Loading...
Duke Lesley 2RC -CS161107 (2) MEMORANDUM TO: Marcus Marion, Engineering FROM: David Sigman, Water Utilities DATE: November 7, 2016 REF: Sheraton - Water Punch List 1.The two domestic meters need to be adjusted; too close to lid. 2” meter should be 4” to 8” from lid. 2.Hydrant off Point West Blvd. needs to be painted yellow. 3.Four valves need extensions on them; too deep – should be 1’ from top of concrete. 4.Fire hydrant needs 2-1/2” nozzle fixed; cross threading.