Loading...
Freeport NIP(6)-LR 980713CONTRA CT INSPECTION SER VICE, Inc. 4305 Glenwood Ct. Granbury, TX 76049 (817) 246-8096 FAX (817) 246-5889 REPORT OF METAL DECK INSPECTION Project: Client: I Freeport North - Building 4 Coppell, TX Reed Engineering Group 2424 Stutz, Suite 400 Dallas, TX 75235 Drawings utilized: Report No: 9911-8 Attention: Keith Atkins Date of Service: 07-13-98 Page 1 of 1 REPORT OF INSPECTION Contract Document/AWS D 1.1-96 Locations/item inspected: Column line 1 to 5 and grid line L to T Discrepancies/comments: A visual inspection was conducted on the above referenced project with results as follows: * 1.) Deck support perimeter angle was found non-compliant due to joints not welded together. 2.) Steel deck was found to comply for: a.) weld pattern b.) puddle weld size c.) side lap screw installation Technician ~/Cfontract Inspection Service This report is for the exclusive use of our client and shall not be modified or reproduced without written approval from said client