Security Fire Systems-LR170606
2424 STUTZ DR. SUITE 400 DALLAS, TX 75235 TEL [214] 350 5600 FAX [214] 350 0019
REPORT OF FIELD DENSITY TESTS
Security Fire Systems
196 S. Freeport Parkway
Coppell, Texas
REPORTED TO: Security Fire Systems, Inc.
196 Freeport Parkway
Coppell, Texas 75019
ATTN: Mr. Mike Alexander
REPORT NO. 16
REPORT DATE: 06-06-17
REG PROJECT NO. 21753
TECHNICIAN: J. Castaneda
PAGE: 1 of 1
CONTRACTOR: Trest Construction
Proctor
No.
ASTM
Standard
Description
Optimum
Moisture, %
Maximum
Density, PCF
1 D-698 Reddish brown clayey sand w/sandstone 12.2 109.9
Test
No.
Date
Location
Depth
Below
Final S. G.
(feet)
Pocket
Pen
(tsf)
Field
Density
(pcf)
Field
Moisture
(%)
Proctor
ID
Compaction
Level (%)
150 05-25-17 Electrical Line: 35’N,
45’W(1)
2.0 3.5 105.5 14.1 1 96.0
151 Electrical Line: 34’N,
45’W(1)
1.0 3.75 106.8 13.4 1 97.2
152 Electrical Line: 33’N,
45’W(1)
0.0 3.75 106.7 13.2 1 97.1
153 Water Line A: STA 8+66 4.0 3.5 105.2 14.0 1 95.7
154 Water Line A: STA 8+65 3.0 4.0 107.8 12.9 1 98.1
155 Water Line A: STA 8+64 2.0 3.5 106.7 13.5 1 97.1
156 Water Line A: STA 8+63 1.0 3.5 105.9 14.3 1 96.4
157 Water Line A: STA 8+62 0.0 3.75 106.8 13.6 1 97.2
Comments: Where tested, materials were in compliance with project specifications.
Footnotes: (1) Measurements referenced from NE building corner.
E-Mail
Distribution: (1) Security Fire Systems, Inc./
Mr. Mike Alexander
(1) GPF Architects, LLC/Mr. Greg Frnka
(1) Trest Construction/Mr. Gilbert Trevino
(1) City of Coppell/Mr. Matthew Mabry
(1) Trest Construction/Mr. Clement Wang
(1) Trest Construction/Mr. Eric Larsen
Submitted by:
REED ENGINEERING GROUP, LTD.
Registration Number F-3114
Bill Woolwine
Sr. Manager, CMT
BW/jm