Kyra Court-LR160815 (3)75247 Ro n e Engineering Texas 8908 Ambassador Row, Dallas, Engineering Firm Registration, No.o. F-1572-1572 Corporate Phone: (214) 630-9745 b� Report of Concrete Compressive Strength Test Client: JRose Architects Report No.: 14163323 2104 Cosmos Way Project No.: 1520637 Argyle, TX 76226 b Date of Service: 08/15/2016 Report Date: 09/13/2016 Project: Kyra Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. b Contractor: Concrete Supplier: Argos Plant: 123 Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 3" - 5" Air (%): 3-6% Test Method: ASTM C-172 (psi) ASTM C-31 (except 10.1.2) 12.57 ASTM C-143 4,470 ASTM C-231 12.57 ASTM C-1064 5,310 ASTM C-138 12.57 ASTM C-1231 5,150 A4TkA (--qQ Cylinder Marked Date Age Set No. Tested (days) 3 1 08/22/2016 7 3 2 09/12/2016 28 3 3 09/12/2016 28 3 4 09/12/2016 28 PROJECT DATA Mix Design I.D.: 1083 Placement Date: 08/15/2016 Weather Conditions: Cloudy Time Sampled: 10:27am Batch time: 09:39am Temperature -Air: 76°F Concrete: 86°F Truck No: 3339 Ticket No: 10900640 Air Content: 3.0% Unit Weight (pcf): NA Overall Placement Location: Paving, Kyra Court, Station 0+00 to 7+00, center line to curb Sample Location: Station 3+30, 10' south of center line REPORT OF TESTS Concrete Compressive Cylinder 4" x 8" Maximum Compressive Diameter Area Load Strength (in) in= (Ibs) (psi) 4.00 12.57 56,190 4,470 4.00 12.57 66,750 5,310 4.00 12.57 64,670 5,150 4.00 12.57 70,830 5,640 Average 5,360 Meafwed Slump (inches) 3.0 Fracture Type Type 4 Type Type 4 Type 4 b� b� b� LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (JC/JC) Page 5 of 8 b'� 75247 Ron E n 1'1 aori ng 8908 Ambassador Row, Dallas, -1572 Texas Engineering Firm Registration, No.o. F-1572 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Client: JRose Architects Report No.: 14163323 2104 Cosmos Way Project No.: 1520637 y' Argyle, TX 76226 Date of Service: 08/15/2016 Report Date: 09/13/2016 Project: Kyra Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. REPORT OF TESTS Concrete Compressive Cylinder 4" x 8" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength FractugO Set No. Tested (days) (in) (in=) (lbs) (psi:) Type 3 5 HOLD RF171 R[� [U R F][] 7 Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 b� LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (JC/JC) Page 6 of 8 9 8908 Ambassador Row, Dallas, TX 75247 Rn Engineering Texas Engineering Firm Registration, No. -F-1572 Corporate Phone: (214) %--,9745 Report of Concrete Compressive Strength Test Client: JRose Architects Report No.: 14163323 2104 Cosmos Way Project No.: 1520637 Argyle, TX 76226 Date of Service: 08/15/2016 Report Date: 09/13/2016 Project: Kyra Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Mix Design I.D.: 1083 Measured Concrete Supplier: Argos Placement Date: 08/15/2016 Slump Plant: 123 Weather Conditions: Cloudy (inches) Specification Requirements Time Sampled: 11:51am Batch time: 10:14am 4.0 Strength: 4,000 psi @ 28 days Temperature - Air: 78°F Concrete: 85°F Slump (in.): 3" - 5" Truck No: 3552 Ticket No: 10900647 Air (%): 3-6% Air Content: 3.0% Unit Weight (pcf): NA Test Method: ASTM C-172 Overall Placement Location: ASTM C-31 (except 10.1.2) Paving, Kyra Court, Station 0+00 to 7+00, center line to curb ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 Sample Location: ASTM C-1231 Station 1+60, 5' north of center line A.gTKA (3Q REPORT OF TESTS 4 Concrete Compressive Cylinder 4" x 8" b -LL Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) int (Ibs) (psi) Type 4 1 08/22/2016 7 4.00 12.57 52,210 4,150 Type 4' 4 2 09/12/2016 28 4.00 12.57 63,200 5,030 Type 4 4 3 09/12/2016 28 4.00 12.57 60,450 4,810 Type 3 4 4 09/12/2016 28 4.00 12.57 59,720 4,750 Type 4 Average 4,860 tram LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. Err./ M Page 7 of 8 y~'V Ione Engineering 0 8908 Ambassador Row, Dallas, TX 75247 Texas Engineering Firm Registration, No. F-1572 Corporate Phone: (214)-'9745 Report of Concrete Compressive Strength Test Client: JRose Architects Report No.: 14163323 2104 Cosmos Way Project No.: 1520637 Argyle, TX 76226 Date of Service: 08/15/2016 Report Date: 09/13/2016 Project: Kyra Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. REPORT OF TESTS Concrete Compressive Cylinder 4" x 8" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in') (lbs) (psi) Type 4 5 HOLD MIN1171 Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Technician: Raul Boisjoli Started: 06:30am Finished: 02:15pm Rone Engineering Report Distribution: Orig: JRose Architects (Argyle, TX) Attn: Mr. Jason Rose (1-ec copy) 1-ec Rone Engineering Project Managers Attn: Mr. Jason Creasy, CET Jason Creasy, CET Project Manager LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are - for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (JC/JC) Page 8 of 8 Ro n e Engineering b� 8908 Ambassador Row, Dallas, TX 75247 Texas Engineering Firm Registration, -1572 Corporate Phone: (214)) 630-9745 Report of Concrete Compressive Strength Test Client: JRose Architects Report No.: 14163323 2104 Cosmos Way Project No.: 1520637 , Argyle, TX 76226 Date of Service: 08/15/2016 b. 2 1 08/22/2016 7 4.00 12.57 54,330 Report Date: 09/13/2016 Project: Kyra Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring ' samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Mix Design I.D.: 1083 Measured Concrete Supplier: Argos Placement Date: 08/15/2016 Slur (inches) Plant: 123 Weather Conditions: Rain Specification Requirements Time Sampled: 09:57am Batch time: 08:48am 4.5 Strength: 4,000 psi @ 28 days Temperature -Air: 76°F Concrete: 86°F Slump (in.): 3" - 5" Truck No: 1000 Ticket No: 12401734 Air (%): 3-6% Air Content: 1.5% Unit Weight (pcf): NA b . Test Method: ASTM C-172 Overall Placement Location: ASTM C-31 (except 10.1.2) Paving, Kyra Court, Station 0+00 to 7+00, center line to curb ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 Sample Location: b ASTM C-1231 Station 5+10, 5' north of center line OCTAA r. -IQ REPORT OF TESTS Concrete Compressive Cylinder 4" x 8" 5,420 Cylinder Maximum Compressive b' Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) int (lbs) (psi) Type 2 1 08/22/2016 7 4.00 12.57 54,330 4,320 Type 4 2 2 09/12/2016 28 4.00 12.57 68,080 5,420 Type 3 2 3 09/12/2016 28 4.00 12.57 66,020 5,250 Type 3 2 4 09/12/2016 28 4.00 12.57 64,160 5,110 Type 3 Average 5,260 b� b� b14 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (JC/JC) Page 3 of 8 b'`� 6� 8908 Ambassador Row, Dallas, TX 75247 Texas Engineering Firm Registration, No. F-1572Rone Engineering Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Client: JRose Architects Report No.: 14163323 2104 Cosmos Way Project No.: 1520637 Argyle, TX 76226 Date of Service: 08/15/2016 *-"!e Report Date: 09/13/2016 Project: Kyra Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. REPORT OF TESTS Concrete Compressive Cylinder 4" x 8" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in=) (lbs) (psi) Type- 2 5 HOLD RF9 RE M R F111 7 Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 b0* h -V 9� LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (JC/JC) Page 4 of 8 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quauw- (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and repoAre for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (JC/JC) Page 1 of 8 004 8908 Ambassador Row, Dallas, 75247 Engineering Texas Engineering Firm Registration, -1572RVne Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strengthfest Client: JRose Architects Report No.: 14163323 2104 Cosmos Way Project No.: 1520637 Argyle, TX 76226 Date of Service: 08/15/2016 Report Date: 09/13/2016 Project: Kyra Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. b PROJECT DATA Contractor: Mix Design I.D.: 1083 Measured Concrete Supplier: Argos Placement Date: 08/15/2016 Slump Plant: 123 Weather Conditions: Rain (Inchfs) Specification Requirements Time Sampled: 07:44am Batch time: 07:00am 4.0 Strength: 4,000 psi @ 28 days Temperature - Air: 76°F Concrete: 85°F Slump (in.): 3" - 5" Truck No: 7102 Ticket No: 12302019 Air (%): 3-6% Air Content: 1.3% Unit Weight (pcf): NA Test Method: ASTM C-172 Overall Placement Location: ASTM C-31 (except 10.1.2) Paving, Kyra Court, Station 0+00 to 7+00, center line to curb ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 Sample Location: ASTM C-1231 Station 6+70, 5' north of centerline n.qTnn r. -'AQ REPORT OF TESTS Concrete Compressive Cylinder 4" x 8" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture* Set No. Tested (days) (in) in' (Ibs) (psi) Type 1 1 08/22/2016 7 4.00 12.57 59,430 4,730 Type 3 1 2 09/12/2016 28 4.00 12.57 75,920 6,040 Type 4 1 3 09/12/2016 28 4.00 12.57 70,900 5,640 Type 3� 1 4 09/12/2016 28 4.00 12.57 73,750 5,870 Type Average 5,850 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quauw- (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and repoAre for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (JC/JC) Page 1 of 8 004 �,� 8908 Ambassador Row, Dallas, -1572 75247 Texas Engineering Firm Registration, No.o. F-1572 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strengthrest Client: JRose Architects Report No.: 14163323 2104 Cosmos Way Project No.: 1520637 Argyle, TX 76226 Date of Service: 08/15/2016 Report Date: 09/13/2016 b" Project: Kyra Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. REPORT OF TESTS b. Concrete Compressive Cylinder 4" x 8" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (int) (lbs) (psi) Type 1 5 HOLD '+ RF�71K) ® F �r� Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 b� b� b� LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quor (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (JC/JC) Page 2 of 8