PA0101-LR010803CONCRETE COMPRESSIVE STRENGTH TEST
8901 Carpenter Frwy,, Suite #100
Report Number: 94011093.0028 Dallas, Texas 75247
(214) 630-1010
Service D~01
Clien~'~tY of CoppeJ~,~rk~Recreation Rape,
[ Attn: Brad Reid ~' *~A
~ 732 DeForest
~[ CoppelITX77
Mat&rial Inform~ion
Specifi~ 3000 psi @ 28 Days 12:00pm Date Cast: July 26, 2001
Technician: Albert Garcia
Batch Time: 11:44am Plant: 41 Weather Conditions: Clear
Supplier: TXI Accumulative Yards: 10
Truck No: 110 Ticket No: 2947979 Placement Method: Direct discharge
Mix I.D. No.: 8272 Sample Locations: See placement location
Placement Location: Sidewalk: See attached sketch
Field Test Data
Test Result Specification Test Method
Slump, inches: 5.00 3-5 ASTM C-143
Air Content, %: 4.0 3-6 ASTM C-231
Concrete Temperature,o F: 92 ASTM C-1064
Ambient Temperature, o F: 90 ASTM C-1064
Plastic Unit Weight, pcf: ~,,1~ $/
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter Area ,~'~ ~~fll~f Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days)
1 1 6.00 28.27 jf~,, I1~,v 08/02/2001
I 2 6.00 28.27 ~ I/ 08/02/2001
Average 3,490
1 3 08/23/2001 28
1 4 08/23/2001 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
ASTM C-31, C-39, C-172, C-1231
Technician: Albert Garcia
Report Distribution: ~ring, Inc.
(1) city of Coppell - Parks & Recreation
(1) TLB Construction Reviewed by:
(1) city of coppell - Constr. Insp. ~ Eric J.~leveland, P.E.
Senior Project Engineer
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not bo reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 1 of 1