Loading...
ST0004-LR010806 (2) ~ GEOTECHNICAL, ENVIRONMENTAL AND MATERIALS ENGINEERS DALLAS FORT WORTH HOUSTON AUSTIN LONGVIEW 11050 Able$ In., Dallas, Texas 75229 phone: (972) 488-8800 fax:(972) ? Concrete Compression Test Report Client: The City of Coppell Report Distribution: (1) The City of Coppell Project: Freeport Parkway Pavement (1) Quantam Contracting Repair TMI Report No.: DC01-066-031 Report Date: 08/06/2001 Specifications Test Data Strength 4000 psi @ 28 Days Placement Date 07/30/2001 Slump 5 in max Sampled By 7uhair Shubbar Air Content 3 % min 6 % max Weather Clear Concrete Temperature n/a Supplier/Mix Hanson/9636 Ambient Temperature n/a Air Content Method ASTM C-231-B Ticket Number: 937301 Time Batched: 1:00 pm Time Sampled: 1:50 pm Slump: 6.5 in* Air Content: 4.8 % Unit Weight: n/a Concrete Temperature: 95° F Ambient Temperature: 99° F Yardage (c.y.): 70 of 110 Placement Location: Paving Sample Location: Station 15+50, North of Freeport Pkwy. An asterisk (') appears next to field data which does NOT meet specifications. Cylinder Age, Max Load Area Strength Fracture Set # # Test Date (days) (lbs. force) (sq.in.) (psi} Type 1 07300101 08/06/2001 7 97800 28.27 3460 unbonded cap 1 07300102 08/06/2001 7 101500 28.27 3590 unbonded cap 1 07300103 08/13/2001 14 1 07300104 08/13/2001 14 1 07300105 08/27/2001 28 I 07300106 08/27/2001 28 1 07300106 07/30/2001 Normal cylinder size: 6" x 12" Field and laboratory tests by TMI are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231. .... / TERRA-MAR, INC. ~//~dtt ¢. Pettit, P.~. Tho results prosente0 in this report pertain only to the specific items teste¢. This report was ~ro0uced fo~o oxclusivo use of the client. Any reproduction of this roport, or any part theroin, is strictly 0rohibitod without the expross wdtton consent of Page I of 2