Freeport NIP(7.2)-LR000718 GEOTECHNICAL AND G F=~ I-1 I I F== ENVIRONMENTAL CONSULTANTS CONCRETE CYLINDER TEST REPORT Freeport V Royal Lane and Creekview Coppell, Texas REPORTED TO: Duke-Weeks Realty Corporation REPORT NO. 35 5495 Beltline Road, Suite 360 REG PROJECT NO. 6591 Dallas, Texas 75240 SAMPLE DATE: 07-18-00 ATTN: Mr. Paul Brown TECHNICIAN: D. Williams CONTRACTOR: Hill & Wilkinson, Inc. Location of Sample Set Number I Location I Quantity Represented I 1 Piers: C-9, L-8, C-7, C-6, C-5, C-4, C-3, C-2 10/20 I Design Information I Source of Concrete I Mix Identification I Specified Strength p.s.i. I I IA'I-I-IMORE 53 3000 I Test Results set I Cy,,nderI I Age I Total Load I Compress,veI Average No. ID Date Tested Test lbs. Strength p.s.i. Strength p.s.J. I 7679 07-25-00 7 91690 3240 7679 08-15-00 28 117760 4170 7679 08-15-00 28 121300 4290 4230 7679 Hold H Cylinder Data No. ID Slump Sample Air Temp. Temp. Entrainment Number 1 7679 5.25 10:40AM 89 93 NA 3108574 Distribution: (1) Duke-Weeks Realty Corporation/ Submitted by: Mr. Paul Brown (1) Hardy McCullah/MLM Architects/ REED ENGINEERING GROUP, INC. Mr. Norman Coates (1) TMBP - Consulting Engineers/ Original Signed By Mr. Frank Merritt (1) Pacheco Koch/Mr. Jim Koch Keith Atkins (1) Hill & Wilkinson, Inc./Mr. Steve Camp KEA/rt (1) City of Coppell/Mr. Lee Stone or Mr. Larry Davis 2424 STUTZ DR. · SUITE 400 · DALLAS, TX 75235 · TEL [214] 350 5600 · FAX [214] 350 0019