REPORT OF FIELD INSPECTION OF CONCRETE
TESTED FOR: ALAN GRIMES PROJECT:
ROGERS O'BRIEN CONSTRUCTION
11145 MORRISON LANE
DALLAS, TX 75229
G & K LALTNDRY PROCESSING
DATE:
February 03, 1999
OUR REPORT NO.: 337-80080-98
FIELD DATA: Concrete was a 3000 psi mix delivered by LATTIMORE.
NO. OF CONCRETE TEMPE~TURE,
SPECIMENS SUPPLIER TIME TRUCK TIME TRUCK YARDS OF AIR
SET NO. MADE TICKET NUMBER DISPATCHED UNLOADED CONCRETE SLUMP, IN CONTENT. % AIR CONCRETE__
147 4 6089448 06:30 am 06:45 am 80.0 4 2.0 45 58
148 4 608455 06:45 am 07:30 am 150.0 5 2.3 50 60
149 4 608463 08:00 am 08:10 am 210.0 4 1/2 2.0 52 64
LOCATION: BUILDING PAD
147 10' EAST & 5' NORTH FROM SOUTHWEST CORNER OF BUILDING
148 100' EAST & 15' NORTH FROM SOUTHWEST CORNER OF BUILDING
149 50' EAST & 40' NORTH FROM SOUTHWEST CORNER OF BUILDING
NOTE: APPLICABLE ASIM STANDARDS, UNLESS OTHERWISE INDICATED: MAKING TEST SPECIMENS: C31-~;'SLUMP: C143-~a;AIR CONTENT: C231-97; ~MPE~TURE: C10~3)
REMARKS: Observed the placement of 300.0 cubic yards of concrete.
TECHNICIAN: M. HERNANDEZ
cc: (1) ROGERS O'BRIEN (1) HALFF ASSOCIATES, INC.
(1) CITY OF COPPELL Attn:GARRETH CAMPBELL
THESE TEST RESULTS APPLY ONLY TO THE SPECIFIC SAMPLES TESTED AND MAY NOT BE INOICATIVE OF THE ENTIRE CONCRETE PLACEMENT.
REPORTS MAY NOT BE REPROOUCED, EXCEPT IN FULL, WITHOUT WRITTEN PERMISSION BY PROFESSIONAL SERVICE INDUSTRIES. INC.