Park West Crossing-LR160719 (5)FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
94151183.0173
07/19/16
07/27/16
8901 Carpenter Fwy Ste 100
Dallas, TX 75247-4547
214-630-1010 Reg No: F-3272
Client Project
ML Realty Partners
Attn: Timothy Geisler
One Pierce Pl Ste 450W
Itasca, IL 60143
Park West Crossing - Phase 2
SEC Freeport Pkwy & Southwestern Blvd
Coppell, TX
Project Number:94151183
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description (pcf)Test Method
92-98>/= +4196.326.094151183.0013 Grayish tan shaley clay ASTM D698
95-2/+2286.830.294151183.0007 Dark and light brown clay (lime
treated)
ASTM D698
Field Test Data
No.Test Location Elev.No.
Test Lift /Mat.Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in)(pcf)(pcf)(pcf)
Building G, Utility Line Bacfill
888 E.8/6.7 4' BFG 1 6 119.1 29.4 32.8 89.7 93
889 E.8/6.7 3' BFG 1 6 118.9 29.0 32.3 89.9 93
890 E.8/9.9 2' BFG 1 6 117.1 28.2 31.7 88.9 92
891 E.8/9.9 1' BFG 1 6 118.6 28.0 30.9 90.6 94
892 E.8/9.9 Final 2 6 113.7 25.6 29.1 88.1 100+
Comments:
Datum:BFG = Below final grade Serial No:27952
Test and/or retest results on this report meet project requirements as noted above.
Perform in-place density and moisture content tests to determine degree of compaction and material moisture
condition.
Services:
Reported To:
Contractor:
Damon
Structure Tone Southwest
James D. Baze
Project Manager
Report Distribution:
(1) ML Realty Partners, Timothy Geisler (1) City of Coppell TX, Matthew Mabry
(1) Halff Associates Inc, Hunter Starkey (1) ML Realty Partners, John Benson
(1) O?Brien Architects , Richard Nordyke (1) Structure Tone Southwest Inc., Damon Renaud
(1) Structure Tone Southwest Inc., Robin Povey (1) TechniStructures, Jason Owens
Reviewed By:
Terracon Rep.: Abe Alvares
ASTM D6938Test Methods:
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1