Duke Freeport-LR160831 (3)Texas Registered Engineering Firm # F-8461
August 31, 2016
Duke Realty
South/West Region
14241 North Dallas Parkway, Suite 1000
ATTN:Mr. Sean Jeanes, P.E. LEED AP
Tohatsu
Location:
Permits:
Dallas, TX 75254
19:6710-A
NEC Bethel Road and Freeport Parkway
Coppell, TX
RE:
ECS Job #
3033 Kellway Drive, Suite 110
Carrollton, TX 75006
(972) 392-3222 [Phone]
(214) 483-9684 [Fax]
ECS Texas, LLP
LETTER OF TRANSMITTAL
CC:Duke Realty - Todd Henry
Duke Realty - Glen Stevenson
Pacheco Koch Consulting Engineers - Clayton J. Strolle, LEED AP
City of Coppell - Matt Mabry
Weir Bros., Inc. - Mike Weir
Meinhardt & Associates - David Meinhardt
LJB inc - Jim Lintz
ENCL:
We are enclosing:
Materials Engineering Division Reports
For your use
As requested
X
X
X
Field Report # 104 08/27/2016 Compaction, Concrete
Timothy TarbuttonMark R. Zortman, P.E.
Principal Engineer Project ManagerAUG 31 2016
1000.1
This report (and any included attachments) shall not be reproduced, except in full, without the prior written approval of ECS.
Texas Registered Engineering Firm # F-8461
ECS Texas, LLP
19:6710-A
104
Tohatsu Saturday 08/27/2016
Project No.
Report No.
Day & DateProject
3033 Kellway Drive, Suite 110
Carrollton, TX 75006
(972) 392-3222 [Phone]
(214) 483-9684 [Fax]
FIELD REPORT
7.75
The undersigned arrived on site, as requested, to observe:
1: The compaction of soils for Sidewalk and Transformer Pad.
Utilizing the nuclear test method to check the compaction of soils; test results indicated that the
compacted material, at the areas and elevations tested, met or exceeded the project
requirements of 95% of the maximum dry density and moisture content above OMC as
obtained in our laboratory using the ASTM D 698-12 Method A Standard.
Locations and elevations of all tests are based on stakeout provided by others. We cannot be
responsible for structures located off of the observed engineered pad, misaligned utilities or
stakeout errors causing uncontrolled fill to be placed in structural areas.
2: The placement of 123 cubic yards of 3600 psi concrete for Pavement.
3: The placement of 19 cubic yards of 3000 psi concrete for Sidewalk.
The required test limits were determined to be a slump of 3-5 inches, air content of 3-6 %,
batch to placement time of 90 minutes, and concrete temperature range of 50-95 degrees
Fahrenheit.
Concrete observed on this date appeared to be placed in compliance with project specifications
with regard to temperature, slump, air content, and batch to placement time.
Two sets of five laboratory cured concrete cylinders were cast for compressive strength testing
in our laboratory.
89°/ Sunny
55.00
6.25
0.50
0.00
07:45A 02:00P
Compaction, Concrete
Location
Contractor
On-Site Time
Lab Time
Client
Coppell, TX
Arrival Departure
Summary of Services Performed (field test data, locations, elevations & depths are estimates) & Individuals Contacted.
Duke Realty - Sean Jeanes, P.E. LEED AP
Duke Realty - Sean Jeanes, P.E. LEED AP
Trip Charges*
Remarks
Chargeable Items
Weather
Mileage*
1.00Travel Time*
Total
Time of
Re Obs.Time
* Travel time and mileage will be billed in accordance with the contract.
Tolls/Parking*
Edward SesayBy 1800
1092303
ECS TEXAS, LLP
Test Method ASTM Nuclear
Project No:
Contractor:
Project Name:Date:
Client:
Page 1
Technician:
Nuclear Gauge No.
Make
Model
Ser. No.
Density Std
Moisture Std
6710-A Tohatsu 08/27/16
Duke Realty
Duke Realty
Edward Sesay
3529
Troxler
3430
2800
424
Field Compaction Summary, ASTM Nuclear
Texas Registered Engineering Firm # F-8461
Description Proctor Method Uncorrected Max. Density Uncorrected Opt. MCSample No.
D4S-1 Fat CLAY with Sand, Dark Brown ASTM D 698-12 Method A Standard 103.90 18.90
D4S-6 Sandy Fat CLAY, Light Gray ASTM D 698-12 Method A Standard 105.70 18.10
D4S-8 Fat CLAY With Sand, Dark Brown ASTM D 698-12 Method A Standard 95.10 22.80
Test Data
Test
No.
Test
Mode
Station /
Location
Probe
Depth
(in.)
Lift /
Elev
Corrected
Maximum
Dry
Density
(pcf)
Corrected
Optimum
Moisture
Content
(%)
%
Oversize
Wet
Density
(pcf)
Dry
Density
(pcf)
Moisture
Content
(%)
Percent
Comp.
(%)CommentsP / F
Sample No.
1 DT 8 Sidewalk 0.00 95.10 22.80 114.5 91.3 25.4 96.0 PD4S-8
2 DT 8 Sidewalk 0.00 105.70 18.10 128.0 104.2 22.9 98.6 PD4S-6
3 DT 8 Sidewalk 0.00 95.10 22.80 114.9 92.9 23.7 97.7 PD4S-8
4 DT 8 Transformer Pad 0.00 103.90 18.90 119.6 98.7 21.1 95.0 PD4S-1
Test Mode: DT = Direct Transmission BS = Back Scatter WO:65521
Texas Registered Engineering Firm # F-8461
Concrete Summary Report
Project:
Location:
Contractor :
Supplier:
Project No.
Day/Date:
Client:
Weather / Temp:
Page 1
No.Ticket
No.
Truck
No.
CY Concrete
Truck Cum
Batch
Time
Truck Time
Arrive Finish Slump % Air Concrete
Temp.
Water
Added Location and Remarks
Tohatsu 6710-A
NEC Bethel Road and Freeport Parkway
Coppell, - Dallas County - TX 75019-
08/27/2016
Duke Realty
Sunny / 89
Duke Realty
LMC
Mix Designation:Multiple (see remarks)Mix Strength:Multiple (see remarks)Design Strength:3600 psi
B to P
min.
1 3032 76830374 9.5 9.5 08:23 08:48 09:00 37
2 0808 63001937 9.5 19.0 08:35 08:54 09:06 31
3 5015 76830375 9.5 28.5 08:32 09:03 09:14 *5.00 3.20(P)80 Mix. Des.: 5409 Mix Str.: 3600 psi42
4 1408 64414182 9.5 38.0 08:38 09:09 09:24 46
5 5030 76830376 9.5 47.5 08:39 09:20 09:32 53
6 0802 63001939 9.5 57.0 09:00 09:44 09:54 54
7 1510 76830378 9.5 66.5 09:14 09:46 10:00 46
8 0810 63001942 9.5 76.0 09:17 09:57 10:08 51
9 9118 63001944 9.5 85.5 09:30 10:17 10:28 58
10 0806 63001945 9.5 95.0 09:44 10:21 10:32 48
11 1420 76830381 9.5 104.5 09:59 10:35 10:45 46
12 3032 76830382 9.5 114.0 10:10 10:57 11:08 58
13 3035 76830385 9.5 123.5 11:46 12:15 12:34 *5.00 3.10(P)85 Mix. Des.: 5177 Mix Str.: 3000 psi48
* Location:By:Edward SesaySidewalk and Pavement
ECS Texas, LLP
WO:65521
* B to P - Batch to Placement time in minutes