Gateway BP(1.2)-LR 960620 (2)unmll
TlflgLB
GENERAL CONTRACTORS, INC.
Thursday, Jun~ 20, 1996
Mr. Kenneth Griffin, City
City of Coppell
255 Parkway Blvd.
Copl~ll, TX 75019
Re: Fritz Warehouse: 660 Cotton Rd. - Fly Ash in paving
Haws and Tingle General Contractors, Inc. ~ requests the use of flyash in concrete paving mix designs for
the approaches, parking and fire lanes for the referenced project. Attached is a letter from TXI's Michael
Caldarone, P.E. (a resident of Coppell) with the following information for your review and c, onsideration:
· A list of cities with their associated mix designs.
· Mix design 8272 a true 5 sack Type I cement reference design with break history.
· Mix designs 8204 and 9490 with break history to compare to 8272.
· A series of rq~rints with relevant paragraphs highlighted.
We also bring to your attention, while fly ash adds considerable improvements for hot weather concret~ placing,
this summer contractors and municipalities am faced with a mai cement shortage. The mills are producing at
maximum capacity. The use of fly ash conserves the cement reserves and will help reduce shortages. We have
used fly ash mix designs for years with good results and our finishers know and undc~ its properties.
In addition, we will he using a 4,000 psi mix design for all voldcular paving on this project. The developer elected
not to stabilize the subgrade and your ~nginecfing department has allowed a 4,000 psi mix design. We propose to
use 5.5 sacks of Type I ~t and ½ sack of Class C flyash, for the equivalent ofa 6 sack mix.
Should you have any specific questions regarding this request please contact either me or Mr. Caldarone at TXI at
(214) 647-6700. Michael will meet with you at your convenience, if noeded. We look forward to approval of fly
ash in our paving concrete mixes and providing a quality project in your fair city.
Sincerely,
Karl Mosor
Project Manager
cc: Kathy Rabuse - Gromatsky Duprec & Assucates Architect
Steve Williamson - Construction Manager - Catellus Development Corp.
909 West Magnolia Avenue, Suite 2 · Fort Worth, Texas 76104
817/921-5248 Metro 817/429-8310 · Fax 817/927-8586
TEXAS INDUSTRIES, INC.
June 17, 1996
Mr. Carl Mosier
Haws & Tingle
General Contractors, Inc.
909 W. Magnolia Suite 2
Fort Worth, TX 76104
RE: Fritz Companies Gateway Project, Coppell, TX
Dear Mr. Mosier:
Pursuant to your request, enclosed is a brief list of various municipalities in the greater
Dallas/Fort Worth area with specifications which allow for the inclusion of fly ash into concrete
mixtures. Additionally, fly ash is incorporated in nearly all Texas Department of Transportation
Class "P" paving applications.
Advantages of fly ash include increased compressive and flexural strengths, reduced
drying shrinkage, increased density and better control of heat development and strength under
hot weather conditions.
Enclosed is some industry related information on fly ash which we hope you find useful
along with a performance comparison of three different TXI mix designs. All three designs are
based on a 5.0 sack cement content. If you have any questions regarding this information, or if
we may be of further service, please feel free to call.
Sincerely,
TEXAS INDUSTRIES, INC.
Michael A. Caldarone, P.E.
Manager-Q.A./Q.C.
ENC.
June 17, 1996
CITY
Arlington, TX
Dallas, TX
Fort Worth, TX
Grand Prairie, TX
Piano, TX
Texas Department
of Transportation
'5490
g2o4
,zo4
9496
SPECIFICATION
Maximum 94 lb. cement replacement
Replace 1.0 lb. cement with 1.25 lb. fly ash
Fly ash permitted in all machine placed and slip formed paving
Maximum 20% cement replacement
Replace 1.0 lb. portland cement with 1.25 lb. fly ash
470 lb. (5.0sk) minimum cementitious content
Maximum 20% cement replacement
Replace cement with fly ash on a pound-for-pound basis
Maximum 20% cement replacement
Maximum 20% cement replacement
Replace 1.0 lb. Type I portland cement with 1.25 lb. fly ash
ITEM 421.2 Materials, (2) Fly Ash
"When fly ash is used, "cement" shall be defmed as "cement
plus fly ash". "Cement plus fly ash" shall be composed of Type
I, II or III portland cement and 20 to 35 percent fly ash by
absolute volume, except that for classes of concrete which are
specified to have less than five (5) sacks of portland cement per
cubic yard, the fly ash replacement of cement shall not exceed
25 percent by absolute volume of the specified cement content."
MIX # 8272
5.00SK ADMIX/AEA 1"CS
3000 PSI ~ 28 Days
PAVING
Maximum Coarse Aggregate Size: ASTM C 33
Maximum Water/Cement Ratio: 6.40 gal/sk .567 lb/lb
Minimum Cement Content per Cubic Yard: 5.00 sacks
Maximum Placement Slump: 4.0 inches
Admixture ASTM C-494: Type A or D
Air Entraining Agent ASTM C-260: 3% - 6%
1"- #4 Crushed Stone
MATERIAL QUANTITIES PER 1 CUBIC YARD AT S.S.D.
470 lbs. or 5.00 sacks ASTM C 150 Type I Cement
1840 lbs. ASTM C 33 1"- #4 Crushed Stone
1352 lbs. ASTM C 33 Concrete Sand
267 lbs. or 32.0 gallons of Water
2.0 to 4.0 oz/cwt of ASTM C-494 Type D
Specified Air Content: 3% - 6%
Placement Slump: 3.0 + or - I inches
MIX # 8204
470# ADMIX/AEA l"CS
3000 PSI ~ 28 Days
PAVING
Maximum Coarse Aggregate Size: ASTM C 33 1"- #4 Crushed Stone
Maximum Water/Cement Ratio: 5.g0 gal/sk .549 lb/lb
Minimum Cement Content per Cubic Yard: 5.25 sacks
Maximum Placement Slump: 4.0 inches
Admixture ASTM C-494: Type A or D
Air Entraining Agent ASTM C-260: 3% - 6%
MATERIAL QUANTITIES PER 1 CUBIC YARD AT S.S.D.
376 lbs. or 4.00 sacks ASTM C 150 Type I Cement
94 lbs. or 1.25 sacks ASTM C 618 Fly Ash
1840 lbs. ASTM C 33 1"- #4 Crushed Stone
1359 lbs. ASTM C 33 Concrete Sand
258 lbs. or 31.0 gallons of Water
2.0 to 4.0 oz/cwt of ASTM C-494 Type D
Specified Air Content: 3% - 6%
Placement Slump: 3.0 + or - 1 inches
MIX # 9490
5.00SK ADMIX/AEA 1"CS(1:1.25) 3000 PSI @ 28 Days
PAVING
Maximum Coarse Aggregate Size: ASTM C 33 1"- #4 Crushed Stone
Maximum Water/Cement Ratio: 5.57 gal/sk .522 lb/lb
Minimum Cement Content per Cubic Yard: 5.57 sacks
Maximum Placement Slump: 4.0 inches
Admixture ASTM C-494: Type A or D
Air Entraining Agent ASTM C-260: 3% - 6%
MATERIAL QUANTITIES PER 1 CUBIC YARD AT S.S.D.
376 lbs. or 4.00 sacks ASTM C 150 Type I Cement
118 lbs. or 1.57 sacks ASTM C 618 Fly Ash
1840 lbs. ASTM C 33 1"- #4 Crushed Stone
1334 lbs. ASTM C 33 Concrete Sand 258 lbs. or 31.0 gallons of Water
2.0 to 4.0 oz/cwt of ASTM C-494 Type D
Specified Air Content: 3% - 6%
Placement Slump: 3.0 + or - I inches
Date: o6/17/96
~l~t
~. ~te ~.
i o2/o8/96 38
2 o2/o9/96 4o
3 02/09/96 40
4 02/12/96 31
5 02/12/96 31
6 02/12/96 31
7 02/13/96 31
8 02/14/96 12
9 02/14/96 31
10 02/14/96 13
11 02/15/96 43
12 02/15/96 43
13 02/15/96 43
14 02/15/96 43
15 02/16/96 43
16 02/19/96 31
17 02/20/96 31
18 02/20/96 50
19 02/21/96 31
20 02/22/96 41
21 02/23/96 31
22 02/26/96 31
23 02/26/96 31
24 02/28/96 40
25 02/28/96 46
26 02/28/96 46
27 02/28/96 46
28 02/28/96 46
29 03/01/96 40
30 03/05/96 38
TEXAS INDUSTRIES, INC.
CONCRETE DESIGN EVALUATION
** Statistics Compiled From Independent Laboratory Test Specimens **
Mix No. E8272 Str~ 3000 psi @ 28 Days
28 Day Test Data
Temperature Placement Percent ....... 28 Day .......
Arab Con Slump of Air PSI 1 PSI 2 PSI Avg
78 68 4.5 4.8 4422 4599 4511
77 75 4.0 N/A 4950 5240 5095
76 71 5.0 N/A 4040 3860 3950
59 60 5.5 N/A 3800 4040 3920
52 61 5.5 5.0 4190 4620 4405
59 65 5.0 4.5 4280 4250 4265
51 63 5.5 5.0 3920 4060 3990
79 70 3.5 5.8 4100 4340 4220
68 64 5.5 N/A 3380 3610 3495
84 84 5.0 ~/A 3210 3420 3315
#/A 62 5.0 4.0 4170 4010 4090
N/A 65 5.5 4.8 3840 3550 3695
N/A 66 5.5 4.6 4080 3940 4010
N/A 65 6.0 4.4 3580 3490 3535
N/A 66 5.7 5.3 4450 4400 4425
73 76 3.5 N/A 4580 4990 4785
80 74 4.5 N/A 4340 4490 4415
N/A 65 5.2 3.5 3900 4030 3965
92 72 4.0 N/A 3730 4030 3880
82 77 4.2 5.0 4310 4160 4235
66 72 5.0 N/A 3940 4260 4100
77 78 4.0 4.0 4730 4610 4670
70 74 5.0 N/A 4400 4230 4315
N/A 61 4.0 5.4 4320 4360 4340
40 56 5.5 N/A 4440 4610 4525
38 55 6.0 ]/A 3870 4120 3995
39 56 7.5 N/A 3680 3760 3720
38 55 6.0 N/A 4130 4660 4395
N/A 73 2.2 4.4 4490 4710 4600
80 78 5.0 N/A 3430 3610 3520
*** Averages *** 66 68 4.9 4.7
4511
4803
4519
4369
4376
4358
4305
4295
4206
4117
4114
4079
4074
4035
4061
4107
4125
4116
4103
4110
4110
4135
4143
4151
4166
4159
4143
4152
4168
4146
Movin~
Avqof 3
4511
48O3
4519
4322
4092
4197
4220
4158
3902
3677
3633
3700
3932
3747
3990
4248
4542
4388
4087
4027
4072
4335
4362
4442
4393
4287
4O80
4037
4238
4172
Page: 1
177
290
180
240
430
30
140
240
230
210
160
29O
140
50
410
150
130
300
150
320
120
170
40
170
25O
80
530
220
180
COMMENTARY OF STATISTICAL EVALUATION OF CONCRETE DESIGN RESULTS.
Mix No. E8272
Strength 3000 psi @ 28 Days
Paragraph 5.5 of ACI 318-8g provides that as data becomes available during
construction, the amount by which {f'cr) must exceed the specified value of
{f'c) may be reduced, provided:
{a) 30 or more test results are available and average of test
results exceeds that required by Section 5.3.2.1, using a
standard deviation calculated in accordance with Section
5.3.1.1, or
(b)
15 to 29 test results are available and average of test
results exceeds that required by Section 5.3.2.1, using a
standard deviation calculated in accordance with Section
5.3.1.2.
The required average compressive strength has been calculated using a
standard deviation calculated in accordance with ACI 318-89 Section
5.3.1.1 or Section 5.3.1.2 and is the larger value of these calculations
f' = f'c + I 34(SD)
cr '
= 3000 + 1.34(00414)
= 3555
f!
= f'c + 2.33(SD) - 500
= 3000 + 2.33(00414) - 500
= 3465
SUMMARY OF STATISTICAL ANALYSIS
28 Day Test Data
Number of Tests .......................... 30
Maximum Value ............................ 5095 psi
Minimum Value ............................ 3315 psi
Range .................................... 1780 psi
Average Strength ......................... 4146 psi
Standard Deviation ....................... 414 psi
Required Average Strength to satisfy
minimum probability conditions of
ACI 318-89 Section 5.3.2.1 ............... 3555 psi
Design excess beyond code requirements.. 591 psi
])ate: 06/17/96
Test
No. Date
1 07/27/95
2 07/27/95
3 07/28/95
4 o8/o5/95
5 o8/o5/95
6 08/05/95
7 08/05/95
8 08/28/95
9 o8/28/95
10 08/29/95
11 08/2~/95
12 0~/14/95
13 09/14/95
14 09/15/95
15 09/15/95
16 10/09/95
17 10/11/95
18 lO/11/95
19 10/11/95
20 10/11/95
21 10/12/95
22 10/12/95
23 10/12/95
24 11/06/95
25 11/07/95
26 11/13/95
27 11/20/95
28 11/20/95
29 lZ/30/95
30 01/29/96
TEXAS INDUSTRIES, INC.
CONCRETE DESIGN EVALUATION '
** Statistics Compiled From Independent Laboratory Test Specimens **
Mix No. E8204
strength 3ooo
28 Day Test Data
Plant Temperature Placement Percent .......
No. Amb Con Slump of Air PSI 1
psi @ 28 Days
28 Day .......
psi2 psi Avg
Cum Movin~
Avg Avg of 3
12 87 91 1.7 4.5 5660 5530 5595
12 94 93 2.7 5.0 4450 4240 4345
31 83 96 5.0 5.3 3430 3330 3380
12 85 92 4.2 5.0 3980 3960 3970
12 91 94 4.2 5.0 3980 4100 4040
12 97 95 5.0 5.0 3540 3690 3615
12 98 95 5.5 5.1 3730 3650 3690
12 90 92 1.7 4.3 4920 5020 4970
12 97 95 2.0 4.5 4990 4870 4930
12 81 93 2.5 5.7 4530 4440 4485
12 87 95 1.7 5.0 4800 4710 4755
12 78 88 1.5 4.6 4680 4780 4730
12 84 85 2.7 4.7 4250 4280 4265
12 82 91 1.7 5.4 4460 4480 4470
12 85 92 3.5 5.1 5020 5110 5065
18 83 *79 4.0 N/A 4140 4270 4205
12 67 65 2.0 4.4 5080 5350 5215
12 70 -71 2.2 N/A 4430 4360 4395
12 82 83 1.5 4.5 4520 4160 4340
12 87 85 2.0 4.5 4100 4160 4130
12 80 N/A 2.0 N/A 5160 5120 5140
12 75 80 4.0 N/A 4170 4390 4280
12 80 83 2.5 W/A 4230 4110 4170
12 64 71 5.0 M/A 4010 39{)0 3955
18 70 71 5.0 N/A 4350 4080 4215
13 42 55 5.5 3.4 4670 4860 4765
47 73 71 6.0 5.7 4520 4900 4710
47 76 73 5.2 6.0 4540 4820 4680
13 72 70 5.0 N/A 4970 5270 5120
40 N/A 64 4.7 5.4 4000 3760 3880
5595
4970
4440
4323
4266
4158
4091
4201
4282
4302
4343
43?5
4367
4374
4420
4407
4454
4451
4445
4430
4463
4455
4443
4422
4414
4428
4438
4447
4470
4450
5595
4970
4440
3898
3797
3875
3782
4092
453O
4795
4723
4657
4583
4488
4600
4580
4828
4605
4650
4288
4537
4517
4530
4135
4113
4312
4563
4718
4837
4560
Page: 1
~e
130
210
100
20
120
150
8O
100
120
90
90
100
30
20
90
130
270
70
360
60
40
220
120
110
270
190
380
280
300
240
*** Averages *** 81 83 3.4 4.9
COMMENTARY OF STATISTICAL EVALUATION OF CONCRETE DESIGN RESULTS
Mix No. E8204
Strength 3000 psi @ 28 Days
Paragraph 5.5 of ACI 318-89 provides that as data becomes available during
construction, the amount by which {f'cr) must exceed the specified value of
(f'c) may be reduced, provided:
{a) 30 or more test results are available and average of test
results exceeds that required by Section 5.3.2.1, using a
standard deviation calculated in accordance with Section
5.3.1.1, or
(b)
15 to 29 test results are available and average of test
results exceeds that required by Section 5.3.2.1, using a
standard deviation calculated in accordance with Section
5.3.1.2.
The required average compressive strength has been calculated using a
standard deviation calculated in accordance with ACI 318-89 Section
5.3.1.1 or Section 5.3.1.2 and is the larger value of these calculations
: f' + 1.34(SD)
f'cr c
3000 + 1.34(00521)
3698
f'cr: f'c + 2.33(SD) 500
3000 + 2.33(00521) - 500
3714
SUMMARY OF STATISTICAL ANALYSIS
28 Day Test Data
Number of Tests .......................... 30
Maximum Value ............................ 5595 psi
Minimum Value ............................ 3380 psi
Range .................................... 2215 psi
Average Strength ......................... 4450 psi
Standard Deviation ....................... 521 psi
Required Average Strength to satisfy
minimum probability conditions of
ACI 318-89 Section 5.3.2.1 ............... 3714 psi
Design excess beyond code requirements.. 736 psi
TEXAS II~$TRIES, INC.
CONC~TE DESIGN EVALUATION
Date: 06/17/96 .~,** Statistics Compiled From Inde~ndent Laboratory Test Specimens **
~0~c~,~.~%_¢~6W~ ~ix No. E949028 DayStren~t~Test Data~ psi @ 28 Days
?est
No. Date
Page: 1
Plant Temperature Placement l~cent ...... 28 Day ....... Om Moving
~. t~b Con $lu~p of Air PSI 1 PSI 2 PSI Avg Avg Avg of 3 l~nge
1 05/10/95 25 69 73 3.5 5.5 4640 4900 4770 4770
2 05/10/95 25 69 72 3.0 5.0 3990 3770 3880 4325
3 05/10/95 25 72 70 2.5 5.0 4160 3880 4020 4223
4 05/10/95 25 69 72 3.5 5.5 4690 4350 4520 4298
5 05/10/95 25 79 76 4.0 4.5 5180 5180 5180 4474
6 05/11/95 12 68 67 2.5 5.5 3648 4280 3964 4389
7 05/12/95 13 76 72 5.0 N/A 5800 5830 5815 4593
8 05/18/95 12 82 79 2.5 6.1 4520 4520 4520 4584
9 05/19/95 12 84 79 2.7 6.1 4690 4710 4700 4597
10 05/22/95 12 81 79 2.7 6.3 4730 4720 4725 4609
11 '05/25/95 12 74 80 4.0 3.0 5810 5830 5820 4719
12 05/26/95 12 80 82 2.7 6.2 4120 4140 4130 4670
13 05/30/95 12 80 83 2.7 5.9 4000 4040 4020 4620
14 06/01/95 12 92 89 3.0 3.5 3690 3740 3715 4556
15 06/02/95 12 89 88 3.0 4.0 3620 3660 3640 4495
16 06/05/95 12 83 88 2.7 5.6 4460 4430 4445 4492
17 06/06/95 12 95 96 4.0 4.5 3890 '3860 3875 4455
18 06/08/95 12 90 92 3.0 6.2 3960 3900 3930 4426
19 06/09/95 12 93 92 2.5 N/A 4280 4200 4240 4416
20 06/12/95 12 85 83 1.5 4.2 5150 5090 5120 4451
21 06/13/95 12 94 92 3.7 6.0 3960 4260 4110 4435
22 06/14/95 12 90 96 2.2 3.7 4340 4070 4205 4425
23 06/16/95 12 91 93 3.0 4.7 4630 4650 4640 4434
24 06/16/95 12 91 80 3.0 5.1 4920 4330 4625 4442
25 06/19/95 12 88 91 3.5 3.9 4460 3970 4215 4433
26 06/21/95 12 96 94 2.7 N/A 4960 5320 5140 4460
27 06/22/95 12 93 94 4.7 4.6 4510 4470 4490 4461
28 08/10/95 38 N/A 93 5.0 N/A 4080 4110 4095 4448
29 08/10/95 38 N/A 98 6.2 N/A 3600 3570 3585 4418
30 10/18/95 12 65 76 2.5 4.0 5740 6190 5965 4470
4770 260
4325 220
4223 280
4140 340
4573
4555 632
4986 30
4766
5012 20
4648 10
5082 20
4892 20
4657 40
3955 50
3792 40
3933 30
3987 30
4083 60
4015 80
4430 60
4490 300
4478 270
4318 20
4490 590
4493 490
4660 360
4615 40
4575 30
4057 30
4548 450
*** Averages *** 83 84 3.3 5.0
COMMENTARY OF STATISTICAL EVALUATION OF CONCRETE DESIGN RESULTS
Mix No. E9490
Strength 3000 psi g 28 Days
Paragraph 5.5 of ACI 318-89 provides that as data becomes available during
construction, the amount by which (f'cr) must exceed the specified value of
{f'c)'may be reduced, provided:
(a) 30 or more test results are available and average of test
results exceeds that required by Section 5.3.2.1, using a
standard deviation calculated in accordance with Section
5.3.1.1, or
(b)
15 to 29 test results are available and average of test
results exceeds that required by Section 5.3.2.1, using a
standard deviation calculated in accordance with Section
5.3.1.2.
The required average compressive strength has been calculated using a
standard deviation calculated in accordance with ACI 318-89 Section
5.3.1.1 or Section 5.3.1.2 and is the larger value of these calculations
f'cr: f'c + 1.34(SD)
3000 + 1.34(00637)
3854
fl
f'c + 2.33(SD) - 500
3000 + 2.33(00637)
3984
500
SUMMARY OF STATISTICAL ANALYSIS
28 Day Test Data
Number of Tests .......................... 30
Maximum Value ............................ 5965 psi
Minimum Value ............................ 3585 psi
Range .................................... 2380 psi
Average Strength ......................... 4470 psi
Standard Deviation ....................... 637 psi
Required Average Strength to satisfy
minimum probability conditions of
ACI 318-89 Section 5.3.2.1 ............... 3984 psi
Design excess beyond code requirements.. 486 psi
P. 02
JUN-*~t-199~ 12:20 ~,,~X.clS INDUSTRIES, [NC. ~
#TX # ~ Se4# ADI4IX/AEA i"C$ 4000 PSi I ~I Days
HATER]AL QIIKriTXES PER t CUBIC YARD AT
451 lbs, or 4.00 sacks AST# C ZSO Type [_Cemnt
113 lb$. or 1.$! sacks ASTHC $18 £1y Ash
1040 lbs. ~ 33 l"- #4 Crushed Stone
12H lbs. 33 Concrete Sand
to 4°0 oz/cwt of ASO4C-4~4 Type O
p1Kment SlW: 4.O
NIX t et74 e,oos~ AmXX/A~A ~"CS 4O0O PSI I # De~,
Nixtmum Coarse ~mar~te Stze: ASTI4 C 33 l"- #4 Cmshed Stone
I~xtmmlMiblr/~t'Ratiot $.!? g~l/sk .457 lb/lb
#tntmm~t Content ~er Cubtc Yard: $.00 sacks
Ih~tmPlicpnt $1Lmq). 5.0 tn~hes
Adltxtum ASTIIC-4~: Type A or D
Air Entr&Snln9 AgenL AS.TI4 C-f§O: .~f, - Gl,
MATERIAL (MMITZTIES PER 1 CUBIC YARD AT S.S.D.
tl~O lbs. or 6.00 sacks ASTN C 150 Type ]; Cement,
lbs. MT# C 33 I"- g4 Crushed Storm
X~gS lbs. M?R C 33 Concrete Sind
268 lbs. or 31.0 glllons of Water
~.o to 4.0 az/cut o~ AST~ (:-4t4 TM1M D,
Specified Air Content: 3%- 6%
PllemlmfltSlmlp; 4.0 + or - I tncims
~:O'd O£O'ON 00:91:
96, TI: NI'IC
98q8-Z~;6-ZT8: dI
aTSUTl ~ sm'eH
INDUSTRIES, I~C. ~,~ ~.~
"* 9titiKlel C~I)U,M ~ Ut~ XJbox'mtexy Yeet SFeolmmm
3,5 6,0
S,O $,$ ,lilt
$,0 9.4
4,7 5.8
4.0 6.6
4.7 5,3 4~
4,0 N/A
s.o 54 ~
3.5 4.~
5,0 5,7
4,0 4.1
4.8 3,5 4~
S,O i.O
4,6 3.6
4.6 4.8
4.3 Ill
4.0 4,1 4~
6.2 4.4
~.0 4.6 ~XO
4,7 5,7 47~
3.5 ~.2 4910
4.1 4.8
4.4
6NO 53# 34*7
4~ ~ m
£O'd O£O'ON T0:9$
96, T~ Nn£
98c;8-Z~6-/_T8: (II
alBUTl ~ smell
JU1~1-1996 12:22 ,..~TEX~ I~IDU~TRIE~, INC. ~ P.II4
~ix No. K0~74
Streng%h 4000 psi e ~ Deys
Par&graph 5.5 of ACI 318-89 provtd~s thaL as dit& becmus avitleb~e dlrgll
construction, the amunt by ~tch (F'c~) mst exce~ ~he s~tfted ve~ ~
fi'c) ~ be ~educed, provided:
(a) 30 or Bore test results are avail&bio and ivories of tnt
results exceeds this required by Sectton S.3.2.~ ,l~lq I
5.3.1.1, or
Cb)
lB to Zg test results ate ivlt]lb]e and ivirlp of tilt
results oxc~d~ that re~trld ~ Sec~ton 5,3,~.1, using a
standlrd devtltlon c&lc:ullted in ~ccordaflcu wtth SectJoa
Tho requtrid average coupre, tvt stre~th his been caJClllitll(I
stindard deviation cl~cu~ited tfl accor(Lince utah ~Cl
6.3.1,1 or Sectton 6.3.1,2 and ts the llrger value of those calculMtem
f'cr" f'c +
= 400o, l.z4(oo~ie)
- 4S]~
f'cr" r'c + p~.33(so) - soo
. 400o + z.3~(oo~N). SM
- 43J<)
SUIt4A~Y OF STATI$I/~L ANALYSIS
28 Dly Test Data
Nuuber of Tests ..... ....... ..... ......... 30
gtxtlm vl~ua... ........... .... ...... .... ~ND
#tnlmmVi~ue ............................ 4Jos
R~nge lieS pst
Av~IM Strength,..
Roqutrid Aver&ge Streflg~h to $ittsfy
mtn~4~t~olO.~tmb/ltty condttlofls oF
AC.! Sictlon 6.3.~.1 ...............4iii
Ibstgn excess b.yond code ~equtrilents 447 pst
IzO'd O£O'ON 'I:0:91:
96, 'I:Z: NI']£
98S8-/_56-ZI8: dI
aI6U~.l ~ SmeH
~TUN~21-1996 12;~2 ~.,TEXRS INDUE;TRIES, II, C, ~ P,~
lflJit
*** AVII~IM #* ?4 ?O 4.! 4.4
am, ~ m.vbq
SO'd O<;'O'ON ~:0:9I
96, I~ NAt'
98q8-Z~:6-Z'[8: QI
alBuIl % SmeH
.~fi'-21-1996 12:23
~,,~,.,,TEXI~ [NDU~TR~ES~ [NC. ~
HlX NC), KGb00
StrengLh 4000 psi
Paragraph 6.6 of AC! 316-B9 provides that as data became ava~lakl~ during
constructtofl, the &aunt by whtch (f'cr) must exceed the simctfted val~e If
(f'c) my be reduced, provided;
(A) 30 or wore test results Ara available and averig~ of
results exceeds thit rt~tred by SectiOn 5.3,8,[, ultag A
StindA~l deviation calculated tn accordance wtth
5.3.1.1, or
(b)
results excmds that rely_Ired by Section 5.3.2.], ~ltml. ·
standard devtltton calculated tn accordance ~tth S~ctt~
s.3.t.a.
The required averag~ compressive strmtgth has been calculatlgl ~st_q I
S,3,I.] or Sectton 6.3.1.2 and ts t~ la,er value of these CllCtll~.tml
f'cr ' f'c +
' f"c * Z.33(SD) - ~
- 4000 + 2.33(00721) - SOO
· 6180
SUIeHARY OF STATISIL~AL ANALYSIS
~6 0~) Test DAta
Nuelmr of Tests .... .... .................. 30
gaxtmmVAlue, ...................... . ....
HtntINmVAlue ....,, ....... ,,,. ...........
Average Strength..... .....
Standard Devtltton ......... .......... .,.. 721 pst
Requtred AverAge StrenGth ~o
mlntll#liprobabiltt~condtttons eT
ACT ]18-~g Sectton 5.3,~.! ............... 5J60
Destgn excess beyond code ~qutrments 356
90'~
0£0' ON
gO:9T
96, Tg Nfl£
98q8-zg6-ZT8: (II
TOTI~L
aT6UTl ~
sm~H