Loading...
Prologis Park-CS170727 Halie Hernandez From:Matthew Mabry Sent:Thursday, July 27, 2017 7:06 AM To:George Marshall; Darryl Zbranek; Halie Hernandez Subject:FW: Pre punch list Prologis building 6 Matthew Mabry Engineering Construction Inspector City of Coppell, TX 214-406-5223 (cell) www.coppelltx.gov From: Matthew Mabry Sent: Wednesday, July 26, 2017 8:30 AM To: 'jpkinmonth@mycon.com' <jpkinmonth@mycon.com> Subject: Pre punch list Prologis building 6 Here is the pre punch list and will need to be completed before you have a final. Let me know if you have any questions 1.All fire hydrants need to be correct size 2.All manholes on site need to have stainless steel rain pans 3.Both vaults on site need to be above grade so water cannot drain into them 4.Domestic meter can needs to be 1 in above grade 5.Curb needs to be marked for domestic meter can with WD and painted blue 6.All grate inlets need to be cleaned and have swppp protection removed 7.FDC needs to be marked on curb 8.West side of building there is a valve that needs to be marked on curb 9.Fire lane needs to be painted 10.Southern part of building fire hydrant needs to face the fire lane 11.Where there are clean outs they need to be marked on curb CO and painted green 12.ADA inspection 13.Bonds for work done in city right of way 14.Vault along Freeport needs to be pumped out and make sure it is draining correctly 15.Irrigation meter needs to be pumped out and all fittings need to be visible inside the can 16.Irrigation meter needs to be marked on curb WI 1 Matthew Mabry Engineering Construction Inspector City of Coppell, TX 214-406-5223 (cell) www.coppelltx.gov 2