
0.00 116.70 11.40 134.0 114.0 17.6 97.7 PD4S-5
6 DT 6 Sanitary Sewer, SS-1B, STA 1+50 SG-1'0.00 116.70 11.40 129.3 111.3 16.1 95.4 PD4S-5
7 DT 6 Sanitary Sewer, SS-1B, STA 1+50 SG-6"0.00 116.70 11.40 134.2 115.8 15.9 99.2 PD4S-5
8 DT 6 Sanitary Sewer, SS-1B, STA 1+50 SG 0.00 116.70 11.40 132.5 113.4 16.9 97.2 PD4S-5
9 DT 6 Sanitary Sewer, SS-1B, STA 2+50 SG-3'6
"
0.00 116.70 11.40 131.4 111.0 18.3 95.1 PD4S-5
10 DT 6 Sanitary Sewer, SS-1B, STA 2+50 SG-3'0.00 116.70 11.40 131.5 111.2 18.2 95.3 PD4S-5
11 DT 6 Sanitary Sewer, SS-1B, STA 2+50 SG-2'6
"
0.00 116.70 11.40 130.6 111.9 16.7 95.9 PD4S-5
12 DT 6 Sanitary Sewer, SS-1B, STA 2+50 SG-2'0.00 116.70 11.40 130.4 111.2 17.2 95.3 PD4S-5
Test Mode: DT = Direct Transmission BS = Back Scatter WO:61928
ECS TEXAS, LLP
Test Method ASTM Nuclear
Project No:
Contractor:
Project Name:Date:
Client:
Page 2
Technician:
Nuclear Gauge No.
Make
Model
Ser. No.
Density Std
Moisture Std
6710-A Tohatsu 05/11/16
Duke Realty
Duke Realty
Milton E. Perez
66373
Troxler
3430
3430
2023
644
Field Compaction Summary, ASTM Nuclear
Test Data
Test
No.
Test
Mode
Station /
Location
Probe
Depth
(in.)
Lift /
Elev
Corrected
Maximum
Dry
Density
(pcf)
Corrected
Optimum
Moisture
Content
(%)
%
Oversize
Wet
Density
(pcf)
Dry
Density
(pcf)
Moisture
Content
(%)
Percent
Comp.
(%)
P / F
Sample No.
Comments
13 DT 6 Sanitary Sewer, SS-1B, STA 2+50 SG-1'6
"
0.00 116.70 11.40 133.7 114.5 16.7 98.1 PD4S-5
14 DT 6 Sanitary Sewer, SS-1B, STA 2+50 SG-1'0.00 116.70 11.40 130.9 112.5 16.3 96.4 PD4S-5
15 DT 6 Sanitary Sewer, SS-1B, STA 2+50 SG-6"0.00 116.70 11.40 134.0 114.6 16.9 98.2 PD4S-5
16 DT 6 Sanitary Sewer, SS-1B, STA 2+50 SG 0.00 116.70 11.40 131.7 112.7 16.8 96.6 PD4S-5
Test Mode: DT = Direct Transmission BS = Back Scatter WO:61928