Hackberry Addition-CS170106T H E C I T Y O F
COPPELL
14 U�K
January 6, 2017
Steven G. Dewald, P.E.
Lightowler Johnson Associates, Inc.
700 Main Avenue
Fargo, ND 58103
RE: Hackberry Addition
Blk A Lt 1(Springhill Suites)
Dear Mr. Dewald,
The City of Coppell has reviewed the referenced plans and has the following comments to offer:
General -
1) Provide all offsite easements by separate instrument at this time. Recorded at county. Provide
labels in plans with volume and page information.
Utility Plans -
2) By revising to a 12" water line you now need to provide a plan and profile with grades and
elevations for the 12" water. High points will need air release valves. Calls in plan should
match in profiles
3) Include size and thickness of any carrier/casing pipes for utility bores.
4) FDC connection runs from the fire riser room not directly from a FH. Relocate FH and FDC
to east side of drive isle.
Please make the necessary changes and submit these marked -up plans and two sets of revised
plans to the City for review. If you have any questions, please contact me at your convenience.
Sincerely,
George S. Marshal, P.E.
Engineering Manger
Office Phone: (972) 304-3562
gmarshall(icoppelltx. gov