CONCRETE CYLINDER TEST REPORT
Security Fire Systems
196 S. Freeport Parkway
Coppell, Texas
REPORTED TO: Security Fire Systems, Inc.
196 Freeport Parkway
Coppell, Texas 75019
ATTN: Mr. Mike Alexander
REPORT NO. 34
REG PROJECT NO. 21753
SAMPLE DATE: 06-20-17
TECHNICIAN: J. Watson
PAGE: 1 of 1
CONTRACTOR: Trest Construction
Location of Sample
Set Number Location Quantity Represented (c.y.)
1 Grade beam: Dumpster pad 9.5/9.5
Design Information
Source of Concrete Mix Identification Specified Strength (psi)
LMC 5177 3000
Test Results
Set
No.
Cylinder
ID
Date Tested
Age @
Test
Total Load
(lbs.)
Compressive
Strength (psi)
Average Strength
(psi)
1 2415 06-27-17 7 30350 2420
2415 07-18-17 28 40470 3220
2415 07-18-17 28 48050 3820
2415 07-18-17 28 46500 3700 3580
2415 Hold H
Cylinder Data
Set
No.
Cylinder
ID
Slump
(inches)
Time of
Sample
Air
Temp.
(°F)
Concrete
Temp.
(°F)
Air
Entrainment
(%)
Unit
Weight
(lbs/ft3)
Ticket
Number
1 2415 5.5 12:43 PM 93 90 3.1 140.8 63016593
Note: (1) Concrete was sampled in accordance with ASTM C-31
(2) Concrete cylinders were tested in accordance with ASTM C-39
E-Mail
Distribution: (1) Security Fire Systems, Inc./
Mr. Mike Alexander
(1) GPF Architects, LLC/Mr. Greg Frnka
(1) Trest Construction/Mr. Gilbert Trevino
(1) City of Coppell/Mr. Matthew Mabry
(1) Trest Construction/
Mr. Clement Wang
(1) Trest Construction/Mr. Eric Larsen
Submitted by:
REED ENGINEERING GROUP, LTD.
Registration Number F-3114
Cary Tipps
Project Manager, CMT
CT/cn