RE: First Construction Review Comments for MacArthur Plaza fire lane and decal plans
Dear Mr. Vilbig:
The City of Coppell has received and reviewed the referenced plans and has the following comments
to offer:
1. Provide a coversheet with the next set of plans.
2. Show the radius at the locations shown.
3. Show the sidewalk away from the back of curb.
4. Provide 4" double reflective white buttons at 30" o.c. at both deceleration lanes.
5. Install markings and signage at the location shown for the deceleration lanes.
6. Check with the fire department concerning radii requirements for the fire lane.
7. Provide keyway to accommodate future paving at the location shown on the plans.
8. Remove details from paving plans. All paving and storm drainage must abide by City of
Coppell Standard Construction Details.
9. On the grading plan, provide % grade calculations at the locations shown. Also show the
transverse slope and longitudinal slope for the deceleration lanes.
10. Adjust the sewer manhole to grade at the northernmost driveway.
11. Show the 100 year hydraulic grade line for the storm sewer profiles.
12. Show the flow arrows on the drainage area map at the location shown on the plans.
13. Correct the note on the erosion control plan regarding the construction standards.
There are various other minor comments throughout the plans. Once these comments have been
addressed, the marked up plans along with two revised sets of plans should be resubmitted to the
City for review. If you should have any questions concerning these comments, please contact me
at 304-3682.