Gateway BP(2.1)-LR 981118 (2) -' Englaeerillg Cl. 9200 King Arthur Drive Dallas, Texas 75247-3610 Phone 214/631-4372 Fax 214/631-4380 CONCRETE COMPRESSION TEST REPORT Report No.: 123 JobNo.: 1598-0007 DateCast: 11/18/98 Project: Lucent Technologies - Phase I Specification: 3500 psi @ 28 days Location: Flume - North side of Building; 35' West from Quantity Represented: t 0/20/40 cu. yds. North East comer of Building Contractor: Sampled By: M. Boone Reported To: Catel!us - Robert, McCann By Order Of: ((~ x 12 Inch) Nominal Cylinder Size: Area-28.27 SQ. IN. Laboratory Number: 8529 Field Number: LIl11801 LIl11802 LIl11803 LIl111804 Test Date: 11/25/98 11/25/98 Maximum Load, LBS: 103100 102180 Age When Tested, Days: 7 7 28 28 Compressive Strength, PSI: 3650 3620 Average Strength, PSh 3640 Type Break: Conical (U.N.O.) Remarks: Method of Curing: Field 1 Days, Laboratory From 11/19 Transported By: M. Boone Temperature: Ambient 72 °F Mix 84 °F Air Content 5.0 % Slump 2.5 Inches Time of Sample: 11:00 (AM)/PM Pick-Up Charge: Yes X No Source of Concrete: Redi-Mix Mix Code: 908 Ticket Nc.. 15286 Fine Aggregate: Unit Weight PCF Coarse Aggregate: Water: Yield CF/CY Cement: Fly Ash: Admixture(s): Distribution: Cadence McShane GDA - Scott McCreary Haynes Whaley - Mark Thompson City of Coppell - Garreth Campbell Signed~"~ (~' (~ "~ t ?.,/I / q ~' Page I of 1 Test Methods: ASTM C 31. C 39, C 143, C 173, C 192, C 231 and C 1064