Security Fire Systems-LR170613 (3) 2424 STUTZ DR.  SUITE 400  DALLAS, TX 75235  TEL [214] 350 5600  FAX [214] 350 0019 CONCRETE CYLINDER TEST REPORT Security Fire Systems 196 S. Freeport Parkway Coppell, Texas REPORTED TO: Security Fire Systems, Inc. 196 Freeport Parkway Coppell, Texas 75019 ATTN: Mr. Mike Alexander REPORT NO. 24 REG PROJECT NO. 21753 SAMPLE DATE: 06-13-17 TECHNICIAN: D. Decuir PAGE: 1 of 1 CONTRACTOR: Trest Construction Location of Sample Set Number Location Quantity Represented (c.y.) 1 Piers: F-2, F-2.5 and F-3 9.5/38 Design Information Source of Concrete Mix Identification Specified Strength (psi) LMC 5150 3000 Test Results Set No. Cylinder ID Date Tested Age @ Test Total Load (lbs.) Compressive Strength (psi) Average Strength (psi) 1 2111 06-20-17 7 41670 3320 2111 07-11-17 28 56990 4540 2111 07-11-17 28 61160 4870 2111 07-11-17 28 57660 4590 4670 2111 Hold H Cylinder Data Set No. Cylinder ID Slump (inches) Time of Sample Air Temp. (°F) Concrete Temp. (°F) Air Entrainment (%) Unit Weight (lbs/ft3) Ticket Number 1 2111 5.0 9:33 AM 76 86 2.3 146.8 76839974 Note: (1) Concrete was sampled in accordance with ASTM C-31 (2) Concrete cylinders were tested in accordance with ASTM C-39 E-Mail Distribution: (1) Security Fire Systems, Inc./ Mr. Mike Alexander (1) GPF Architects, LLC/Mr. Greg Frnka (1) Trest Construction/Mr. Gilbert Trevino (1) City of Coppell/Mr. Matthew Mabry (1) Trest Construction/ Mr. Clement Wang (1) Trest Construction/Mr. Eric Larsen Submitted by: REED ENGINEERING GROUP, LTD. Registration Number F-3114 Cary Tipps Project Manager, CMT CT/cn