IAAM-LR 990921 (2) REPORT OF CONCRETE
COMPRESSION TEST
ALPHA TESTtNG, INC.
2209 Wisconsin St., Suite 100 ~
Dallas, Texas 75229
972/620-8911 - 972/263-4937 (Metro)
FAX: 972/406-8023
TESTED FOR: FRANK DALE CONSTRUCTION, INC. DATE OF ~SSUE: 09/21/99
SOUTHLAKE, TEXAS
PROJECT: 1AAM HEADQUARTERS BUILDING OUR REPORT NO.: 99571-52
COPPELL, TEXAS
FIELD DATA
LOCATION OF CONCRETE PLACEMENT P1ER NO. D-8.1
DATE PLACED 09/21/99 PLANT 31
TIME 12:20 DELIVER TICKET NO. 1417388
SLUMP (ASTM C-143) 6 MIX PROPORTIONS (SSD)
AIR CONTENT (ASTM C-231 [] OR C-173 r"l) N/A CEMENT N/A
AIR TEMPEI:~RTURE 91 WATER N/A
CONCRETE TEMPERATURE 82 FINE AGGREGATE N/A
DATE RECEIVED 09122/99 COARSE AGGREGATE N/A
FIELD DATA SUBMITTED BY S.M./ ADMIXTURE N/A
MIX DATA SUBMITTED BY
SPECIMENS CAPPED Iff ACCORDANCE WITH ASTM C-&17~' OR C-1251 []
COMPRESSION TEST RESULTS E.(Cylinders made by ALPHA
(NOMINAL CYUNDER SIZE 6' X 12') represenlative.
(ASTM C-39) [] Cylinders made by A~chitect's
o~ Cont~acto¢~ ;epre~en~.ative.
LAB TYPE DATE AGE TOTAL AREA COMPRESSIVE [~ylindms picked up by ALPHA
NO. CURING TESTED DAYS LOAD STRENGTH, PSI laboratory.
69 LAB 09/28/99 7 88,009 28.27 3,110 [] Cylinders delivered to ALPHA
70 LAB 10/19/99 28 28.27 laborao~.
71 LAB 10/1 g/99 28 28.27 I-I Compression test results comply with
72 LAB HOLD H 28.27 applicable specifications.
D Compression lest resulls do not comply
with applicable specifications.
[]
Specifications 28 3,000 R ~/~ul~bmitted
REMARKS: 'I~.PH~"~T IN G, INC.
Geotechnical Engineering · ConsfTuction Materials Testing · Environmental Engineering · Consutflhg