Park West Crossing-LR160927
STRUCTURAL STEEL OBSERVATIONS REPORT
Report Number:94151183.0292
* Report Contains Deviation(s)
Service Date:09/27/168901 Carpenter Fwy Ste 100
Report Date:09/29/16 Dallas, TX 75247-4547
214-630-1010 Reg No: F-3272
ClientProject
ML Realty PartnersPark West Crossing - Phase 2
Attn: Timothy GeislerSEC Freeport Pkwy & Southwestern Blvd
One Pierce Pl Ste 450WCoppell, TX
Itasca, IL 60143
Project Number: 94151183
On this date, Terracon's representative arrived at the above referenced job site as scheduled for structural steel observations. A visual
observation was performed as noted below.
A.Building E, Foundation Level, Tilt Wall Panel To Pier. Re-observation Item From Report 94151183.0289:
1.Tilt wall panel to pier cap welded connections were now determined to be compliant. Yet the north
wall leaveout panel still not set.
B.Building E, Roof Level Framing @ E-K/1-4:
*1.Column anchor bolts, two (2) locations were found to have missing nuts.
2.Joist and girder seat welds were determined to be compliant.
*3.Joist bridging not complete at the end wall attachments.
*4.Joist seat support lug weldments at the tilt wall panel embed plates were determined to be compliant.
Yet two (2) locations, the slip bolted stud panel joint connections were found to be incomplete.
C.Building F, Foundation Level, Tilt Wall Panel To Pier:
*1.Tilt wall panel to pier cap welded connection were determined to be compliant, with the following
two (2) exceptions
*a.South wall, one (1) location not welded.
*b.East wall, leaveout panel not set.
*Noted discrepancies and/or incomplete work.
Services: Structural steel observations.
Terracon Rep.: Randy T. Walcker, C.W.I.
Reported To:
Contractor:Structure Tone Southwest
Report Distribution:
(1) ML Realty Partners, Timothy Geisler(1) City of Coppell TX, Matthew Mabry
(1) Halff Associates Inc, Hunter Starkey(1) ML Realty Partners, John Benson
Reviewed By:____________________________________
(1) O?Brien Architects , Richard Nordyke(1) Structure Tone Southwest Inc., Damon
James D. Baze
Renaud
(1) Structure Tone Southwest Inc., Robin (1) TechniStructures, Jason Owens
Project Manager
Povey
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to
the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.