Fairfield Inn-LR170428CONCRETE COMPRESSIVE STRENGTH TEST REPORT Report Number: 94161112.0061 1rerracon Service Date: 04/28/17 Report Date: 05/04/17 8901 Carpenter Fwy Ste 100 Task: Dallas, TX 75247-4547 Client 214-630-1010 Re No: F-3272 Northpoint Construction Attn: Dilip Pranav 8530 Esters Blvd Irving, TX 75063 Project Fairfield Inn - Coppell TX Northpoint Dr at SH 121 Coppell, TX Project Number: 94161112 Material Information Sample Informatinn Specified Strength: 4,000 psi (it) 28 days Mix ID: 5632 Supplier: Charley's Batch Time: 1241 Plant: 127724 Truck No.: 703 Ticket No.: 422028 Field Test Data Test Slump (in): Air Content (%): Concrete Temp, (F): Ambient Temp. (F): Plastic Unit Wt, (pcf): Yield (Cu. Yds.): Laboratory Test Data Result _ Specification T 1/2 3-5 4.3 3-6 79 66 148.2 Sample Date: Sampled By: Weather Conditions: Accumulative Yards: Placement Method: Water Added Before (gal): Water Added After (gal): Sample Location: Placement Location: 04/28/17 Sample Time: 0141 Globe Engineers, Inc. Clear 10/350 Batch Size (cy): 10 Pump 0 5 Slump After (in): 3.5 Location #1 Pavement Fire Lane Driveway, & Parking Spaces @ E of building, see attached sketch Set Specimen Avg Diem. Area Date Date Age at Maximum Compressive No. ID —1 (in) (sq in) Received Tested Test (days) Load Strength Fracture I 4.00 12.57 —� `' OS/OI/17 3 _ (lbs 43,890 (psi) Type 1 3 4.00 12.57 05/05/17 7 3,490 1 1 4 4.00 12.57 05/26/17 28 1 5 4.00 12.57 05/26/17 28 1 6 4.00 12.57 05/26/I7 28 1 7 4.00 12.57 06/23/17 56 Comments: Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Terracon Rep.: Globe Engineers, Inc. Reported To: Contractor: Report Distribution: (1) Northpoint Construction, Di lip Pranav (1) Northpoint Construction. Jamie Ogden (l) Kencarkey Interests LLC, Jeremy Henicke Test Methods: ASTM C 31, ASTM C39, ASTM 0138, ASTM 0143, ASTM C172, ASTM 0231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CR0001, 11-16.12, Rev.6 Page] of 4 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Report Number: 94161112.0061 1rerracon Service Date; 04/28/17 Report Date: 05/04/17 8901 Carpenter Fwy Ste 100 Task: Dallas, TX 75247-4547 Client 214-630-1010 Re No: F-3272 Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Terracon Rep,: Globe Engineers, Inc. Reported To: Contractor: Report Distribution: (1) Northpoint Construction, Dilip Pranav (1) Northpoint Construction, Jamie Ogden (1) Kencarkey Interests LLC, Jeremy Ilenicke Test Methods: ASTM C 31, ASTM C39, ASTM 0138, ASTM C143, ASTM C 172 ASTM C231 A , , 5TM C 1064„ ASTM C 123 l The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CROON, i 1 -it: -12, Rev.6 Page 2 of 4 Project Northpoint Construction Attn: Dilip Pranav Fairfield Inn - Cappell TX 8530 Esters Blvd Northpoint Dr at SH 12I Irving, TX 75063 Coppell, TX Project Number: 94161112 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Sample Date; P 04/28J17 Sample Time: Mix ID• 5632 Sampled By: 0300 Globe Engineers, Inc. Supplier: iey's Weather Conditions: Clear Batch Time: 0146 0146 Plant: 127724 Accumulative Yards: 110/350 Batch Size (Y)• c 10 Truck No.: 704 Ticket Na.: 422{238 Placement Method: Water Added Before (gal): Pump 0 Field Test Data Water Added After (gal): 0 Test Result Specification Sample Location: Placement Location: Location #2 S Slump {in): 4 1/2 3-5 Pavement Fire Lane Driveway; & Air Content ("/o): 4.1 3-6 Parking Spaces @ E of building Concrete Temp. (F): $1 Ambient Temp. (F): 69 Plastic Unit Wt. (pef): 148.9 Yield (Cu. Yds.): Laboratory Test Data Set Specimen Avg Diam. Area Date Age at Maximum Compressive late No. ID 2 in (�) (sq in) Received Test Load Strength Fracture Tested (days) (lbs) 1 2 3 4.00 4.00 12.57 12.57 05/01/17 3 41! ,730 3(32p Type 4 2 4 2 4.00 12.57 05/05/17 7 05!26/17 28 5 2 6 4.00 12.57 05/26/17 28 2 7 4.00 4.00 12.57 12.57 05/26/17 28 06/23/17 56 Comments: Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Terracon Rep,: Globe Engineers, Inc. Reported To: Contractor: Report Distribution: (1) Northpoint Construction, Dilip Pranav (1) Northpoint Construction, Jamie Ogden (1) Kencarkey Interests LLC, Jeremy Ilenicke Test Methods: ASTM C 31, ASTM C39, ASTM 0138, ASTM C143, ASTM C 172 ASTM C231 A , , 5TM C 1064„ ASTM C 123 l The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CROON, i 1 -it: -12, Rev.6 Page 2 of 4 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Report Number: 94161112.0061 1rerracon Service Date: 04/28/17 Report Date: 05/04/17 8901 Carpenter Frey Ste 100 Task: Dallas, TX 752474547 Client 214-630-1010 Re No:F-3272 Northpoint Construction Attn: Dilip Pranav 8530 Esters Blvd Irving, TX 75063 Project Fairfield Inn - Coppell TX Northpoint Dr at SH 121 Coppell, TX Project Number: 94161112 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: 5632 Supplier Charley's Batch Time: 0254 Plant: 127724 Truck No.: 735 Ticket No.: 422049 Field Test Data Test Slump (in): Air Content Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Result Specification $ � 3-5 4.0 3-6 81 70 149.4 Sample Date: Sampled By: Weather Conditions: Accumulative Yards: Placement Method: Water Added Before (gal): Water Added After (gal): Sample Location: Placement Location: 04/28/17 Sample Time: 0359 Globe Engineers, Inc. Clear 2101350 Batch Size (cy): 10 Pump 0 0 Location #3 Pavement Fire Lane Driveway; & Parking Spaces @ E of building Laboratory Test Data Set Specimen Avg Diam. Area Date Age at Maximum Compressive No.Set ID (sq in) Received Date Tested Test (days)(lbs Load Strength Fracture 3 1 4.00 12.57 0505/ 3 ) � psi) Type 3 3 4.00 I2.57 05/05/17 7 40,650 3,230 1 3 4 4.00 3 12.57 05/26/17 28 5 4.00 3 6 12.57 45/26/17 28 4.00 3 7 12.57 05/26/17 28 4.00 12.57 06/23/17 56 Comments: Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Terracon Rep,: Globe Engineers, Inc. Reported To: Contractor: Report Distribution: (1) Northpoint Construction, Dihp Pranav (1) Northpoint Construction, Jamie t7gden (1) Kencarkey Interests LLC, JeremyHenicke Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM 01064, ASTM 01231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only appiicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CR000:. 11-16-12. Rev.6 Page 3 of 4 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Report Number: 94161112.0061 f �� Service Date: 04/28/17 con Report Date: 05/04/17 8901 Carpenter Fwy Ste 100 Task: Dallas, TX 75247-4547 214-630-1010 Re No:F-3272 Client Northpoint Construction Attn: Dilip Pranav 8530 Esters Blvd Irving, TX 75063 Project Fairfield Inn - Coppell TX Northpoint Dr at SH 121 Coppell, TX Project Number; 94161112 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: 5632 Supplier: Charley's Batch Time: 0446 Plant: 127724 Truck No.: 705 Ticket No.: 422059 Field Test Data Test Slump (in): Air Content (%): Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pef): Yield (Cu. Yds.): Laboratory Test Data Result Specification 5 3-5 3.9 3-6 81 70 148.8 Sample Date: Sampled By: Weather Conditions: Accumulative Yards: Placement Method: Water Added Before (gal) Water Added After (gal): Sample Location: Placement Location: 04/28/17 Sample Time: 0612 Globe Engineers, Inc. Clear 310/350 Batch Size (ey): 10 Pump 0 0 Location #4 Pavement Fire Lane Driveway; & Parking Spaces @ E of building Set Specimen Avg Diam. Area Date Date Age at Maximum Compressive No. ID (in) (sq in) Received Tested Test (days) Load (lbs Strength Fracture 4 4 1 3 4.00 12.57 05/01/17 3 42,000 (psi) Type 3,340 4 4.00 12.57 05/05/17 7 4 4 4.00 12.57 05/26/17 28 4 5 4.00 I2.57 05/26/17 28 4 6 4.00 12.57 05/26/17 28 4 7 4.00 12.57 06/23/17 56 Comments: Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Terracon Rep.: Globe Engineers, Inc. Reported To: Contractor: Report Distribution: (l) Northpoint Construction, Dilip Pranav (1) Kencarkey Interests LLC, Jeremy Henicke Reviewed By: (1) Northpoint Construction, Jamie Ogden Senior Project Materials Engineer Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessadiy indicative of the properties of other apparently similar or identical materials. CRE1001, 11-16-12, Rev.6 Page 4 of 4 - v'� f oda. �• --.� _—r—��„ � ���' w • W fi J g i � �.__S '4�" z.-� �` ti }v=im w �'+ 1r �4 �} • a!i s k� N'r j IV 47 G t• • 1 �'r • I ►• ,fit, ,tS' - r i �;`,�yl. *''^- ��„ice - a4 �.,,y,t” -M "�' y�y��� fi '•y -. `. • W.y.. r k t' • W F' r t. - T �Q', '� i axe � .•. �, � _ tie �.. .... a4r•0 Wa. ,e ..-. Yrli - L•+•i9 tl.T6 it Tbb.6CF ..k ut "mss,. -...v.,.�!C�.'uM-. itT.-�'"'4�Y �•,y��.s, "1� fit• � D mr r« 2 PC )A � tv T RRACQN REPORT NO.