Freeport NIP(7.4)-LR000824 T$IT 2502 Gravel Drive - Ft. Worth, TX 76118 817-589-9933 Date: August 24, 2000 Report of Built- Up Roof Inspection PROJECT: Freeport Building VI Coppell, TX GENERAL CONTRACTOR: H_ill & Wilkenson 800 Klien Rd. Suite 100 - Piano, TX 75074 CONTACT: Mike Worley 214-299-4300 Mob. 214-914-7854 ROOFING CONTRACTOR: Pinkston Hollar 2887 A W. Pioneer Pkwy. - Arlington, TX ROOFING FORF_~MAN: Scott Lockwood Mob. 817-401-0809 MANUFACTORER: Tamko System - Type I~ Asphalt - 4 ply with aggregate ballast Technical Information WEATHER CONDITIONS: Sunny AMBIENT TEMPERATURES: 84 to 101 FORECAST FOR NEXT DAY: Same SIZE OF CREW: 19 TIME: 7 to 4 pm ROOFING MATERIALS RECEIVED? No LABELS ATTACHED? Yes MATERIALS STORED AS REQL~IRED? Yes MATERIALS REJECTED ? No SPECIFIED TEMPERATURES: (Asphalt) Kettle: 500 + 25 degrees F. EVT (Application): 450 +25 degrees F. Kettle: 1:00 pm- 500 EVT: 1:30 pm- 460 DECK INSPECTED? Yes CRICKETS INSTALLED? No Location: NA AREA OF ROOF APPLICATION: E-G/13-17 Number of SQ's (SF X 100) placed this date: 140 SQ Was placement per specifications: Yes OPERATIONS INSPECTED: Installation of 1.6" Iso insulation was mechanicallv attached to the deck with 2 l/4"fasteners. Fourteen (14) in the corners, twelve (12) at the perimeter (eight feet into the field of the roof) and eight fasteners per 4' X 8' insulation board. Application of the 1/2" fesco insulation was as required. Staggered over the Iso seams and adhered in a solid mopping of hot asphalt. Cant strips were applied at the perimeter and around curbs, set in hot asphalt. Four (4) plies of Tamko fiberglass felts were applied in a lapping fashion., in a solid mopping of hot asphalt. Technidan: Carlos Williams Time: 12 to 4pm