Loading...
WA9302-LR 960107 (3)'EOTECHNICAL E GEE Consultants, Inc. EI NVIRONMENTAL 2540 Glenda Lane · Suite 108 · Dallas, Texas 75229 · (214) 620-9791 · Fax (214) 620-9794 REPORT OF CONCRETE MIX INSPECTION Report Date: JallualqJ 7, 1996 Date Concrete Placed: December 29, 1995 Standard 6"x12" Client: City of Coppell Area 28.27 Square Inches Project: 6.0 Million Gallon Water Storage Tank concrete Report No.: 59 Contractor: Natgun Construction Project No.: 95-0196 Concrete Supplier and Plant: RediMix Concrete - Plant #1 Location of Placement: Dome Panels MATERIALS ~ ..../ ~h ~. INSPECTION DATA Description (Lbs./Cu. Yd) Mix Number: 685 Time Sample Batehe& 9:55 am Cement: Time Sampled: 10:25 am Fly Ash: Sample Location: Dome Panels 2B-l, 2A-l, 1A-I, 4A-I, 5A-l, 6A-1 Coarse Aggregate: Truck/Ticket No: 127/17215 Intermediate Aggregate: Temperature: Fine Aggregate: Ambient Range: 45°F Concrete Range: 52°F Admixtures: Slump Range (inches): 8~A'' 1 Weather Conditions: Partly Cloudy 2 Time Started: 8:00 am Added Water: Time Completed: 6:00 pm Sample Air Content (%): 3.5% Total Cubic Yards Placed: 10 C.Y. Required Strength (Lbs./sq.in.): 5,000 psi Specimen Measured Age Date Total Lead Compressive Strength Remarks Number Slump (in.) (Days) Tested (Lbs.) (Lbs./Sq.ln.) CWT 226 8%" 7 01/05/96 121,040 4,280 CWT 227 8%" 28 01/26/96 CWT 228 8~h'' 28 01/26/96 CWT 229 8%" Hold Hold Test Methods Utillzal Fracture Regular Cylinders Made By: W.I. ASTM C-31,C-39,C-143 (Unless Noted Otherwise) Rcmarlm and/or DLstfibutiom Note: Slump before super plasticizer was 41/~" co: Mr. Larry Davis - City of Coppell Mr. Bob Barbarisi, Jr. - Natgun Corporation Mr. Gary Hendricks - ShimeL Jacobs and Finklea ~ ~ hie. Reviewed by:/~ ~