Loading...
Red Hawk-CS170113 MEMORANDUM TO: Terry Holmes, The Holmes Builder FROM: Marcus Marion, Engineering DATE: January 13, 2017 REF: Red Hawk - Engineering Punch List 1. The public hydrant on the property needs to painted yellow. (Standard Detail 4120, note 9) 2. There needs to be a 6” – 8” lip on the vault because the vault wasn’t placed 8” above the ground. (Std. Det. 4160) 3. There needs to be a double check after the domestic meter. There needs to be copper pipe from the corporation stop to the tie-in of the double check. 4. Saw-cuts and expansion joints need to be sealed properly (Std. Det. 2050) 5. All cracks need to be cut and sealed 6. Clean storm drain This is a PRE-punch list. We have to give Streets, Water, and Sewer a 48-hour notice for their walk-thru. Their list may be more specific than my list because ours is a quick visual inspection. Our list needs to be complete prior to scheduling a Public Works walk-thru. If you have any questions, please let me know.