1000Royal_75019_31186 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT City:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-22082 Result: Passed Account Name : Shell Address of Assembly : 1000 Royal Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Reduced Pressure Principle Frequency :Annual Manufacturer :Watts Model No :009 Size :1/2 Serial No :A02360 Location At:rear of store What does this serve? Domestic Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Reduced Pressure Principle Assembly Pressure Vacuum Breaker Double Check Valve Assembly 1st check 2nd check Relief Valve Air Inlet Check Valve Held at 6.9 psid Closed Tight Leaked Held at 6.5 psid Closed Tight Leaked Opened at 2.1 psid Did not open Opened at psid Did not open Held at psid Leaked Repairs and Materials Used Test Results after Repair 1st check 2nd check Relief Valve Air Inlet Check Valve Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Opened at psid Held at psid Remarks : Test gauge used : Potable Make : Apollo Model : 40-200-TK5U Serial No. : 05141063 Date Tested for Accuracy : 7/11/2017 The above is certified to be true at the time of testing. Firm name : Allied Flow Specialists,Inc.Certified Tester : Christopher Coffman Firm Address : PO Box 1150 Certified Tester No. : BP0016261 Exp.Date : 11/25/2017 Firm Phone No : 972-723-5535 Test Date : 9/18/2017 *Test Records must be kept for at least three years. **Use only manufacturer's replacement parts. The following form must be completed for each assembly tested.