603AirlineDr_75019_31291 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT
City:Coppell
PWS I.D.:0570040
Address:816 S.Coppell Road
Coppell,Texas 75019
Phone:972-462-5150
Contact Person:Jerry Davis
Catalog No: TXTCOP-21243
Result: Passed
Account Name : Current water Customer
Address of Assembly : 603 Airline Dr
Address Type : Commercial
Inspection
The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be
operating within acceptable parameters.
Type of Assembly :Double Check Valve Frequency :Annual
Manufacturer :Beeco Model No :B645 Size :8 Serial No :9814225
Location At:vault in front of entry gate
What does this serve? FireLine
Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes
Reduced Pressure Principle Assembly Pressure Vacuum Breaker
Double Check Valve Assembly
1st check 2nd check Relief Valve Air Inlet Check Valve
Held at 2.2 psid
Closed Tight
Leaked
Held at 1.8 psid
Closed Tight
Leaked
Opened at psid
Did not open
Opened at psid
Did not open
Held at psid
Leaked
Repairs and Materials Used
Test Results after Repair
1st check 2nd check Relief Valve Air Inlet Check Valve
Held at psid
Closed Tight
Leaked
Held at psid
Closed Tight
Leaked
Opened at psid Opened at psid Held at psid
Remarks :
Test gauge used : Potable
Make : Midwest Model : 845-5-0029 Serial No. : 02170803 Date Tested for Accuracy : 2/8/2017
The above is certified to be true at the time of testing.
Firm name : Total Fire &Safety Certified Tester : Jerod Rogers
Firm Address : 7909 Carr Str Certified Tester No. : BP0011917 Exp.Date : 09/26/2019
Firm Phone No : 972-532-3369 Test Date : 9/16/2017
*Test Records must be kept for at least three years.
**Use only manufacturer's replacement parts.
The following form must be completed for each assembly tested.