Loading...
NEW_135S_DentonTapRd_75019_38303 BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT Name of PWS:Coppell PWS I.D.:0570040 Address:816 S.Coppell Road Coppell,Texas 75019 Phone:972-462-5150 Contact Person:Jerry Davis Catalog No: TXTCOP-30292 Test Date: 1/19/2018 Result: Passed Reason for Test: New Account Name : Schlotzskys Address of Assembly : 135 S.Denton Tap Rd Address Type : Commercial Inspection The backflow prevention assembly detailed below has been tested as required by TCEQ regulations and is certified to be operating within acceptable parameters. Type of Assembly :Reduced Pressure Principle Frequency :Annual What does this serve? Domestic Manufacturer :Watts Model No :009QT Size :1/2 Serial No :373538 Location At:drive thru carbonator Is the assembly installed in accordance with manufacturer recommendations and/or local codes?Yes Is the assembly installed on a non-potable water supply (auxiliary)?No Reduced Pressure Principle Assembly Pressure Vacuum Breaker Double Check Valve Assembly 1st check 2nd check Relief Valve Air Inlet Check Valve Initial Test Date:1/19/2018 Time:9:30 AM Held at 7.2 psid Closed Tight Leaked Held at 7.3 psid Closed Tight Leaked Opened at 2 psid Did not open Opened at psid Did it fully open Yes No Held at psid Leaked Repairs and Materials Used ** Test After Repair Date: Time: Held at psid Closed Tight Leaked Held at psid Closed Tight Leaked Opened at psid Opened at psid Held at psid ***2nd check:numeric reading required for DCVA only Test gauge used: Potable Make: Wilkins Model: TG-5 Serial No.: 03090462 Date Tested for Accuracy: 4/15/2017 Remarks : Firm Name : BH Backflow Licensed Tester : Bruce Hardin Firm Address : P.O.Box 270115 BPAT License # : BP0012720 Firm Phone No : 214-502-7100 License Expiration Date : 12/07/2019 The above is certified to be true at the time of testing. * Test Records must be kept for at least three years.[30 TAC §290.46(B)] ** Use only manufacturer's replacement parts.