Sonic-LR160909Concrete Compression Test
Report
2209 Wisconsin St.
Dallas, TX 75229
(972)620-8911
Alpha Testing, Inc.
TBPE Firm No. 813
FIELD DATA
Placement Location:NORTHEAST CORNER OF APPROACH
Project Desc:SONIC RESTAURANT
201 NORTH DENTON TAP ROAD
Our Report #:161578-17
MIRA ENTERPRISES
9500 IH 20
EASTLAND, TX 76448
MIKE BATTEASATTN:
(254) 629-0978Fax Number:
Date Placed:8/12/2016
Time Placed:N/A
N/A
N/A
N/A
N/A
Date Received:8/13/2016
Concrete Supplier:N/A
Submitted By:CONTRACTOR
Plant Number:B1
Delivery Ticket No.:N/A
N/A
Batch Time:N/A
Tested For:
Lab
No.:
Cure
Type:
Date
Tested:
Age
(Days):
Max
Load:
Area:
Sq. In.PSI:
Cap
Spec:
CYLINDER COMPRESSION TEST RESULTS
Avg.
Length
Avg.
Width
Avg Depth/
Diameter
Cast By:CONTRACTOR
Cured Specification:ASTM C-31
Mix ID:N/A
Break
Type:
Sample Location:N/A
PM:TODD SMITH
Date Issued:09/09/2016
Specified Strength:4000
Result
Air Content:
Ambient Temp (F):
Concrete Temp (F):
Unit Weight:
Slump (ASTM C-143):
29 8/19/2016 7 5009612.56 3990LABC-1231 8 N/A 42
30 9/9/2016 28 5853012.56 4660LABC-1231 8 N/A 42
31 9/9/2016 28 5842412.56 4650LABC-1231 8 N/A 42
32 9/9/2016 28 5985112.56 4770LABC-1231 8 N/A 42
Average 28-day Compressive Strength is compliant with project specifications
Notes:All information other than the test results was furnished by others and assumed to be correct.
Ashoke Saha picked up the cylinders.
CC:
4690
Respectfully Submitted By:__________________________________________________________ of Alpha Testing, Inc.
Geotechnical Engineering * Construction Materials Testing * Environmental Engineering * Consulting 247011
Break Types: 1: Cone 2: Cone and Split 3: Cone and Shear 4: Shear 5: Columnar * = Specification out of spec
Test Method: Unless noted, concrete was sampled and tested in accordance with ASTM C172, C143, C231, C173, C1064, C31, C1231 and C138. Compression strength tests per ASTM
C39.