Security Fire Systems-LR170606 2424 STUTZ DR.  SUITE 400  DALLAS, TX 75235  TEL [214] 350 5600  FAX [214] 350 0019 REPORT OF FIELD DENSITY TESTS Security Fire Systems 196 S. Freeport Parkway Coppell, Texas REPORTED TO: Security Fire Systems, Inc. 196 Freeport Parkway Coppell, Texas 75019 ATTN: Mr. Mike Alexander REPORT NO. 16 REPORT DATE: 06-06-17 REG PROJECT NO. 21753 TECHNICIAN: J. Castaneda PAGE: 1 of 1 CONTRACTOR: Trest Construction Proctor No. ASTM Standard Description Optimum Moisture, % Maximum Density, PCF 1 D-698 Reddish brown clayey sand w/sandstone 12.2 109.9 Test No. Date Location Depth Below Final S. G. (feet) Pocket Pen (tsf) Field Density (pcf) Field Moisture (%) Proctor ID Compaction Level (%) 150 05-25-17 Electrical Line: 35’N, 45’W(1) 2.0 3.5 105.5 14.1 1 96.0 151 Electrical Line: 34’N, 45’W(1) 1.0 3.75 106.8 13.4 1 97.2 152 Electrical Line: 33’N, 45’W(1) 0.0 3.75 106.7 13.2 1 97.1 153 Water Line A: STA 8+66 4.0 3.5 105.2 14.0 1 95.7 154 Water Line A: STA 8+65 3.0 4.0 107.8 12.9 1 98.1 155 Water Line A: STA 8+64 2.0 3.5 106.7 13.5 1 97.1 156 Water Line A: STA 8+63 1.0 3.5 105.9 14.3 1 96.4 157 Water Line A: STA 8+62 0.0 3.75 106.8 13.6 1 97.2 Comments: Where tested, materials were in compliance with project specifications. Footnotes: (1) Measurements referenced from NE building corner. E-Mail Distribution: (1) Security Fire Systems, Inc./ Mr. Mike Alexander (1) GPF Architects, LLC/Mr. Greg Frnka (1) Trest Construction/Mr. Gilbert Trevino (1) City of Coppell/Mr. Matthew Mabry (1) Trest Construction/Mr. Clement Wang (1) Trest Construction/Mr. Eric Larsen Submitted by: REED ENGINEERING GROUP, LTD. Registration Number F-3114 Bill Woolwine Sr. Manager, CMT BW/jm