Loading...
Freeport NIP(2.4)-CS 971216 ~?~ 304 ~547 l~/{~x¢~ t~J¢ CITY .~-? COPPE££ ~ CITY O~ COPPELL C::OFPELL U'~ZLZTZES DZV'ZSZGIq DATE: December i 6, 199? TO: Larry Davis, Construction Inspector FROM: Larry Smith, Utilities Division RE: Walk-thru for Deree Listed below are Street Division comments relative to walk thru. 1. Domestic meter needs 4" ~ipe over bottom cut-off and lid. 2. Need backflow %es~ for both vaults and both irt. & dom.meters. 3. 6" clean-out needs gluq inside and need~ proper olean-ou~ lid. 4. Fire hydrant in front o~ Royal Ln need~ correct markings on curb and ~aint main line =aive blue. 5. On fire hydrant near front door on ~outh side of building. Locate fire hydrant valve and gain~ red. 6. First fire hydrant north side of building,mark curb for valve. 7. Second fire hydrant northside needs an ~xtension on F.H.valve. 8. All valves that are not in ~avement need to be ~oured with concrete - not mortar. 9. Man-hole in middle of drive, south side needs to get chimney seal out of the bottom and reinstall. 10. Need to check plans to see where clean-out~ are. Locate sewer clean-out.