Forest Cove 2-LR 980304ALPHA TESTINCNC.
2209 Wisconsin St., Suite 100
Dallas, Texas 75229
(972) 620-8911
REPOi-1T OF FIELD
COMPACTION TESTS
/
TESTED FOR PACIFIC UNITED/DEV. CORP. DATE
C/O ROBERT POPs & ASSOC.
PLANO, TEXAS
FOREST COVE ESTATES
PHASE 1 & 2
PROJECT COPPELL, TEXAS OUR REPORT NO.
03/04/98
98018-25
TEST DATA:
TEST DA~ ~ ~OIL ID OPTIMUM MAX~UM LAB IN PLACE IN PLA~ PERCE~ COMMENT*
~IS~RE Dm ~NS~ ~IS~RE DRY DENS~ COMPACTION
NO. flUMBER % ~F % ~:~
253 03/04 t~3-2.0 3 13.6 113,6 14.9 108 95 1-A
254 03/04 [:~.3-1.0 3 13.6 113,6 14.2 108 95 1-A
255 03/04 FG-2.0 2 18.5 105.6 19.3 101 96 1-A
256 03/04 FG-1.0 i 2 18.5 105.6 18.8 104 98 1-A
257 03/04 FG-2.0 i 2 18.5 105.6 18.6 103 98 1-A
258 03/04 FG-1.0 i 2 18.5 105.6 19.5 102 97 1-A
259 03/04 FG-2.0 i 2 18.5 105.6 20~0 104 99 1-A
TEST LOCATtON: NO STATION FOR WATER LINES
I
253 8" WATER LINE ADJACE1TI' TO BLOCK "A" LOT #2
254 8" WATER LINE ADJACENw TO BLOCK "A" LOT #2
255 8" WATER LINE ADJACEITr TO BLOCK "A" LOT #5
256 8" WATER LINE ADJACENT TO BLOCK "A" LOT #5
I
257 8" WATER LINE ADJACENT TO BLOCK "A" LOT #6 S.E. CORNER
I
258 8" WATER LINE ADJACENT TO BLOCK "A" LOT #6 S.E. CORNER
1
I
259 8" WATER LINE ADJACENT TO BLOCK "C" LOT #1 ACROSS STREET
i
1. FILL
2. NATURAL SUBGRADE
3. LIME STABILIZED
4. CEMENT TREATED
CG01083-18
* A. IN PLACE PERCENT MOISTURE AND PERCENT COMPACTION COMPLY WITH SPECIFICATIONS ~
B. PERCENT COMPACTION DOES NOT COMPLY WITH SPECIFICATIONS / Respectfully S~bmitted ....
TEST "C ,. MO,STU. NOT OO P'Y W,T. ONS /
ALPHA TESTIN~'~ 'NC.
2209 Wisconsin St., Suite 100
Dallas, Texas 75229!
(972) 620-8911
REPOrlT OF FIELD
COMPACTION TESTS
TESTED FOR PACIFIC UNITED DEV. CORP.
C/O ROBERT POP~ & ASSOC.
PI.d~O, TEXAS
FOREST COVE ESTATES
PHASE 1 & 2
PROJECT
COPPELL, TEXAS
DATE
03/04/98
OUR REPORT NO.
98018-25A
TEST DATA:
TEST DATE '"'"-...~LEV. .~OIL ID OPTIMUM MAXIMUM LAB IN PLACE IN PLACE PERCENT
MOISTURE DRY DENSITY MOISTURE DRY DENSITY COMPACI'ION COMMENT*
NO. DEPTH ~ I~lUMBER % PCF % PCF
260 03/04 FG-1.0 2 18 . 5 105.6 18 . 9 102 96 1-A
261 03/04 FG-2.0 2 18.5 105.6 19.9 102 97 1-A
262 03/04 FG-1.0 2 18.5 105.6 20.1 103 98 1-A
I
263 03/04 FG-2.0 ! 2 18.5 105.6 18.6 103 97 1-A
264 03/04 FG-1.0 2 18.5 105 . 6 19.0 104 99 1-A
I
I
TEST LOCATION:
260 8" WATER LINE ADJACENT TO BLOCK "C" LOT #1 ACROSS STREET
261 8" WATER LINE ADJACENT TO BLOCK "D" LOT #8
262 8" WATER LINE ADJACENT TO BLOCK "D" LOT #8
263 8" WATER LII~ ADJACENT TO BLOCK "D" LOT #5
264 8" WATER LINE ADJACENT TO BLOCK "D" LOT #5
1. FILL * A. IN PLACE PERC '-NT MOISTURE AND PERCENT COMPACTION COMPLY WITH SPECIFICATIONS /~ ·
2. NATURAL SUBGRADE B. PERCENT COMF ACTION DOES NOT COMPLY WITH SPECIFICATIONS /Respectfully Subn~itted
3. LIME STABILIZED C. PERCENT IN PL ICE MOISTURE DOES NOT COMPLY WITH SPECIFICATIONS ........ ' / '
4. CEMENT TREATED D. RETEST // ALPHA TEST~'/~.~;II~.