REPORT OF FIELD DENSITY TESTS
Security Fire Systems
196 S. Freeport Parkway
Coppell, Texas
REPORTED TO: Security Fire Systems, Inc.
196 Freeport Parkway
Coppell, Texas 75019
ATTN: Mr. Mike Alexander
REPORT NO. 13
REPORT DATE: 05-24-17
REG PROJECT NO. 21753
TECHNICIAN: J. Castaneda
PAGE: 1 of 2
CONTRACTOR: Trest Construction
Proctor
No.
ASTM
Standard
Description
Optimum
Moisture, %
Maximum
Density, PCF
1 D-698 Reddish brown clayey sand w/sandstone 12.2 109.9
2 D-698 Light brown sandy clay 13.5 110.5
3 D-698 Dark brown clayey sand 10.5 117.1
4 D-698 Reddish brown sandy clay 13.5 110.7
5 D-698 Red & light brown clayey sand 11.6 114.0
Test
No.
Date
Location
Depth
Below
Final S. G.
(feet)
Pocket
Pen
(tsf)
Field
Density
(pcf)
Field
Moisture
(%)
Proctor
ID
Compaction
Level (%)
90 05-08-17 Sanitary Line A: STA
00+60
11.0 3.5 106.3 16.3 2 96.2
91 Sanitary Line A: STA
00+61
10.0 3.75 107.2 15.9 2 97.0
92 Sanitary Line A: STA
00+62
9.0 3.75 106.5 16.1 2 96.4
93 Sanitary Line A: STA
00+63
8.0 3.75 107.8 15.7 2 97.6
94 Sanitary Line A: STA
00+64
7.0 4.0 108.2 16.0 2 97.9
95 Sanitary Line A: STA
00+65
6.0 3.25 105.9 15.5 2 95.8
96 Sanitary Line A: STA
00+66
5.0 3.5 106.5 16.2 2 96.4
97 Sanitary Line A: STA
00+67
4.0 3.75 107.7 14.8 2 97.5
98 Sanitary Line A: STA
00+68
3.0 3.75 108.1 14.9 2 97.8
99 Sanitary Line A: STA
00+69
2.0 3.75 107.5 15.3 2 97.3
REPORT NO. 13
REPORT DATE: 05-24-17
REG PROJECT NO. 21753
PAGE: 2 of 2
Test
No.
Date
Location
Depth
Below
Final S. G.
(feet)
Pocket
Pen
(tsf)
Field
Density
(pcf)
Field
Moisture
(%)
Proctor
ID
Compaction
Level (%)
100 05-08-17 Sanitary Line A: STA
00+70
1.0 3.75 106.9 16.0 2 96.7
101 Sanitary Line A: STA
00+71
0.0 3.75 107.8 16.1 2 97.6
102 05-09-17 Water Line: STA 3+01 3.0 3.5 106.3 16.0 2 96.2
103 Water Line: STA 3+02 2.0 3.25 105.9 15.9 2 95.8
104 Water Line: STA 3+03 1.0 3.75 108.0 14.9 2 97.7
105 Water Line: STA 3+04 0.0 3.75 107.9 15.5 2 97.6
106 Water Line: STA 2+00 3.0 3.5 106.9 16.0 2 96.7
107 Water Line: STA 2+01 2.0 3.75 107.5 15.0 2 97.3
108 Water Line: STA 2+02 1.0 3.75 107.6 15.2 2 97.4
109 Water Line: STA 2+01 0.0 3.75 108.2 14.9 2 97.9
Comments: Where tested, materials were in compliance with project specifications.
E-Mail
Distribution: (1) Security Fire Systems, Inc./
Mr. Mike Alexander
(1) GPF Architects, LLC/Mr. Greg Frnka
(1) Trest Construction/Mr. Gilbert Trevino
(1) City of Coppell/Mr. Matthew Mabry
(1) Trest Construction/Mr. Clement Wang
(1) Trest Construction/Mr. Eric Larsen
Submitted by:
REED ENGINEERING GROUP, LTD.
Registration Number F-3114
Bill Woolwine
Sr. Manager, CMT
BW/mg