Gunner P2-LR001011 TERRA-MAR, INC.
GEOTECHNICaL ENVIRONMENTAL AND MATERIALS ENGINEERS
DALLAS FORT WORTH HOUSTON LONGYIEW ,4USTIN
11050.4bles Lane, Dallas, Texas 75229 Phone:972-488-8800 Fax:972-488-8080
CONCRETE INSPECTION AND COMPRESSION TEST REPORT
DISTRIBUTION:
CLIENT: North American Communities Archon Group - Angie Rawe
PROJECT: Karrington Apartments North American Communities - Kurt Heinbecker
REPORT DATE: 10/11/00 C.D. Construction - Garreth Campbell
TMI REPORT It: DC00-040-098 Ciw ofCoppell - Greg Jones
SPECIFICATIONS PROJECT DATA
Strength (psi): 3000 Placement Date: 9/13/00
Slump (in.): 1 - ~ Sampled By: S. Adli
Air Content (%): 4 - 6 Weather: Cloudy
Concrete Temp (CF): 95 Supplier;Mix: TXI -: 8203
FIELD DATA: SET gl
Ticket #: 2733095 Time Batched: 8:42 AM Time Sampled: 9:20 AM
Slump (in.): 6 Air Content (%): 5 Unit Weight (pcf): N/A
Cone. Temp. (°F): 90 Ambient Temp. (°F): 88 Yardage (c.y.): 10.:20
Placement Location: Trash Compactor Slab
Sample Location: Trash Compactor Slab
Remarks:
CONCRETE COMPRESSION TEST RESULTS
CYLINDERS MOLDED AND CURED PER ASTM C3 I. TESTED PER ASTM C39. CAPPED PER ASTM C 1231
Set # Age Max Load Strength
Cylinder # lest Date Area (sq.in) Notes
1 (Days) (lbs) (psi)
091301 9/20/00 7 91600 28.27 3240
091302 10/11/00 28 118830 28.27 4200
091303 10/11/00 28 117730 28.27 4160
KAR
091304 Discard
(1) NOI~'~L.-kL CYLINDER SIZE 6" X 12", AREA 28.27 sq. in., UNLESS NOTED ABOVE.
(2) UNBONDED CAP SYSTEM USED L.~LESS OTHERWISE NOTED ABOVE.
(3) FIELD TESTS ARE PER APPLICABLE ASTM STAND.M1.DS: C138, C143, C172. C231
Page 1 of 1 CME Manager - Dallas
Note: This report is for the exclusive use of the client addressed. This report may not be reproduced except in its
entirety, without the written consent of TMI. Results apply only to above tests.