Gibbs Station 1-LR 920505 (3)ALPHA TESTING, INC.
2209 Wisconsin St., Suite 100
Dallas. Texas 75229
(214) 620-8911
REPORT OF FIELD
COMPACTION TESTS
TESTED FOR: HEATH & KNIGHT PROPERTIES, INC. DATE:
DALLAS, TEXAS
05/05/92
PROJECT:
GIBBS STATION
LAKES OF COPPELL
COPPELL, TEXAS
OUR REPORT NO.
92020-6A
TEST DATA:
Tr'ST DAT£ ~l-"rV. loll. ID OPTIMUM iN IBLACII IN PLAC'
NO. [ rjjpTfl ~J NUM.III MOl Ulll .... MOlITUlllqb IIY pCpOIENIITYCOMPACTiONP~'II CENT COMM B'NTe
20 05/05 SG 5 13.4 113.5 15.3 112 99 2-A
21 05/05 SG 5 13.4 113.5 14.8 112 99 2-A
22 05/05 SG 9 13.6 114.3 15.2 112 98 2-A
23 05/05 $G 9 13.6 114.3 15.4 110 96 2-A
24 05/05 SG 9 13.6 114.3 15.0 111 97 2-A
25 05/05 SG 9 13.6 114.3 15.0 111 97 2-A
26 05/05 $G 5 13.4 113.5 14.7 112 99 2-A
TEST LOCATION:
20 BLOCK C LOT 25 20' N. & 20' E. FROM S.W. CORNER
21 BLOCK C LOT 28 40' N. & 10' E. FROM S.W. CORNER
22 BLOCK C LOT 31 30' N. & 10' ~. FROM S.E. CORNER
23 BLOCK C LOT 34 40' N. & 20' E. FROM S.N. CORNER
24 ~LOCK C LOT 1 10' N. & 20' E. FROM S.W. CORNER
25 BLOCK C LOT 4 40' N. & 40' E. FROM S.W. CORNER
26 50' S. OF STREET $. OF BLOCK E LOT 16
1. FILL
2. NATURAL SUBGRADE
3. LIME STABILIZED
4.
A. TEST RESULTS COMPLY WITH SPECIFICATIONS
B. COMPACTION DOES NOT COMPLY WITH SPECIFICATIONS
C. MOISTURE DOES NOT COMPLY WITH SPECIFICATIONS
D. RETEST