---- - Concrete Compression Test Report
Client: The City of Coppell Report Distribution: (1) The City of Coppell
Project: Freeport Parkway Pavement (1) Quantam Contracting
Repair
TMI Report No.: DC01-066-023
Report Date: 08/15/2001
Specifications Test Data
Strength 4000 psi @ 28 Days Placement Date 07/18/2001
Slump 5 in max Sampled By Zuhair Shubbar
Air Content 3 % min 6 % max Weather Clear
Concrete Temperature n/a Supplier/Mix Hanson/9636
Ambient Temperature n/a Air Content Method ASTM C-231-B
Ticket Number: 819405 Time Batched: 12:13 pm Time Sampled: 12:55 pm
Slump: 7.25 in* Air Content: 8.0 %* Unit Weight: n/a
Concrete Temperature: 95° F Ambient Temperature: 96° F Yardage (c.y.): 20 of 50
Placement Location: Paving
Sample Location: North Freeport Parkway at East side
An asterisk (*) appears next to field data which does NOT meet specifications.
Set # Cyl~der Age. Max Load Area Stren.qth Fracture
Test Date (days) (lbs. force) (sq.in.) (psi'j Type
1 07180101 07/25/2001 7 110810 28.27 3920 unbonded cap
I 07180102 07/25/2001 7 102810 28.27 3640 unbonded cap
1 07180103 08/01/2001 14 118300 28.27 4180 unbonded cap
I 07180104 08/01/2001 14 117730 28.27 4160 unbonded cap
I 07180105 08/15/2001 28 125080 28.27 4420
unbonded
cap
1 07180106 08/15/2001 28 135260 28.27 4780~' unbonded cap
28 day average 4600
Normal cylinder size: 6" x 12"
Field and laboratory tests by TMI are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or
,-,
The results presented in this report pertain only to the specific items tested. This report was produced for the exclusive use of the client. Any reproduction of