Loading...
IAAM-LR 990921 (2) REPORT OF CONCRETE COMPRESSION TEST ALPHA TESTtNG, INC. 2209 Wisconsin St., Suite 100 ~ Dallas, Texas 75229 972/620-8911 - 972/263-4937 (Metro) FAX: 972/406-8023 TESTED FOR: FRANK DALE CONSTRUCTION, INC. DATE OF ~SSUE: 09/21/99 SOUTHLAKE, TEXAS PROJECT: 1AAM HEADQUARTERS BUILDING OUR REPORT NO.: 99571-52 COPPELL, TEXAS FIELD DATA LOCATION OF CONCRETE PLACEMENT P1ER NO. D-8.1 DATE PLACED 09/21/99 PLANT 31 TIME 12:20 DELIVER TICKET NO. 1417388 SLUMP (ASTM C-143) 6 MIX PROPORTIONS (SSD) AIR CONTENT (ASTM C-231 [] OR C-173 r"l) N/A CEMENT N/A AIR TEMPEI:~RTURE 91 WATER N/A CONCRETE TEMPERATURE 82 FINE AGGREGATE N/A DATE RECEIVED 09122/99 COARSE AGGREGATE N/A FIELD DATA SUBMITTED BY S.M./ ADMIXTURE N/A MIX DATA SUBMITTED BY SPECIMENS CAPPED Iff ACCORDANCE WITH ASTM C-&17~' OR C-1251 [] COMPRESSION TEST RESULTS E.(Cylinders made by ALPHA (NOMINAL CYUNDER SIZE 6' X 12') represenlative. (ASTM C-39) [] Cylinders made by A~chitect's o~ Cont~acto¢~ ;epre~en~.ative. LAB TYPE DATE AGE TOTAL AREA COMPRESSIVE [~ylindms picked up by ALPHA NO. CURING TESTED DAYS LOAD STRENGTH, PSI laboratory. 69 LAB 09/28/99 7 88,009 28.27 3,110 [] Cylinders delivered to ALPHA 70 LAB 10/19/99 28 28.27 laborao~. 71 LAB 10/1 g/99 28 28.27 I-I Compression test results comply with 72 LAB HOLD H 28.27 applicable specifications. D Compression lest resulls do not comply with applicable specifications. [] Specifications 28 3,000 R ~/~ul~bmitted REMARKS: 'I~.PH~"~T IN G, INC. Geotechnical Engineering · ConsfTuction Materials Testing · Environmental Engineering · Consutflhg